 "manufacturer": "ABB",
 "manufacturer_slug": "abb",
 "model": "ACS550-01/U1 general purpose drive (embedded Modbus RTU)",
 "model_slug": "acs550",
 "short_model": "ACS550",
 "aliases": [
  "ACS550-01",
  "ACS550-U1"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.",
 "summary": "ABB's ACS550 general purpose drive has a built-in RS-485 port that runs Modbus RTU. Control bits and relay outputs are coils, status bits and digital inputs are discrete inputs, and all parameters plus the control/status words and references are 16-bit holding registers, with parameter NNNN at register 4NNNN. This map covers the control block, main operating data, fault and alarm words, fault history and the EFB set-up parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual states the drive uses zero-based Modbus addressing: holding register 40002 is sent as 0001 and coil 33 as 0032. So 40001 = wire 0, parameter NNNN = register 4NNNN = wire NNNN - 1 (e.g. 0103 -> 40103 -> 102); coils 00001-00016 are control-word bits, 00033+ relay outputs; discrete inputs 10001-10032 are status-word bits and 10033+ digital inputs; input registers 30001/30002 are AI1/AI2."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "ACS550-01/U1 User's Manual (0.75...160 kW / 1...200 hp)",
  "doc_number": "3AFE64804588 (3AUA0000001418) Rev H",
  "revision_date": "2014-07-04",
  "url": "https://search.abb.com/library/Download.aspx?DocumentID=3AFE64804588&LanguageCode=en&DocumentPartId=1&Action=Launch",
  "pages": "Complete parameter list (ranges, resolution, defaults) pp. 91-105; fault/alarm word bits p. 113; group 53 pp. 184-185; 9802 p. 201; EFB setup pp. 205-210; actual value scaling p. 211; Modbus technical data pp. 215-223 (zero-based addressing p. 216, coils/discrete inputs pp. 217-219, 4xxxx table pp. 219-221); ABB control profiles pp. 224-228"
 },
 "notes": [
  "All registers are 16-bit; there is no word order. Scaling uses each parameter's Resolution column, which the manual says multiplies the fieldbus integer (e.g. 0.1 Hz).",
  "40001/40004 work only with 5305 = ABB DRV LIM (default) or ABB DRV FULL; 40031-40034 only with the DCU profile. ABB DRV LIM ignores control word bits 4 and 10. The coil table labels ABB DRV LIM coil 00004 (bit 3) 'START' while the control-word table calls bit 3 INHIBIT OPERATION; it is the same bit.",
  "Discrete inputs 10001-10013 are listed with their ABB Drives profile meaning; with the DCU profile the same inputs carry DCU status bits (READY, ENABLED, STARTED, RUNNING...). Only 6 DI and 6 RO are listed; RO4-6 need the OREL-01 extension.",
  "Actual values 40005-40012 follow 5310-5317; 40005/40006 default to 0103 and 0104 according to the Modbus chapter, although the group 53 table lists 0 as the default of 5310-5317.",
  "Parity default is unclear: the parameter list gives 5304 default 0 (8 NONE 1) while the EFB setup table says selecting Modbus sets it to 1 (8 NONE 2). Read 5304 from the drive. 5303 baud (default 9.6 kbit/s) is left out because its fieldbus encoding is not stated.",
  "Left out: 0111 External ref 1 (Hz or rpm depending on 9904), PID, process-variable and energy-saving signals, fault time stamps 0402/0403, status/DI at fault, and the DCU REF registers 40045-40048, and input registers 30001/30002 (AI1/AI2 level 0-100 %, integer scaling not stated; use 0120/0121 instead).",
  "Exception 03 is returned for writes out of range, to read-only parameters, while started, or while a factory macro is selected."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 32,
   "documented": "00033",
   "name": "Relay output 1",
   "description": "Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "00034",
   "name": "Relay output 2",
   "description": "Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "00035",
   "name": "Relay output 3",
   "description": "Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "00036",
   "name": "Relay output 4",
   "description": "Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 36,
   "documented": "00037",
   "name": "Relay output 5",
   "description": "Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 37,
   "documented": "00038",
   "name": "Relay output 6",
   "description": "Always readable; forcing needs the drive configured for fieldbus control. RO4-6 need OREL-01.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "10001",
   "name": "Status bit 0: RDY_ON",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "10002",
   "name": "Status bit 1: RDY_RUN",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "10003",
   "name": "Status bit 2: RDY_REF",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 3,
   "documented": "10004",
   "name": "Status bit 3: TRIPPED",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "10005",
   "name": "Status bit 4: OFF_2_STA (active low)",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "10006",
   "name": "Status bit 5: OFF_3_STA (active low)",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "10007",
   "name": "Status bit 6: SWC_ON_INHIB",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "10008",
   "name": "Status bit 7: ALARM",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 8,
   "documented": "10009",
