 "manufacturer": "Aermec",
 "manufacturer_slug": "aermec",
 "model": "LCG series DC inverter air conditioners (built-in Modbus)",
 "model_slug": "lcg-series",
 "short_model": "Aermec LCG",
 "aliases": [
  "LCG"
 ],
 "equipment_type": "Split AC unit (VRF / split AC gateway built in)",
 "applies_to": "Aermec LCG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; Modbus Protocol user manual LCG 5385758_02 (24.01).",
 "summary": "The indoor-unit controller of Aermec LCG units answers Modbus RTU directly, so no extra gateway is needed. Holding registers carry on/off, mode, fan speed, setpoint, louvre position and temperatures; coils carry feature flags (turbo, silent, locks, energy saving) and a long list of indoor, outdoor and inverter-drive fault bits. Up to 255 units can share a BMS line.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The protocol says registers are words numbered from 0 and coils are bits numbered from 0 (Byte0.0 = bit 0). Word n is wire address n and Bit n is coil n; the example frames agree (read starting at word 1 sends 0x0001, coil 5 sends 0x0005)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Modbus Protocol User manual LCG",
  "doc_number": "5385758_02",
  "revision_date": "2024-01",
  "url": "https://www.aermec.com/download?id=14523",
  "pages": "p. 7 serial settings, pp. 8-12 addressing and frames, pp. 13-14 precautions, pp. 19-27 registers (words), pp. 28-43 coils (bits)"
 },
 "notes": [
  "Only named points are listed; reserved words and bits are left out.",
  "Left out because the table row is incomplete in the source: bit 18 (no name), bits 125, 155, 196 and 216-247 (blank names), plus bits 3, 48, 67, 94, 124, 189, 197, 200, 206 and 209 which fall on page breaks where the address and text do not line up reliably.",
  "Some fault bits are printed with the legend '1: yes 0: on'; the 0 state is read here as 'no fault'.",
  "Word 2 uses 0xAA for on and 0x55 for off, not 1/0.",
  "The point list matches Aermec's LPG series protocol; the LCG table lists DRED values 1-3 only (no value 0)."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 8,
   "documented": "Bit8",
   "name": "ODU flag present",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "Bit9",
   "name": "Master wired controller flag",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "Bit13",
   "name": "Slave wired controller flag",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 17,
   "documented": "Bit17",
   "name": "Remote lock",
   "description": "1 = locked by remote monitoring or the charging system.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 19,
   "documented": "Bit19",
   "name": "Remote mode shield",
   "description": "1 = mode changes from the unit are blocked.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 20,
   "documented": "Bit20",
   "name": "Remote On/Off shield",
   "description": "1 = on/off from the unit is blocked.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 21,
   "documented": "Bit21",
   "name": "Remote energy saving shield",
   "description": "1 = shield on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 24,
   "documented": "Bit24",
   "name": "Absence mode",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 25,
   "documented": "Bit25",
   "name": "Healthy function",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 26,
   "documented": "Bit26",
   "name": "I-Demand comfort/energy saving",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "Bit27",
   "name": "Turbo",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 28,
   "documented": "Bit28",
   "name": "E-heating permission",
   "description": "0 = electric heater allowed, 1 = not allowed.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 29,
   "documented": "Bit29",
   "name": "X-fan",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 30,
   "documented": "Bit30",
   "name": "Silent",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 31,
   "documented": "Bit31",
   "name": "Low temp drying mode",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 32,
   "documented": "Bit32",
   "name": "Energy saving under cooling",
   "description": "1 = on. Write together with bit 33.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "Bit33",
   "name": "Energy saving under heating",
   "description": "1 = on. Write together with bit 32.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "Bit34",
   "name": "Buttons lock (child lock)",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "Bit35",
   "name": "On/Off memory",
   "description": "0 = memorize, 1 = do not memorize.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 36,
   "documented": "Bit36",
   "name": "°C/°F flag",
   "description": "1 = °F, 0 = °C.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 40,
   "documented": "Bit40",
   "name": "Timer status",
   "description": "1 = timer set.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 46,
   "documented": "Bit46",
   "name": "Gate control system present",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 47,
   "documented": "Bit47",
   "name": "Human body sensing module present",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 49,
   "documented": "Bit49",
   "name": "Timer On flag",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 50,
   "documented": "Bit50",
   "name": "Timer Off flag",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 51,
   "documented": "Bit51",
   "name": "Indoor ambient source",
   "description": "0 = return-air sensor, 1 = wired controller sensor.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 55,
   "documented": "Bit55",
   "name": "Low standby power control",
   "description": "1 = mode 2, 0 = mode 1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 65,
   "documented": "Bit65",
   "name": "Wired controller temp sensor error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 70,
   "documented": "Bit70",
   "name": "Wired controller memory chip error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 72,
   "documented": "Bit72",
   "name": "Cancel timer",
   "description": "1 = cancel.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 74,
   "documented": "Bit74",
   "name": "Up & down swing mode",
   "description": "0 = simple swing, 1 = fixed angle and small-area swing.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 91,
   "documented": "Bit91",
   "name": "Electric heating",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 92,
   "documented": "Bit92",
   "name": "Water pump",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 93,
   "documented": "Bit93",
   "name": "Fresh air valve switch",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 95,
   "documented": "Bit95",
   "name": "Error output status",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 97,
