 "manufacturer": "ABB",
 "manufacturer_slug": "abb",
 "model": "ACH480 HVAC drive (embedded Modbus RTU)",
 "model_slug": "ach480",
 "short_model": "ACH480",
 "aliases": [
  "ACH480-04",
  "ACH480 HVAC control program"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.",
 "summary": "ABB's compact HVAC variable frequency drive with a built-in RS-485 port that speaks Modbus RTU (as well as BACnet MS/TP and N2). The first six holding registers carry the control word, two references, status word and two actual values; every parameter is also a holding register derived from its group and index. This map covers the cyclic block, the error registers, key 01/04/05 monitoring parameters, the comm-loss settings and the main 32-bit actual values.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual uses 6-digit references 400001-465536 for the 65536 holding registers, so 400001 = wire address 0. Masters limited to 5 digits can use 40001-49999 for 400001-409999; 32-bit parameter registers (420000+) need 6-digit or raw addressing. With 58.33 Addressing mode = Mode 0 (default) a 16-bit parameter gg.ii sits at 400000 + 100*gg + ii (e.g. 01.11 -> 400111, wire 110) and a 32-bit copy at 420000 + 200*gg + 2*ii (e.g. 01.07 -> 420214, wire 20213). Mode 1 uses 400000 + 256*gg + ii and Mode 2 uses 400000 + 512*gg + 2*ii; this map assumes Mode 0. 32-bit registers are listed CDAB, which assumes 58.34 Word order = LO-HI, the default."
 },
 "default_word_order": "CDAB",
 "firmware": "ACH480 HVAC control program, manual revision E",
 "source": {
  "title": "ACH480 HVAC control program firmware manual",
  "doc_number": "3AXD50000247134 Rev E",
  "revision_date": "2026-02-13",
  "url": "https://search.abb.com/library/Download.aspx?DocumentID=3AXD50000247134&LanguageCode=en&DocumentPartId=1&Action=Launch",
  "pages": "EFB setup pp. 263-265; register addressing pp. 267-268; control/status words pp. 270-275; start/stop sequence p. 279; holding register table p. 282; error registers p. 289; parameters 01/04/05 pp. 373-379; group 58 pp. 575-581; Additional parameter data (FbEq32) pp. 653-655, 681"
 },
 "notes": [
  "Registers 400001-400006 are the factory defaults of Data I/O 1-6 (58.101-58.106) and can be re-pointed; 400007-400014 are user-selectable via 58.107-58.114 and are not listed.",
  "Control and status word bits are shown for the ABB Drives profile (58.25 = 0, default). With the DCU profile (58.25 = 5) the words are passed through unconverted with a different bit layout (bit 0 STOP, bit 1 START, bit 2 REVERSE, bit 4 RESET...). In this HVAC program control-word bits 8 and 9 are reserved (no jogging).",
  "Reference/actual registers are signed 16-bit; 20000 corresponds to the value of 46.01 Speed scaling or 46.02 Frequency scaling (46.03 torque), so their engineering value depends on drive settings and is left unscaled here.",
  "32-bit registers follow 58.34 Word order; the default LO-HI sends the low word first (CDAB). With HI-LO the order becomes ABCD. Within each register the high byte is sent first.",
  "16-bit scaling is the manual's FbEq16 column (e.g. '10 = 1 V' -> scale 0.1); 32-bit scaling is the FbEq32 column in the Additional parameter data chapter. Parameters whose 16-bit scaling is 'See par. 46.xx' (01.01, 01.06, 01.07, 01.10, 01.14, 01.72-01.74) are listed only in their 32-bit form.",
  "Left out: 06.xx control/status words, 05.10 control board temperature (unit depends on a setting), 01.50-01.53 hour/day kWh logs, HVAC-specific groups (PID, multipump, override) and configuration parameters other than the comm-loss settings.",
  "58.16 Communication loss time (default 30.0 s, range 0.0-6000.0 s) is left out: its 16-bit scaling is printed as '1 = 1 s' while the 32-bit table gives '10 = 1 s', so the 16-bit integer's unit is unclear.",
  "Coils and discrete inputs also exist but are omitted.",
  "If 96.78 Legacy Modbus mapping is enabled (ACx550-style register numbering), the register layout changes and this map no longer applies."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "400001",
   "name": "Control word (EFB CW)",
   "description": "ABB Drives profile bits shown; DCU profile layout differs (58.25).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "OFF1_CONTROL: 1 = ready to operate, 0 = ramp stop (OFF1)",
    "1": "OFF2_CONTROL: 0 = emergency OFF, coast to stop",
    "2": "OFF3_CONTROL: 0 = emergency stop (OFF3 ramp)",
    "3": "INHIBIT_OPERATION: 1 = operation enabled (run), 0 = inhibit",