   "name": "Status bit 8: AT_SETPOINT",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 9,
   "documented": "10010",
   "name": "Status bit 9: REMOTE",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 10,
   "documented": "10011",
   "name": "Status bit 10: ABOVE_LIMIT",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 11,
   "documented": "10012",
   "name": "Status bit 11: EXT2",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 12,
   "documented": "10013",
   "name": "Status bit 12: RUN_ENABLE",
   "description": "ABB Drives profile (5305 = 0 or 2) meaning.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 32,
   "documented": "10033",
   "name": "DI1",
   "description": "Digital input state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 33,
   "documented": "10034",
   "name": "DI2",
   "description": "Digital input state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 34,
   "documented": "10035",
   "name": "DI3",
   "description": "Digital input state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 35,
   "documented": "10036",
   "name": "DI4",
   "description": "Digital input state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 36,
   "documented": "10037",
   "name": "DI5",
   "description": "Digital input state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 37,
   "documented": "10038",
   "name": "DI6",
   "description": "Digital input state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "Control word (ABB Drives)",
   "description": "Only with 5305 = 0 or 2; copy in 5319.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "OFF1 CONTROL: 1 = ready to operate, 0 = ramp stop",
    "1": "OFF2 CONTROL: 0 = emergency off, coast to stop",
    "2": "OFF3 CONTROL: 0 = emergency stop (2208)",
    "3": "INHIBIT OPERATION: 1 = operation enabled (needs run enable, 1601)",
    "4": "RAMP_OUT_ZERO (ABB DRV FULL only): 0 = force ramp output to zero",
    "5": "RAMP_HOLD: 0 = halt ramping",
    "6": "RAMP_IN_ZERO: 0 = force ramp input to zero",
    "7": "RESET: 0->1 = fault reset (1604 = COMM)",
    "8": "Unused",
    "9": "Unused",
    "10": "REMOTE_CMD (ABB DRV FULL only): 1 = fieldbus control enabled",
    "11": "EXT CTRL LOC: 1 = EXT2, 0 = EXT1 (1102 = COMM)",
    "12": "Unused",
    "13": "Unused",
    "14": "Unused",
    "15": "Unused"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "Reference 1",
   "description": "0...+/-20000 = 0...1105 REF1 MAX.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "Reference 2",
   "description": "0...+/-10000 = 0...1108 REF2 MAX.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "Status word (ABB Drives)",
   "description": "Only with 5305 = 0 or 2; copy in 5320.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "RDY_ON: ready to switch on",
    "1": "RDY_RUN: ready to operate",
    "2": "RDY_REF: operation enabled",
    "3": "TRIPPED: fault",
    "4": "OFF_2_STA: 1 = OFF2 inactive",
    "5": "OFF_3_STA: 1 = OFF3 inactive",
    "6": "SWC_ON_INHIB: switch-on inhibit active",
    "7": "ALARM",
    "8": "AT_SETPOINT: actual equals reference",
    "9": "REMOTE: 1 = EXT1/EXT2, 0 = local",
    "10": "ABOVE_LIMIT: supervised value above limit (group 32)",
    "11": "EXT CTRL LOC: 1 = EXT2 selected",
    "12": "EXT RUN ENABLE received",
    "13": "Unused",
    "14": "Unused",
    "15": "Unused"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "Actual 1",
   "description": "Default copy of 0103 output frequency (5310); 0.1 Hz with the default.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "Actual 2",
   "description": "Default copy of 0104 current (5311); 0.1 A with the default.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "40031",
   "name": "DCU control word LSW",
   "description": "Only with 5305 = 1 (see 0301).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "40032",
   "name": "DCU control word MSW",
   "description": "Only with 5305 = 1 (see 0302).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "DCU status word LSW",
   "description": "Only with 5305 = 1 (see 0303).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "40034",
   "name": "DCU status word MSW",
   "description": "Only with 5305 = 1 (see 0304).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "40101",
   "name": "0101 Speed & dir",
   "description": "Signed motor speed; negative = reverse.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "40102",
   "name": "0102 Speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "40103",
   "name": "0103 Output freq",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "40104",
   "name": "0104 Current",
   "description": "Measured motor current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "40105",
   "name": "0105 Torque",
   "description": "Percent of nominal motor torque.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "40106",
   "name": "0106 Power",
   "description": "Measured motor power.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "40107",
   "name": "0107 DC bus voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "40109",
   "name": "0109 Output voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "40110",
   "name": "0110 Drive temp",
