 "manufacturer": "ABB",
 "manufacturer_slug": "abb",
 "model": "Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)",
 "model_slug": "protronic-digitric",
 "short_model": "Protronic / Digitric",
 "aliases": [
  "Protronic 100",
  "Protronic 500",
  "Protronic 550",
  "Digitric 500"
 ],
 "equipment_type": "Process controller (sensor / PID controller)",
 "applies_to": "ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.",
 "summary": "ABB's Protronic and Digitric panel controllers expose their internal variables to a Modbus RTU master through an interface module. Global variables (analog inputs and outputs and the per-loop controller values) are 32-bit IEEE floats in pairs of holding registers starting at register 0; online parameters and binary I/O have their own ranges. This map covers the basic and slot-1 analog I/O plus the main setpoint, process value, deviation and output values of control loops 1-4.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Register numbers are printed in decimal starting at 0 and go on the wire unchanged: the manual's example reads analog input AE01 from registers 0 and 1 with start address 00 00. Function 03 is preferred; function 04 returns the same data."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "Protronic 100/500/550, Digitric 500 - MODBUS interface description",
  "doc_number": "42/62-50040 EN Rev. 04",
  "revision_date": "2001-11",
  "url": "https://library.e.abb.com/public/c125698f006840e9c1256b21003c16bd/42-62-50040-EN-04-11_01.pdf",
  "pages": "pp. 9-10 (functions, read example from register 0), pp. 14-15 (REAL format, pair-of-registers word order), p. 18 (register ranges), pp. 19-26 (Appendix 1 global variable table)"
 },
 "notes": [
  "Word order: with the pair-of-registers method the even register carries the low word and the next (odd) register the high word of the IEEE-754 REAL, so floats are CDAB.",
  "The same variables can also be read in a mantissa/exponent format by adding 2000 to the register number (FW 1.149 and later); that format is not listed.",
  "Values are in the engineering units configured in the controller, so no units are given.",
  "Loop variables repeat every 150 registers (loop 1 from 150, loop 2 from 300, loop 3 from 450, loop 4 from 600). Many more loop variables (constants, limits, PID parts, free variables) and analog I/O of slots 2-7 follow the same table and are not all listed.",
  "Online parameters sit at 10000-20000 (10000 + loop x 1000 + 2 x parameter number, e.g. loop 1 Kp = 11002). Register 900 accepts key-press codes for remote keyboard operation. Binary inputs/outputs are read as coils (e.g. BE01 from 151). These are not listed.",
  "The table does not mark which global variables are writable; all are listed read-only here. Writes use function 06 (two telegrams for a REAL) or 16."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Basic device analog input 1 (.AE01)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Basic device analog input 2 (.AE02)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Slot 1 analog input 1 (.AE11)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Slot 1 analog input 2 (.AE12)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Slot 1 analog input 3 (.AE13)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Slot 1 analog input 4 (.AE14)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 70,
   "documented": "70",
   "name": "Basic device analog output 1 (.AA01)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 72,
   "documented": "72",
   "name": "Slot 1 analog output 1 (.AA11)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 74,
   "documented": "74",
   "name": "Slot 1 analog output 2 (.AA12)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "76",
   "name": "Slot 1 analog output 3 (.AA13)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "160",
   "name": "Loop 1 current setpoint (.L1_WAKT)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 164,
   "documented": "164",
   "name": "Loop 1 process value (digital display) (.L1_XDIGI)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 170,
   "documented": "170",
   "name": "Loop 1 control deviation (.L1_XW)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 184,
   "documented": "184",
   "name": "Loop 1 PID output (.L1_PID_Y_OUT)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 188,
   "documented": "188",
   "name": "Loop 1 control deviation in % (.L1_XW_PRZ)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 228,
   "documented": "228",
   "name": "Loop 1 computer setpoint (.L1_WCOMPUTER)",
   "description": "Setpoint given by a host computer.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 238,
   "documented": "238",
   "name": "Loop 1 active setpoint (.L1_WW)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "310",
   "name": "Loop 2 current setpoint (.L2_WAKT)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "314",
   "name": "Loop 2 process value (digital display) (.L2_XDIGI)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 320,
   "documented": "320",
   "name": "Loop 2 control deviation (.L2_XW)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 334,
   "documented": "334",
   "name": "Loop 2 PID output (.L2_PID_Y_OUT)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 338,
   "documented": "338",
   "name": "Loop 2 control deviation in % (.L2_XW_PRZ)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 378,
   "documented": "378",
   "name": "Loop 2 computer setpoint (.L2_WCOMPUTER)",
   "description": "Setpoint given by a host computer.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 388,
   "documented": "388",
   "name": "Loop 2 active setpoint (.L2_WW)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 460,
   "documented": "460",
   "name": "Loop 3 current setpoint (.L3_WAKT)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 464,
   "documented": "464",
   "name": "Loop 3 process value (digital display) (.L3_XDIGI)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 470,
   "documented": "470",
   "name": "Loop 3 control deviation (.L3_XW)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 484,
   "documented": "484",
   "name": "Loop 3 PID output (.L3_PID_Y_OUT)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 488,
   "documented": "488",
   "name": "Loop 3 control deviation in % (.L3_XW_PRZ)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 528,
   "documented": "528",
   "name": "Loop 3 computer setpoint (.L3_WCOMPUTER)",
   "description": "Setpoint given by a host computer.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 538,
   "documented": "538",
   "name": "Loop 3 active setpoint (.L3_WW)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 610,
   "documented": "610",
   "name": "Loop 4 current setpoint (.L4_WAKT)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 614,
   "documented": "614",
   "name": "Loop 4 process value (digital display) (.L4_XDIGI)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 620,
   "documented": "620",
   "name": "Loop 4 control deviation (.L4_XW)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 634,
   "documented": "634",
   "name": "Loop 4 PID output (.L4_PID_Y_OUT)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 638,
   "documented": "638",
   "name": "Loop 4 control deviation in % (.L4_XW_PRZ)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 678,
   "documented": "678",
   "name": "Loop 4 computer setpoint (.L4_WCOMPUTER)",
   "description": "Setpoint given by a host computer.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 688,
   "documented": "688",
   "name": "Loop 4 active setpoint (.L4_WW)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read the loop values with function 03 as CDAB floats: process value at 164 (loop 1), active setpoint at 238, controller output at 184; add 150 per further loop. Analog inputs start at register 0.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 164,
    "why": "Loop 1 process value"
   },
   {
    "table": "holding_register",
    "address": 238,
    "why": "Loop 1 active setpoint"
   },
   {
    "table": "holding_register",
    "address": 184,
    "why": "Loop 1 PID output"
   },
   {
    "table": "holding_register",
    "address": 170,
    "why": "Loop 1 control deviation"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Analog input 1"
   }
  ],
  "enable": "Fit the RS-485 (or RS-232) interface module and set the station address and line settings on the controller; addresses 1-255 are allowed, 0 is broadcast.",
  "watchdog": null,
  "quirks": [
   "REAL values are low word first (even register = low word).",
   "Always read or write both registers of a REAL together.",
   "Function 04 behaves like 03 and 02 like 01."
  ],
  "setup": [
   "RS-485: up to 32 stations, cable under 1200 m, stubs under 0.3 m, electrically isolated; RS-232 for a single PC up to 10 m."
  ],
  "gotchas": [
   "Gaps in the register table (e.g. 60-69, 78-79) are unassigned."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/abb/protronic-digitric",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}