 "manufacturer": "ABB",
 "manufacturer_slug": "abb",
 "model": "CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)",
 "model_slug": "cms-700",
 "short_model": "CMS-700",
 "aliases": [
  "CMS-700",
  "CMS700",
  "ABB CMS-700",
  "CMS-700 control unit"
 ],
 "equipment_type": "Power meter (branch circuit monitoring)",
 "applies_to": "ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).",
 "summary": "The CMS-700 control unit measures mains voltage, current, power and energy and collects up to 96 open-core or solid-core branch current sensors. It serves everything over Modbus RTU (RS-485) and Modbus TCP on port 8001. Branch currents are 16-bit values in 0.01 A; mains values and branch power/energy are 32-bit, high word first.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 19200,
  "parity": "Even",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": 8001
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The mapping table prints each address in hex (with the decimal beside it), and sensor 1 sits at 0000h, so the printed value is the request address with no offset. The manual has no example frame."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "CMS-700 User manual - Circuit Monitoring System",
  "doc_number": "2CCC481011M0201 Rev. C",
  "revision_date": "2018-09",
  "url": "https://library.e.abb.com/public/ae914775dba84d5ea4ed896c6c0378f9/CMS%20Manual_web.pdf",
  "pages": "Modbus encoding p. 54; RS-485 settings p. 55; data formats and special values pp. 56-57; mapping table pp. 63-67"
 },
 "notes": [
  "The manual says multi-register data has the most significant part in the lowest address (high word first).",
  "Per-sensor blocks repeat for sensors 1-96: TRMS 0000h-005Fh, AC 0100h-015Fh, DC 0200h-025Fh, min 0400h+, max 0800h+, hold 0C00h+, polarity 2000h+, power factor 7300h+ (one register each); branch power 2200h+ and energy 2300h+ (two registers each). Only the first entries are listed.",
  "Special values: 7FF0h = data pending, 7FFCh = sensor not reachable, 7FFDh = data type disabled, 7FFEh = overload, 7FFFh = no such sensor (FFFF7FFxh for 32-bit values).",
  "The table has a few misprints in its summary rows (the last AC sensor row shows 005F for 351; the group 2 energy row repeats 9'472); this map lists only rows whose hex and decimal agree.",
  "The frame description lists 1 stop bit; parity can be even (default), odd or none. Data bits are not stated.",
  "Left out: sensor serial/version blocks (1000h+), branch and group names, phase/group assignment registers and the threshold alarm block (8100h+).",
  "Group energy (2500h+, 100 Wh steps) is left out because the table prints the same decimal address (9'472) for groups 1 and 2."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0000h (0)",
   "name": "TRMS current, sensor 1",
   "description": "Sensor n: add n-1 (n = 1-96).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001h (1)",
   "name": "TRMS current, sensor 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 95,
   "documented": "005Fh (95)",
   "name": "TRMS current, sensor 96",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 256,
   "documented": "0100h (256)",
   "name": "AC current, sensor 1",
   "description": "Sensor n: add n-1 (n = 1-96).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 512,
   "documented": "0200h (512)",
   "name": "DC current, sensor 1",
   "description": "Sensor n: add n-1 (n = 1-96). Signed.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1024,
   "documented": "0400h (1024)",
   "name": "TRMS minimum, sensor 1",
   "description": "Sensor n: add n-1 (n = 1-96).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2048,
   "documented": "0800h (2048)",
   "name": "TRMS maximum, sensor 1",
   "description": "Sensor n: add n-1 (n = 1-96).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3072,
   "documented": "0C00h (3072)",
   "name": "TRMS hold value, sensor 1",
   "description": "Captured by the trigger-hold command. Sensor n: add n-1 (n = 1-96).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "2000h (8192)",
   "name": "DC polarity, sensor 1",
   "description": "Bit 12: 0 = direct, 1 = reverse. Sensor n: add n-1 (n = 1-96).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "12": "DC polarity reverse"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8704,
   "documented": "2200h (8704)",
   "name": "Active power, sensor 1",
   "description": "Calculated branch power. Sensor n: add 2 x (n-1) (n = 1-96).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8960,
   "documented": "2300h (8960)",
   "name": "Active energy, sensor 1",
   "description": "Calculated branch energy. Sensor n: add 2 x (n-1) (n = 1-96).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9216,
   "documented": "2400h (9216)",
   "name": "Active power, group 1",
   "description": "Group n: add 2 x (n-1) (n = 1-96).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12304,
   "documented": "3010h (12304)",
   "name": "Trigger hold / reset min-max",
   "description": "Bit 4 = trigger hold, bit 0 = reset min/max.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "Reset min and max values",
    "4": "Trigger hold measurement"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29440,
   "documented": "7300h (29440)",
   "name": "Power factor, sensor 1",
   "description": "Configured PF used for branch power. Sensor n: add n-1 (n = 1-96).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32768,
   "documented": "8000h (32768)",
   "name": "Number of current alarms",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32769,
   "documented": "8001h (32769)",
   "name": "Alarm status, branch 1",
   "description": "Branch n: add n-1 (8001h-8060h).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36866,
   "documented": "9002h (36866)",
   "name": "Voltage L1-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36868,
   "documented": "9004h (36868)",
   "name": "Voltage L2-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36870,
   "documented": "9006h (36870)",
   "name": "Voltage L3-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36880,
   "documented": "9010h (36880)",
   "name": "Line current L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36882,
   "documented": "9012h (36882)",
   "name": "Line current L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36884,
   "documented": "9014h (36884)",
   "name": "Line current L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36888,
   "documented": "9018h (36888)",
   "name": "Power factor L1",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36890,
   "documented": "901Ah (36890)",