   "description": "Power transistor temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "40112",
   "name": "0112 External ref 2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "40113",
   "name": "0113 Ctrl location",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "LOCAL",
    "1": "EXT1",
    "2": "EXT2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "40114",
   "name": "0114 Run time (R)",
   "description": "Resettable run hours.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 114,
   "documented": "40115",
   "name": "0115 kWh counter (R)",
   "description": "Rolls over at 65535; resettable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 119,
   "documented": "40120",
   "name": "0120 AI 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 120,
   "documented": "40121",
   "name": "0121 AI 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 123,
   "documented": "40124",
   "name": "0124 AO 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 139,
   "documented": "40140",
   "name": "0140 Run time",
   "description": "Thousands of hours.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 140,
   "documented": "40141",
   "name": "0141 MWh counter",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "MWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "40143",
   "name": "0143 Drive on time hi",
   "description": "Power-on days.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 143,
   "documented": "40144",
   "name": "0144 Drive on time lo",
   "description": "2 s ticks within the day.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 2,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 152,
   "documented": "40153",
   "name": "0153 Mot therm stress",
   "description": "Motor thermal load.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "40305",
   "name": "0305 Fault word 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OVERCURRENT",
    "1": "DC OVERVOLT",
    "2": "DEV OVERTEMP",
    "3": "SHORT CIRC",
    "4": "Reserved",
    "5": "DC UNDERVOLT",
    "6": "AI1 LOSS",
    "7": "AI2 LOSS",
    "8": "MOT OVERTEMP",
    "9": "PANEL LOSS",
    "10": "ID RUN FAIL",
    "11": "MOTOR STALL",
    "12": "CB OVERTEMP",
    "13": "EXT FAULT 1",
    "14": "EXT FAULT 2",
    "15": "EARTH FAULT"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 305,
   "documented": "40306",
   "name": "0306 Fault word 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Obsolete",
    "1": "THERM FAIL",
    "2": "OPEX LINK",
    "3": "OPEX PWR",
    "4": "CURR MEAS",
    "5": "SUPPLY PHASE",
    "6": "ENCODER ERR",
    "7": "OVERSPEED",
    "8": "Reserved",
    "9": "DRIVE ID",
    "10": "CONFIG FILE",
    "11": "SERIAL 1 ERR",
    "12": "EFB CON FILE",
    "13": "FORCE TRIP",
    "14": "MOTOR PHASE",
    "15": "OUTP WIRING"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "40307",
   "name": "0307 Fault word 3",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "EFB 1",
    "1": "EFB 2",
    "2": "EFB 3",
    "3": "INCOMPATIBLE SW",
    "4": "USER LOAD CURVE",
    "5": "Reserved",
    "6": "Reserved",
    "7": "Reserved",
    "8": "Reserved",
    "9": "Reserved",
    "10": "System error",
    "11": "System error",
    "12": "System error",
    "13": "System error",
    "14": "System error",
    "15": "Param. setting fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 307,
   "documented": "40308",
   "name": "0308 Alarm word 1",
   "description": "Write 0 to clear.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "OVERCURRENT",
    "1": "OVERVOLTAGE",
    "2": "UNDERVOLTAGE",
    "3": "DIR LOCK",
    "4": "IO COMM",
    "5": "AI1 LOSS",
    "6": "AI2 LOSS",
    "7": "PANEL LOSS",
    "8": "DEVICE OVERTEMP",
    "9": "MOTOR TEMP",
    "10": "Reserved",
    "11": "MOTOR STALL",
    "12": "AUTORESET",
    "13": "AUTOCHANGE",
    "14": "PFC I LOCK",
    "15": "Reserved"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "40309",
   "name": "0309 Alarm word 2",
   "description": "Write 0 to clear.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Reserved",
    "1": "PID SLEEP",
    "2": "ID RUN",
    "3": "Reserved",
    "4": "START ENABLE 1 MISSING",
    "5": "START ENABLE 2 MISSING",
    "6": "EMERGENCY STOP",
    "7": "ENCODER ERROR",
    "8": "FIRST START",
    "9": "Reserved",
    "10": "USER LOAD CURVE",
    "11": "START DELAY",
    "12": "Reserved",
    "13": "Reserved",
    "14": "Reserved",
    "15": "Reserved"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "40401",
   "name": "0401 Last fault",
   "description": "Latest fault code; 0 = history clear.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 403,
   "documented": "40404",
   "name": "0404 Speed at flt",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 404,
   "documented": "40405",
   "name": "0405 Freq at flt",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 405,
   "documented": "40406",
   "name": "0406 Voltage at flt",
   "description": "DC bus voltage at the fault.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 406,
   "documented": "40407",
   "name": "0407 Current at flt",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 407,
   "documented": "40408",