   "documented": "Bit97",
   "name": "Indoor evaporator temp sensor error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 98,
   "documented": "Bit98",
   "name": "Indoor return air temp sensor error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 99,
   "documented": "Bit99",
   "name": "Light board ambient temp sensor error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 101,
   "documented": "Bit101",
   "name": "Water overflow protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 102,
   "documented": "Bit102",
   "name": "IDU memory chip error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 104,
   "documented": "Bit104",
   "name": "Jumper cap error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 105,
   "documented": "Bit105",
   "name": "Indoor fan error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 112,
   "documented": "Bit112",
   "name": "Card in/out status",
   "description": "1 = card in.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 113,
   "documented": "Bit113",
   "name": "People in room",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 114,
   "documented": "Bit114",
   "name": "Static pressure type",
   "description": "0 = low static, 1 = high static.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 120,
   "documented": "Bit120",
   "name": "Comm failure with master wired controller",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 121,
   "documented": "Bit121",
   "name": "Comm failure with slave wired controller",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 122,
   "documented": "Bit122",
   "name": "Comm failure with ODU",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 147,
   "documented": "Bit147",
   "name": "Outdoor fan status",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 150,
   "documented": "Bit150",
   "name": "4-way valve status",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 151,
   "documented": "Bit151",
   "name": "Compressor status",
   "description": "1 = on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 152,
   "documented": "Bit152",
   "name": "Discharge temperature protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 153,
   "documented": "Bit153",
   "name": "Refrigerant shortage protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 154,
   "documented": "Bit154",
   "name": "DC fan motor protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 156,
   "documented": "Bit156",
   "name": "Over power protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 157,
   "documented": "Bit157",
   "name": "Overload protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 158,
   "documented": "Bit158",
   "name": "Low pressure protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 159,
   "documented": "Bit159",
   "name": "High pressure protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 160,
   "documented": "Bit160",
   "name": "Evaporator anti-freezing protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 161,
   "documented": "Bit161",
   "name": "Outdoor ambient temp sensor error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 162,
   "documented": "Bit162",
   "name": "Discharge temp sensor error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 163,
   "documented": "Bit163",
   "name": "Condenser temp sensor error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 164,
   "documented": "Bit164",
   "name": "Outdoor coil pipe temp sensor error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 166,
   "documented": "Bit166",
   "name": "ODU memory chip error",
   "description": "1 = error.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 174,
   "documented": "Bit174",
   "name": "Drive communication failure",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 176,
   "documented": "Bit176",
   "name": "SAVE status",
   "description": "1 = yes.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 177,
   "documented": "Bit177",
   "name": "Cooling only flag",
   "description": "0 = heat pump, 1 = cooling only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 179,
   "documented": "Bit179",
   "name": "System defrosting",
   "description": "1 = defrosting.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 182,
   "documented": "Bit182",
   "name": "Low power consumption status",
   "description": "1 = ready.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 183,
   "documented": "Bit183",
   "name": "AC input phase sequence protection",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 184,
   "documented": "Bit184",
   "name": "Drive DC bus undervoltage",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 185,
   "documented": "Bit185",
   "name": "Drive DC bus overvoltage",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 186,
   "documented": "Bit186",
   "name": "Drive AC input current protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 187,
   "documented": "Bit187",
   "name": "Drive IPM protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 188,
   "documented": "Bit188",
   "name": "Drive PFC protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 190,
   "documented": "Bit190",
   "name": "Compressor phase loss protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 191,
   "documented": "Bit191",
   "name": "Drive module reset",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 192,
   "documented": "Bit192",
   "name": "Compressor over-current protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 193,
   "documented": "Bit193",
   "name": "Compressor power protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 194,
   "documented": "Bit194",
   "name": "Drive current check circuit failure",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 195,
   "documented": "Bit195",
   "name": "Compressor out-of-step protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 198,
   "documented": "Bit198",
   "name": "Drive module high temperature",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 199,
   "documented": "Bit199",
   "name": "Drive module temp sensor failure",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 201,
   "documented": "Bit201",
   "name": "Compressor low field (flux weakening)",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 202,
   "documented": "Bit202",
   "name": "Drive frequency limit",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 203,
   "documented": "Bit203",
   "name": "Drive frequency reduction",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 204,
   "documented": "Bit204",
   "name": "Drive AC input low voltage",
   "description": "1 = active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 205,
   "documented": "Bit205",
   "name": "Drive under charge",
