 "manufacturer": "ACI (Automation Components Inc.)",
 "manufacturer_slug": "aci",
 "model": "Wall Plate Series BACnet/Modbus temperature/RH sensor",
 "model_slug": "wall-plate-series",
 "short_model": "Wall Plate Series",
 "aliases": [
  "A/RH-BM wall plate",
  "Wall Plate Series BACnet Modbus"
 ],
 "equipment_type": "Sensor (room temperature / humidity)",
 "applies_to": "ACI Wall Plate Series stainless wall-plate temperature, RH and temperature/RH sensors with the BACnet MS/TP / Modbus RTU interface (guide I0000931).",
 "summary": "ACI's stainless wall-plate room sensor for temperature, humidity or both, with a DIP-switch selectable BACnet MS/TP or Modbus RTU RS-485 interface and no analog output. Readings are signed tenths in input registers; a few holding registers set units, offsets and user labels.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Each row gives a Reference (1-based, e.g. 3) and an Address (0-based, e.g. 2). The documented field here holds the Reference; the address field holds the Address column, which is what goes on the wire."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Wall Plate Series BACnet / Modbus User's Guide",
  "doc_number": "I0000931",
  "revision_date": null,
  "url": "https://www.workaci.com/media/791/download",
  "pages": "pp. 7-9 (interface, baud, EOL), p. 10 (address), p. 13 (framing, test mode), pp. 14-16 (Modbus RTU map)"
 },
 "notes": [
  "The map prints a 1-based Reference column and a 0-based Address column side by side (e.g. Reference 3 = Address 2 for the temperature value); this map uses the Address column.",
  "RH values and RH range registers are described only as tenths of %RH without a sign statement; they are listed as unsigned since RH cannot be negative. The RH offset is explicitly allowed to be negative (example -16 = -1.6 %RH) so it is INT16.",
  "Temperature registers carry no fixed unit: the unit follows holding register 0 (62 °C, 63 K, 64 °F).",
  "Temperature-only models have no RH element and RH-only models no temperature element; input register 0 shows which is fitted."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 1000,
   "documented": "1001",
   "name": "Test mode enable",
   "description": "1 = IR3/IR4 return the test values in HR1001/HR1002; not kept after reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (live values)",
    "1": "Enabled (test values)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "1",
   "name": "Sensors present",
   "description": "Which sensing elements are fitted.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Temperature sensor present",
    "1": "RH sensor present"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "3",
   "name": "Temperature sensor value",
   "description": "Tenths, in the unit chosen in HR1 (address 0).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "4",
   "name": "RH sensor value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2000,
   "documented": "2001",
   "name": "Temperature range min",
   "description": "Lowest reportable temperature, tenths.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2001,
   "documented": "2002",
   "name": "Temperature range max",
   "description": "Highest reportable temperature, tenths.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2002,
   "documented": "2003",
   "name": "RH range min",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2003,
   "documented": "2004",
   "name": "RH range max",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9000,
   "documented": "9001",
   "name": "Unsigned test value",
   "description": "Always 12345; checks decoding.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9001,
   "documented": "9002",
   "name": "Signed test value",
   "description": "Always -12345; checks signed decoding.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9002,
   "documented": "9003-9006",
   "name": "Test string",
   "description": "Always \"-123.45\", null terminated.",
   "data_type": "STRING",
   "length": 4,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9006,
   "documented": "9007-9010",
   "name": "Serial number",
   "description": "ASCII, not null terminated.",
   "data_type": "STRING",
   "length": 4,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9010,
   "documented": "9011-9016",
   "name": "Firmware version",
   "description": "ASCII, not null terminated, e.g. 02.00.000.90.",
   "data_type": "STRING",
   "length": 6,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Temperature units",
   "description": "Unit used for the temperature value and ranges.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "62": "°C",
    "63": "K",
    "64": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Temperature offset",
   "description": "Added to the reading; -5.0 to 5.0 °C/K (-9.0 to 9.0 °F).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "RH offset",
   "description": "Added to the RH reading; -10.0 to 10.0 %RH.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "1001",
   "name": "Test mode temperature value",
   "description": "Returned by IR3 while test mode is on.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "1002",
   "name": "Test mode RH value",
   "description": "Returned by IR4 while test mode is on.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9000,
   "documented": "9001-9016",
   "name": "Device name",
   "description": "User text, null terminated.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9016,
   "documented": "9017-9048",
   "name": "Device location",
   "description": "User text, null terminated.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9048,
   "documented": "9049-9080",
   "name": "Device description",
   "description": "User text, null terminated.",
   "data_type": "STRING",
   "length": 32,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Switch the sensor to Modbus with SW4 DIP 4, give it a non-zero address and a fixed baud rate, then read input registers 2 (temperature, tenths) and 3 (RH) with function 04. Check input registers 9000/9001 once to confirm your master decodes unsigned and signed values correctly.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 2,
    "why": "Temperature value"
   },
   {
    "table": "input_register",
    "address": 3,
    "why": "Relative humidity"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Temperature unit"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "Which sensors are fitted"
   },
   {
    "table": "input_register",
    "address": 9000,
    "why": "Decoding check 12345"
   },
   {
    "table": "input_register",
    "address": 9001,
    "why": "Signed decoding check -12345"
   }
  ],
  "enable": "SW4 DIP 4 ON selects Modbus RTU; address on switches 1-7 (must not be 0); baud on switches 8-10; power-cycle or press reset after any switch change.",
  "watchdog": null,
  "quirks": [
   "Temperature unit is set by holding register 0, not fixed; values are tenths of that unit.",
   "Test mode (coil 1000) substitutes HR1000/HR1001 values into the live registers and is cleared by reset or power cycle.",
   "String registers: test string and user text are null terminated, serial number and firmware are not."
  ],
  "setup": [
   "Set SW4 DIP 4 ON to select Modbus (factory default is BACnet MS/TP), then power-cycle or press reset.",
   "Set the address on switches 1-7 (binary, 1-127). Address 0 is the factory default and cannot be used with Modbus.",
   "Set the baud rate on switches 8-10 (9600-115200); auto-baud does not work in Modbus mode.",
   "SW4 PAR 2 / PAR 1 DIP switches (1 = ON) set framing: 0/0 8-E-1, 0/1 8-O-1, 1/0 8-N-2, 1/1 8-N-1.",
   "Move the EOL jumper to EN on the last device of the RS-485 trunk (default DIS)."
  ],
  "gotchas": [
   "The factory default is BACnet MS/TP with auto-baud; a sensor left at defaults will not answer Modbus.",
   "Address 0 is invalid for Modbus.",
   "8-None-1 framing is labelled non-standard by ACI."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/aci/wall-plate-series",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}