   "name": "Power factor L2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36892,
   "documented": "901Ch (36892)",
   "name": "Power factor L3",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36902,
   "documented": "9026h (36902)",
   "name": "Total apparent power",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36904,
   "documented": "9028h (36904)",
   "name": "Apparent power L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36906,
   "documented": "902Ah (36906)",
   "name": "Apparent power L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36908,
   "documented": "902Ch (36908)",
   "name": "Apparent power L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36910,
   "documented": "902Eh (36910)",
   "name": "Total active power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36912,
   "documented": "9030h (36912)",
   "name": "Active power L1",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36914,
   "documented": "9032h (36914)",
   "name": "Active power L2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36916,
   "documented": "9034h (36916)",
   "name": "Active power L3",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36918,
   "documented": "9036h (36918)",
   "name": "Total reactive power",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36920,
   "documented": "9038h (36920)",
   "name": "Reactive power L1",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36922,
   "documented": "903Ah (36922)",
   "name": "Reactive power L2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36924,
   "documented": "903Ch (36924)",
   "name": "Reactive power L3",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAr",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36926,
   "documented": "903Eh (36926)",
   "name": "Total active energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36928,
   "documented": "9040h (36928)",
   "name": "Total reactive energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36980,
   "documented": "9074h (36980)",
   "name": "Active energy L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36982,
   "documented": "9076h (36982)",
   "name": "Active energy L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36984,
   "documented": "9078h (36984)",
   "name": "Active energy L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36994,
   "documented": "9082h (36994)",
   "name": "Voltage THD L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36996,
   "documented": "9084h (36996)",
   "name": "Voltage THD L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36998,
   "documented": "9086h (36998)",
   "name": "Voltage THD L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37000,
   "documented": "9088h (37000)",
   "name": "Current THD L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37002,
   "documented": "908Ah (37002)",
   "name": "Current THD L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37004,
   "documented": "908Ch (37004)",
   "name": "Current THD L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37030,
   "documented": "90A6h (37030)",
   "name": "Total apparent energy",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37038,
   "documented": "90AEh (37038)",
   "name": "Active energy L1 (100 Wh steps)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 100,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37040,
   "documented": "90B0h (37040)",
   "name": "Active energy L2 (100 Wh steps)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 100,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37042,
   "documented": "90B2h (37042)",
   "name": "Active energy L3 (100 Wh steps)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 100,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37044,
   "documented": "90B4h (37044)",
   "name": "Total active energy (100 Wh steps)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 100,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37052,
   "documented": "90BCh (37052)",
   "name": "Total reactive energy (100 varh steps)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 100,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37060,
   "documented": "90C4h (37060)",
   "name": "Total apparent energy (100 VAh steps)",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 100,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37632,
   "documented": "9300h (37632)",
   "name": "CT ratio L1/L2/L3",
   "description": "Range 0.1-6000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37633,
   "documented": "9301h (37633)",
   "name": "CT ratio N",
   "description": "Range 0.1-6000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37634,
   "documented": "9302h (37634)",
   "name": "Line current L4/N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37636,
   "documented": "9304h (37636)",
   "name": "Current THD L4/N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 0000h-005Fh for all branch TRMS currents in one block (0.01 A) and 9002h-90C4h for the mains. Branch power and energy come from 2200h and 2300h.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Branch 1 TRMS current"
   },
   {
    "table": "holding_register",
    "address": 36866,
    "why": "Mains voltage L1-N"
   },
   {
    "table": "holding_register",
    "address": 36880,
    "why": "Mains current L1"
   },
   {
    "table": "holding_register",
    "address": 36910,
    "why": "Mains total active power"
   },
   {
    "table": "holding_register",
    "address": 37044,
    "why": "Mains active energy (100 Wh)"
   },
   {
    "table": "holding_register",
    "address": 8960,
    "why": "Branch 1 energy"
   }
  ],
  "enable": "Set Modbus ID, baud rate and parity in the web UI (Settings > Communication / Modbus). Modbus TCP can be switched on or off there and its port changed; the standard port is 8001.",
  "watchdog": null,
  "quirks": [
   "Modbus TCP uses port 8001 by default, not 502.",
   "Reads use function 03 and single writes use 06; the manual says not to use other functions (the table also lists 10 for names and polarity).",
   "16-bit branch values use 7FF0h-7FFFh as status codes."
  ],
  "setup": [
   "Default 19200 baud, even parity.",
   "Add a 120 ohm terminator on units with serial number after 700K1820000 if needed."
  ],
  "gotchas": [
   "Below about 60 mA CT secondary current the mains current reads 0 and power factor reads 1.",
   "The FAQ gives 429,496 kWh as the maximum energy value for the mains and each branch."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/abb/cms-700",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}