   "description": "1 = under charge, 0 = charged.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 207,
   "documented": "Bit207",
   "name": "Drive AC input power type",
   "description": "Flag 1/0; meaning not given.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 208,
   "documented": "Bit208",
   "name": "Drive storage chip failure",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 210,
   "documented": "Bit210",
   "name": "Drive charge circuit failure",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 211,
   "documented": "Bit211",
   "name": "Drive AC input voltage abnormal",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 212,
   "documented": "Bit212",
   "name": "Compressor temp sensor failure",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 213,
   "documented": "Bit213",
   "name": "Drive AC zero-cross protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 214,
   "documented": "Bit214",
   "name": "Temperature drift protection",
   "description": "1 = failure.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 215,
   "documented": "Bit215",
   "name": "Current sensor connection protection",
   "description": "1 = failure (sensor not on U or V phase).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "Word 2",
   "name": "Unit On/Off",
   "description": "0xAA (170) = on, 0x55 (85) = off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "170": "On (0xAA)",
    "85": "Off (0x55)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "Word 4",
   "name": "Ambient temp",
   "description": "Indoor ambient temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "Word 5",
   "name": "IDU Addr.",
   "description": "1-16 with a central controller, 1-255 in PC address mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "Word 17",
   "name": "Set mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Cooling",
    "2": "Heating",
    "3": "Drying",
    "4": "Fan only",
    "5": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "Word 19",
   "name": "Set fan speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Speed 1",
    "2": "Speed 2",
    "3": "Speed 3",
    "4": "Speed 4",
    "5": "Speed 5",
    "6": "Turbo"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "Word 20",
   "name": "Set temp",
   "description": "16-30 °C; reads 12 in low-temp drying and 8 in absence mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "Word 22",
   "name": "Up & down swing",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Swing 1-5",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4",
    "6": "Position 5",
    "7": "Swing 3-5",
    "8": "Swing 2-5",
    "9": "Swing 2-4",
    "10": "Swing 1-4",
    "11": "Swing 1-3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "Word 23",
   "name": "Left & right swing",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off (default after power-on)",
    "1": "Swing, same direction",
    "2": "Position 1",
    "3": "Position 2",
    "4": "Position 3",
    "5": "Position 4",
    "6": "Position 5",
    "12": "15 position (as printed)",
    "13": "Swing, opposite direction"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "Word 24",
   "name": "Fresh air valve status",
   "description": "0-10: fresh air valve mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "Word 25",
   "name": "Sleep mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No sleep mode",
    "1": "Sleep mode 1",
    "2": "Sleep mode 2",
    "3": "Sleep mode 3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 34,
   "documented": "Word 34",
   "name": "Clean function",
   "description": "0 = no clean function, 10-39 = contamination grade.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 35,
   "documented": "Word 35",
   "name": "Energy saving cooling lower limit",
   "description": "Lowest setpoint allowed when cooling energy saving is on (16-30).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "Word 36",
   "name": "Energy saving heating upper limit",
   "description": "Highest setpoint allowed when heating energy saving is on (16-30).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 39,
   "documented": "Word 39",
   "name": "Selection of ambient temp sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Return-air sensor",
    "2": "Wired controller sensor",
    "3": "Return air for cool/dry/fan, wired controller for heat/auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "Word 49",
   "name": "Outdoor ambient temp",
   "description": "-100 to 155.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 77,
   "documented": "Word 77",
   "name": "DRED function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "DRED1 mode",
    "2": "DRED2 mode",
    "3": "DRED3 mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "Word 82",
   "name": "Return air temp",
   "description": "Ambient temperature at the return-air port.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "Word 83",
   "name": "Light board temp",
   "description": "Ambient temperature at the display (light) board.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read words 2-25 for on/off, mode, fan, setpoint and louvres and word 4/49 for indoor and outdoor temperature; read coils 0-215 for status and fault bits. Write word 2 (0xAA/0x55), 17, 19 and 20 to control the unit.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 17,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 19,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 20,
    "why": "Setpoint"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Indoor temperature"
   },
   {
    "table": "holding_register",
    "address": 49,
    "why": "Outdoor temperature"
   },
   {
    "table": "coil",
    "address": 151,
    "why": "Compressor running"
   },
   {
    "table": "coil",
    "address": 95,
    "why": "Error output"
   }
  ],
  "enable": "The Modbus interface is built into the indoor-unit controller; the unit address and BMS mode are set from the wired controller (see the unit's service manual).",
  "watchdog": null,
  "quirks": [
   "Writes are refused while an energy-saving limit blocks the requested setpoint; the BMS should check the result.",
   "Energy saving bits 32 and 33 must be written together.",
   "Fault code 0x04 in an exception reply means the interface lost contact with the unit; it is also returned after power-up until valid data arrives."
  ],
  "setup": [
   "RS485, 9600 baud, 8 data bits, no parity, 1 stop bit.",
   "Twisted pair, kept at least 15 cm from power cables; use repeaters for long lines."
  ],
  "gotchas": [
   "In fan or auto mode the sleep setting is ignored; in auto mode the remote temperature shield is ignored.",
   "Heating commands to cooling-only units (bit 177 = 1) have no effect."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/aermec/lcg-series",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}