   "name": "0408 Torque at flt",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 411,
   "documented": "40412",
   "name": "0412 Previous fault 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "40413",
   "name": "0413 Previous fault 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1606,
   "documented": "41607",
   "name": "1607 Param. save",
   "description": "Write 1 to save parameters permanently.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "DONE",
    "1": "SAVE"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3017,
   "documented": "43018",
   "name": "3018 Comm fault func",
   "description": "Reaction to fieldbus loss.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "NOT SEL",
    "1": "FAULT",
    "2": "CONST SP 7",
    "3": "LAST SPEED"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3018,
   "documented": "43019",
   "name": "3019 Comm fault time",
   "description": "0.0-600.0 s, default 3.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5301,
   "documented": "45302",
   "name": "5302 EFB station ID",
   "description": "Default 1 for Modbus.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5303,
   "documented": "45304",
   "name": "5304 EFB parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "8 NONE 1",
    "1": "8 NONE 2",
    "2": "8 EVEN 1",
    "3": "8 ODD 1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5304,
   "documented": "45305",
   "name": "5305 EFB ctrl profile",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "ABB DRV LIM",
    "1": "DCU PROFILE",
    "2": "ABB DRV FULL"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5305,
   "documented": "45306",
   "name": "5306 EFB OK messages",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5306,
   "documented": "45307",
   "name": "5307 EFB CRC errors",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5307,
   "documented": "45308",
   "name": "5308 EFB UART errors",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5308,
   "documented": "45309",
   "name": "5309 EFB status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "IDLE",
    "1": "EXECUT INIT",
    "2": "TIME OUT",
    "3": "CONFIG ERROR",
    "4": "OFF-LINE",
    "5": "ON-LINE",
    "6": "RESET",
    "7": "LISTEN ONLY"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5309,
   "documented": "45310",
   "name": "5310 EFB par 10",
   "description": "Parameter mapped to 40005.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5310,
   "documented": "45311",
   "name": "5311 EFB par 11",
   "description": "Parameter mapped to 40006.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9801,
   "documented": "49802",
   "name": "9802 Comm prot sel",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "NOT SEL",
    "1": "STD MODBUS",
    "4": "EXT FBA (adapter in slot 2)"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set 9802 = 1 (STD MODBUS), set 5302 and the line settings, then 5305 = 2 (ABB DRV FULL) and point 1001/1102/1103 at COMM. Write the control word and REF1 at 40001/40002, poll the status word 40004 and output frequency/current at 40103/40104.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Control word: start/stop/reset"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Reference 1 (20000 = 1105 REF1 MAX)"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Status word"
   },
   {
    "table": "holding_register",
    "address": 102,
    "why": "0103 Output frequency, 0.1 Hz"
   },
   {
    "table": "holding_register",
    "address": 103,
    "why": "0104 Current, 0.1 A"
   },
   {
    "table": "holding_register",
    "address": 105,
    "why": "0106 Power, 0.1 kW"
   },
   {
    "table": "holding_register",
    "address": 400,
    "why": "0401 Last fault"
   },
   {
    "table": "holding_register",
    "address": 304,
    "why": "0305 Fault word 1"
   }
  ],
  "enable": "Set 9802 COMM PROT SEL = 1 (STD MODBUS); this loads Modbus defaults into group 53. Set 5302 station ID (a new address applies after a power cycle, or after setting 5302 to 0 and then the new value), 5303 baud and 5304 parity. For control set 1001 EXT1 COMMANDS = COMM, 1102 EXT1/EXT2 SEL and 1103 REF1 SELECT = COMM, and optionally 1601 RUN ENABLE and 1604 FAULT RESET SEL = COMM. Parameter writes are volatile until 1607 PARAM. SAVE = 1.",
  "watchdog": "3018 COMM FAULT FUNC (NOT SEL default / FAULT 28 SERIAL 1 ERR / CONST SP 7 / LAST SPEED with alarm 2005 I/O COMM) after 3019 COMM FAULT TIME (default 3.0 s).",
  "quirks": [
   "Zero-based addressing: 4xxxx is sent as xxxx - 1.",
   "Everything is 16-bit.",
   "With ABB DRV LIM (default) control word bits 4 and 10 are ignored; choose ABB DRV FULL for the full ABB Drives state machine.",
   "Alarm words 0308/0309 stay set until the whole word is written to zero."
  ],
  "setup": [
   "RS-485 on X1:28-32 with terminal 31 as logical ground; DIP switch J2 sets RS-485 termination.",
   "Fit termination at both ends of the RS-485 line."
  ],
  "gotchas": [
   "5302 = 0 holds the RS-485 channel in reset and stops communication.",
   "Parameter writes over Modbus are lost at power-down unless saved with 1607."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/abb/acs550",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}