 "manufacturer": "ABB",
 "manufacturer_slug": "abb",
 "model": "SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)",
 "model_slug": "pr122dc-pr123dc-modbus",
 "short_model": "PR122DC/PR123DC",
 "aliases": [
  "PR122DC",
  "PR123DC",
  "PR120/D-M",
  "Emax DC",
  "SACE Emax DC"
 ],
 "equipment_type": "Power meter (DC circuit breaker trip unit)",
 "applies_to": "ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).",
 "summary": "The PR122DC and PR123DC are the DC versions of ABB's Emax trip units. With the PR120/D-M module they talk Modbus RTU: pole currents, DC voltage, power and energy are input registers, and commands such as open, close and trip reset are written to two holding registers. 32-bit values are sent low word first.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The map gives relative addresses on 30001 (input registers, function 4) and 40001 (holding registers) bases; its example says run-time measures at offset 200 are 30201, relative address 200, which is the wire address with 'Standard' addressing."
 },
 "default_word_order": "CDAB",
 "firmware": "SW 3.01 and later",
 "source": {
  "title": "Communication System Interface for protection trip units PR122DC and PR123DC + PR120/D-M Com module",
  "doc_number": "1SDH000841R0001 rev 02",
  "revision_date": "2014-04-04",
  "url": "https://library.e.abb.com/public/14a57dd39209c59dc12578b100664838/1SDH000841R0001.pdf",
  "pages": "Comms parameters p. 5; Modbus map and word order pp. 9-10; commands p. 13; state pp. 16-18; run-time measures p. 19; information p. 20"
 },
 "notes": [
  "The document states 4-byte values are sent with the low word at the lower address (LOW-HIGH), bytes within a word high first, so 32-bit registers are CDAB.",
  "External bus settings: 9600 or 19200 baud, address 1-247, Standard or ABB addressing, E,8,1 / O,8,1 / N,8,2 / N,8,1. The document does not state the external-bus factory values.",
  "IB, IB_2, ground current, voltage, power and energy are PR123DC only.",
  "Left out: state words other than 2 and 8, statistics, history, logger and parameter areas.",
  "Over the external bus, commands are accepted only in Remote mode (state 2 bit 9)."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 101,
   "documented": "30102 (rel. 101)",
   "name": "State 2 - flags",
   "description": "Breaker position and remote/local.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Any alarm / timing / warning",
    "1": "Any trip (latched)",
    "2": "CB tripped",
    "3": "CB connected (0 = isolated)",
    "4": "CB closed (0 = open)",
    "5": "CB undefined",
    "6": "No communication on local bus",
    "7": "Springs charged",
    "8": "Trip command fail",
    "9": "Remote mode (0 = local)",
    "10": "Programming OK",
    "11": "Programming failed",
    "12": "Internal bus programming session",
    "13": "Test bus programming session",
    "14": "Local bus programming session",
    "15": "System bus programming session"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 107,
   "documented": "30108 (rel. 107)",
   "name": "State 8 - latched trips",
   "description": "Cleared by CB reset or trip reset.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "L tripped",
    "1": "S tripped",
    "2": "S2 tripped",
    "3": "I tripped (or MCR)",
    "4": "Iinst tripped",
    "5": "G tripped",
    "7": "OT tripped",
    "9": "U tripped",
    "10": "UV tripped",
    "11": "OV tripped",
    "13": "RP tripped"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 200,
   "documented": "30201-30202 (rel. 200)",
   "name": "Maximum current",
   "description": "2^32-1 = not available.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 202,
   "documented": "30203 (rel. 202)",
   "name": "Maximum current polarity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not available",
    "1": "IA",
    "2": "IA_2",
    "3": "IB",
    "4": "IB_2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 203,
   "documented": "30204-30205 (rel. 203)",
   "name": "IA current",
   "description": "2^32-1 = not available.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 205,
   "documented": "30206-30207 (rel. 205)",
   "name": "IA_2 current",
   "description": "2^32-1 = not available.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 207,
   "documented": "30208-30209 (rel. 207)",
   "name": "IB current",
   "description": "PR123DC. 2^32-1 = not available.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 209,
   "documented": "30210-30211 (rel. 209)",
   "name": "IB_2 current",
   "description": "PR123DC. 2^32-1 = not available.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 211,
   "documented": "30212-30213 (rel. 211)",
   "name": "Ground current",
   "description": "PR123DC. 2^32-1 = not available.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 217,
   "documented": "30218 (rel. 217)",
   "name": "DC voltage",
   "description": "PR123DC; 65535 = not available.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 218,
   "documented": "30219-30220 (rel. 218)",
   "name": "Total active power",
   "description": "PR123DC; 2^31-1 = not available.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 220,
   "documented": "30221-30222 (rel. 220)",
   "name": "Positive active energy",
   "description": "PR123DC.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 222,
   "documented": "30223-30224 (rel. 222)",
   "name": "Negative active energy",
   "description": "PR123DC.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 224,
   "documented": "30225-30226 (rel. 224)",
   "name": "Total active energy",
   "description": "PR123DC.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 700,
   "documented": "30701 (rel. 700)",
   "name": "Slave ID",
   "description": "Identifies the trip unit model.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "88": "PR123DC (0x58)",
    "89": "PR122DC (0x59)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 704,
   "documented": "30705 (rel. 704)",
   "name": "Rated current In",
   "description": "100-6300 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001 (rel. 0)",
   "name": "Command type",
   "description": "Write with the parameter in one function-16 request.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "0": "Dummy",
    "1": "Trip reset",
    "2": "Signalling reset",
    "3": "Communication statistics reset",
    "4": "Log event reset",
    "5": "Start programming session",
    "6": "Abort programming session",
    "7": "Stop programming session",
    "8": "CB open",
    "9": "CB close",
    "10": "CB reset",
    "11": "Wink toggle",
    "12": "History measure reset",
    "13": "History energy reset",
    "14": "Datalogger trigger restart",
    "15": "Datalogger stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002 (rel. 1)",
   "name": "Command parameter",
   "description": "0 when the command needs none.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read input registers 200-225 for currents, voltage, power and energy, and 101/107 for breaker state and trips. Open, close or reset with a function-16 write of command type and parameter to registers 0-1.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 101,
    "why": "CB open/closed, tripped, remote"
   },
   {
    "table": "input_register",
    "address": 107,
    "why": "Which protection tripped"
   },
   {
    "table": "input_register",
    "address": 203,
    "why": "Pole A current"
   },
   {
    "table": "input_register",
    "address": 217,
    "why": "DC voltage"
   },
   {
    "table": "input_register",
    "address": 218,
    "why": "Total active power"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Commands"
   }
  ],
  "enable": "Fit the PR120/D-M module and set the external bus address, baud and protocol on the trip unit. Remote mode (state 2 bit 9) is needed for open/close commands.",
  "watchdog": null,
  "quirks": [
   "32-bit values are low word first.",
   "Measures are input registers (function 4).",
   "Commands always need function 16 with both registers."
  ],
  "setup": [
   "Set the external-bus address (1-247), baud (9600/19200), addressing type and frame format (E,8,1 / O,8,1 / N,8,2 / N,8,1) on the trip unit."
  ],
  "gotchas": [
   "Slave ID register 700 tells PR122DC (0x59) from PR123DC (0x58)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/abb/pr122dc-pr123dc-modbus",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}