    "4": "RAMP_OUT_ZERO: 0 = force ramp output to zero",
    "5": "RAMP_HOLD: 0 = hold ramp",
    "6": "RAMP_IN_ZERO: 0 = force ramp input to zero",
    "7": "RESET: 0->1 = fault reset",
    "8": "Reserved",
    "9": "Reserved",
    "10": "REMOTE_CMD: 1 = fieldbus control; 0 = last CW/reference kept unless both are 0",
    "11": "EXT_CTRL_LOC: 1 = select EXT2, 0 = select EXT1",
    "12": "USER_0",
    "13": "USER_1",
    "14": "USER_2",
    "15": "USER_3"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "400002",
   "name": "Reference 1 (EFB Ref1)",
   "description": "Signed; 20000 = value of 46.01/46.02 scaling, type per 58.26.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "400003",
   "name": "Reference 2 (EFB Ref2)",
   "description": "Signed second reference; type and scaling per 58.27.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "400004",
   "name": "Status word (EFB SW)",
   "description": "ABB Drives profile bits shown; DCU profile layout differs (58.25).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "RDY_ON: ready to switch on",
    "1": "RDY_RUN: ready to operate (0 = OFF1 active)",
    "2": "RDY_REF: operation enabled",
    "3": "TRIPPED: fault",
    "4": "OFF_2_STATUS: 1 = OFF2 inactive",
    "5": "OFF_3_STATUS: 1 = OFF3 inactive",
    "6": "SWC_ON_INHIB: switch-on inhibited",
    "7": "ALARM: warning active",
    "8": "AT_SETPOINT: actual value at reference",
    "9": "REMOTE: 1 = remote (EXT1/EXT2), 0 = local",
    "10": "ABOVE_LIMIT: speed/frequency at or above supervision limit",
    "11": "USER_0",
    "12": "USER_1",
    "13": "USER_2",
    "14": "USER_3",
    "15": "Reserved"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "400005",
   "name": "Actual value 1 (EFB Act1)",
   "description": "Signed; 20000 = value of 46.01/46.02, type per 58.28.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "400006",
   "name": "Actual value 2 (EFB Act2)",
   "description": "Signed second actual value; type per 58.29.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "400090",
   "name": "Reset error registers",
   "description": "Write 1 to clear error registers 400091-400095.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Do nothing",
    "1": "Reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 90,
   "documented": "400091",
   "name": "Error function code",
   "description": "Function code of the last failed query.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 91,
   "documented": "400092",
   "name": "Error code",
   "description": "Detail code when exception 04h was returned.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "2": "Low/High limit exceeded",
    "3": "Faulty index (array parameter)",
    "5": "Incorrect data type",
    "101": "General error (65h)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 92,
   "documented": "400093",
   "name": "Failed register",
   "description": "Last register that failed to read or write.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 93,
   "documented": "400094",
   "name": "Last register written successfully",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 94,
   "documented": "400095",
   "name": "Last register read successfully",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "400103",
   "name": "01.03 Motor speed %",
   "description": "Motor speed in percent of synchronous speed.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "400108",
   "name": "01.08 Motor current % of motor nom",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "400109",
   "name": "01.09 Motor current % of drive nom",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "400111",
   "name": "01.11 DC voltage",
   "description": "Measured DC link voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "400113",
   "name": "01.13 Output voltage",
   "description": "Calculated motor voltage (AC).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "400115",
   "name": "01.15 Output power % of motor nom",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 117,
   "documented": "400118",
   "name": "01.18 Inverter GWh counter",
   "description": "Whole GWh through the drive; combine with 01.19 and 01.20.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "GWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 118,
   "documented": "400119",
   "name": "01.19 Inverter MWh counter",
   "description": "Whole MWh, rolls over into 01.18.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "400120",
