ABB Modbus register maps

Updated 28 October 2026

9 ABB models, 736 registers in all, each re-typed from ABB’s own free documentation and checked against it.

9 of 9 shown

ABB: default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
ACH580 HVAC drive (embedded Modbus RTU)RTU119200 baud, 8E1CDABModicon58
ACQ580 water and wastewater drive (embedded Modbus RTU)RTU119200 baud, 8E1CDABModicon53
ACS355 machinery drive (embedded Modbus RTU)RTU19600 baud, 8N116-bit onlyModicon55
ACS480 general purpose drive (embedded Modbus RTU)RTU119200 baud, 8E1CDABModicon52
ACS580 general purpose drive (embedded Modbus RTU)RTU119200 baud, 8E1CDABModicon58
ACS880 industrial drive, primary control program (embedded Modbus RTU)RTU119200 baud, 8E1CDABModicon64
EQ meter B21 (Modbus RTU)RTUNot stated-ABCDhex 0-based95
EQ meter B23 / B24 (Modbus RTU)RTUNot stated-ABCDhex 0-based149
M4M 20 / M4M 30 network analyzerRTU/TCPNot stated-ABCDhex 0-based152