   "name": "01.20 Inverter kWh counter",
   "description": "kWh part (0-1000), rolls over into 01.19.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "400124",
   "name": "01.24 Flux actual %",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "400162",
   "name": "01.62 Abs motor speed %",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 164,
   "documented": "400165",
   "name": "01.65 Abs output power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 165,
   "documented": "400166",
   "name": "01.66 Abs output power % motor nom",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "400401",
   "name": "04.01 Tripping fault",
   "description": "Hex code of the fault that caused the trip; 0 = none.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "400402",
   "name": "04.02 Active fault 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "400403",
   "name": "04.03 Active fault 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 405,
   "documented": "400406",
   "name": "04.06 Active warning 1",
   "description": "Hex code of the first active warning.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 406,
   "documented": "400407",
   "name": "04.07 Active warning 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 407,
   "documented": "400408",
   "name": "04.08 Active warning 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 410,
   "documented": "400411",
   "name": "04.11 Latest fault",
   "description": "Most recent stored (non-active) fault code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 411,
   "documented": "400412",
   "name": "04.12 2nd latest fault",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "400413",
   "name": "04.13 3rd latest fault",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 415,
   "documented": "400416",
   "name": "04.16 Latest warning",
   "description": "Most recent stored warning code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "400501",
   "name": "05.01 On-time counter",
   "description": "Days the drive has been powered.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 501,
   "documented": "400502",
   "name": "05.02 Run-time counter",
   "description": "Days the inverter has been modulating.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 503,
   "documented": "400504",
   "name": "05.04 Fan on-time counter",
   "description": "Cooling fan running time.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 510,
   "documented": "400511",
   "name": "05.11 Inverter temperature",
   "description": "Drive temperature as percent of fault limit.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5813,
   "documented": "405814",
   "name": "58.14 Communication loss action",
   "description": "Reaction to EFB communication loss.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No action",
    "1": "Fault",
    "2": "Last speed",
    "3": "Speed ref safe",
    "4": "Fault always",
    "5": "Warning"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5814,
   "documented": "405815",
   "name": "58.15 Communication loss mode",
   "description": "Which messages reset the comm-loss timer.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Any message",
    "2": "Cw / Ref1 / Ref2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20201,
   "documented": "420202",
   "name": "01.01 Motor speed used (32-bit)",
   "description": "Estimated motor speed; CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20211,
   "documented": "420212",
   "name": "01.06 Output frequency (32-bit)",
   "description": "Estimated output frequency; CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20213,
   "documented": "420214",
   "name": "01.07 Motor current (32-bit)",
   "description": "Measured motor current; CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20219,
   "documented": "420220",
   "name": "01.10 Motor torque (32-bit)",
   "description": "Percent of nominal motor torque; CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20221,
   "documented": "420222",
   "name": "01.11 DC voltage (32-bit)",
   "description": "CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20227,
   "documented": "420228",
   "name": "01.14 Output power (32-bit)",
   "description": "Unit follows 96.16 Unit selection (kW or hp); CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20307,
   "documented": "420308",
   "name": "01.54 Cumulative inverter energy (32-bit)",
   "description": "Signed total energy through the drive; CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20343,
   "documented": "420344",
   "name": "01.72 U-phase RMS current (32-bit)",
   "description": "CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20345,
   "documented": "420346",
   "name": "01.73 V-phase RMS current (32-bit)",
   "description": "CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20347,
   "documented": "420348",
   "name": "01.74 W-phase RMS current (32-bit)",
   "description": "CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21005,
   "documented": "421006",
   "name": "05.03 Hours run (32-bit)",
   "description": "Motor run time in hours; CDAB assumes 58.34 = LO-HI (default).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set 58.01 = Modbus RTU, point the start/stop and reference sources at the embedded fieldbus, then write the ABB Drives control word and Reference 1 at 400001/400002 and poll the status word and actual values at 400004-400006. Read further monitoring values from their parameter registers (400000 + 100*group + index).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Control word: start/stop/reset"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Reference 1 (speed/frequency setpoint, 20000 = 46.01/46.02)"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Status word: ready/running/fault/remote"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Actual value 1 (speed/frequency feedback)"
   },
   {
    "table": "holding_register",
    "address": 110,
    "why": "01.11 DC voltage"
   },
   {
    "table": "holding_register",
    "address": 400,
    "why": "04.01 Tripping fault code"
   },
   {
    "table": "holding_register",
    "address": 20211,
    "why": "01.06 Output frequency, 0.01 Hz (32-bit)"
   },
   {
    "table": "holding_register",
    "address": 20213,
    "why": "01.07 Motor current, 0.01 A (32-bit)"
   }
  ],
  "enable": "Set 58.01 Protocol enable = Modbus RTU, then 58.03 node address, 58.04 baud and 58.05 parity, and apply them with 58.06 Communication control = Refresh settings (or reboot). For control set 20.01 Ext1 commands (and 20.06 for EXT2) = Embedded fieldbus and the reference source, e.g. 22.11 Ext1 speed ref1 or 28.11 Ext1 frequency ref1 = EFB ref1. Save parameter writes permanently with 96.07 Parameter save manually.",
  "watchdog": "58.14 Communication loss action (No action by default / Fault / Last speed / Speed ref safe / Fault always / Warning) with 58.16 Communication loss time (default 30.0 s) and 58.15 Communication loss mode (default: only control word/reference writes reset the timer). A loss trips 6681 EFB comm loss or warns A7CE; 'Speed ref safe' runs at 22.41/28.41. There is a 30 s boot-up delay before monitoring starts.",
  "quirks": [
   "Addresses are 6-digit Modicon references: 400001 = wire 0. 32-bit parameter registers start at 420000 and cannot be reached with 5-digit (4xxxx) addressing.",
   "32-bit values in this map are listed CDAB, which assumes 58.34 Word order = LO-HI (default). If 58.34 is set to HI-LO, read them as ABCD.",
   "References and actual values are signed 16-bit with 20000 = the 46.01/46.02 scaling value, not engineering units.",
   "Only the lower 16 bits of the drive's 32-bit control/status words are visible at 400001/400004.",
   "Start (manual's sequence): write 1142 (0x476); when status bit 0 is 1 write 1150 (0x47E, ready/stopped), then 1151 (0x47F) to run. Stop: 1143 (0x477) per 21.03 Stop mode, 1150 OFF1 ramp stop, 1149 (0x47D) OFF2 coast, 1147 (0x47B) OFF3 emergency ramp. Fault reset: rising edge of control-word bit 7."
  ],
  "setup": [
   "Defaults: node 1, 19.2 kbit/s, 8 data bits, even parity, 1 stop bit (58.03-58.05); 58.04 can also be Autodetect.",
   "Changes to group 58 take effect only after 58.06 = Refresh settings or a control-unit reboot.",
   "58.07 Communication diagnostics flags parity, baud and addressing errors; 58.08-58.12 count packets and errors."
  ],
  "gotchas": [
   "The same RS-485 port also runs BACnet MS/TP or N2; 58.01 decides which protocol is active.",
   "If 96.78 Legacy Modbus mapping is enabled the drive uses ACx550-style register numbering and this map no longer applies.",
   "Exception 04h means the drive rejected the request; read 400092 Error code for the reason."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/abb/ach480",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}