 "manufacturer": "Aermec",
 "manufacturer_slug": "aermec",
 "model": "WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)",
 "model_slug": "wtx-chiller",
 "short_model": "Aermec WTX",
 "aliases": [
  "WTX",
  "TBX"
 ],
 "equipment_type": "Chiller",
 "applies_to": "Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).",
 "summary": "The WTX controller is a Carel pCO5+ that answers Modbus RTU through the AER485P1 card. This map lists the integer registers (chiller mode, compressor states, currents, voltages, demand and limits, run-hour counters, unit status) and the digital points (on/off, alarm reset, relay outputs and the full alarm list for up to four Turbocor compressors).",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 19200,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The manual states protocol addresses are base 0 and that addresses start from zero; its example reads address 1 with the frame 01 03 00 01. The BMS addresses in the tables go on the wire unchanged. Integer variables sit at 5001 + the Carel index (Carel 1 = 5002)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Manuale per creazione BMS - BMS manual, Connessione tramite Internet ModBus, WTX",
  "doc_number": "5009100_00",
  "revision_date": "2017-05",
  "url": "https://www.aermec.com/download?id=6523",
  "pages": "English section: p. 13 BMS card defaults, pp. 14-15 analogue variables (not mapped), pp. 15-16 integer variables, pp. 17-21 digital variables"
 },
 "notes": [
  "Left out: all analogue variables (temperatures, pressures, setpoints, addresses 1-205). The manual lists ranges like -999.9 to 999.9 but never states the register scale, so the raw-to-value factor is not settled.",
  "Also left out: compressor speed, minimum and maximum speed registers (5006/5007, 5037-5040, 5104/5105, 5116-5119), because the '[0 ... 48000] / 10 RPM' wording does not make clear whether the register holds rpm or rpm/10; and 5003 (Aermec internal use).",
  "Run-hour counters come in two parts: an upper register in thousands of hours and a lower register in hours (0-999).",
  "Digital points are read with function 1 and written with function 5, so they are listed as coils; integer variables use functions 3 and 6."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 1,
   "documented": "1",
   "name": "On / Off Unit",
   "description": "1 = unit on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "2",
   "name": "Reset alarms",
   "description": "Write 1 to reset.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "4",
   "name": "ID1 digital input",
   "description": "0 = closed, 1 = open.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "10",
   "name": "On / Off plant by supervisor",
   "description": "BMS on/off command.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "13",
   "name": "Compressor Alarm 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 14,
   "documented": "14",
   "name": "Compressor Alarm 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 30,
   "documented": "30",
   "name": "NO1 - Pump 1 evaporator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 31,
   "documented": "31",
   "name": "NO14 - Pump 2 evaporator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 32,
   "documented": "32",
   "name": "NO2 - Antifreeze resistance",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "33",
   "name": "NO4 - EEV valve suction",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "34",
   "name": "NO5 - Conservation Consent",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "35",
   "name": "NO7 - I / LOCK 1 - Turbocharger Consent 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 36,
   "documented": "36",
   "name": "Compressor 1 ON",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 37,
   "documented": "37",
   "name": "Compressor 2 ON",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 38,
   "documented": "38",
   "name": "NO12 - I / BLOCK 2 - Turbocharger Consent 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 42,
   "documented": "42",
   "name": "NO3 - Fan / condenser pump",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 43,
   "documented": "43",
   "name": "Turbocharger Solenoid Inverter 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 44,
   "documented": "44",
   "name": "Turbocharger solenoid 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 45,
   "documented": "45",
   "name": "Solenoid turbocharger engine 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 46,
   "documented": "46",
   "name": "Solenoid turbocharger 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 49,
   "documented": "49",
   "name": "NO13 - I / BLOCK 3 - Turbocharger Consent 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 50,
   "documented": "50",
   "name": "NO15 - I / BLOCK 4 - Turbocharger Consent 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 51,
   "documented": "51",
   "name": "Compressor 3 ON",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 52,
   "documented": "52",
   "name": "Compressor 4 ON",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 53,
   "documented": "53",
   "name": "Turbocharger Solenoid Inverter 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 54,
   "documented": "54",
   "name": "Turbocharger solenoid inverter 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 55,
   "documented": "55",
   "name": "Solenoid turbocharger 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 56,
   "documented": "56",
   "name": "Turbocharged solenoid engine 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 78,
   "documented": "78",
   "name": "AL108 - Turbocor2 SCR phase",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 79,
   "documented": "79",
   "name": "AL109 - Turbocor2 Offline",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 80,
   "documented": "80",
   "name": "AL110 - Turbocor2 Startup failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 81,
   "documented": "81",
   "name": "AL111 - EVD Offline",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 82,
   "documented": "82",
   "name": "AL112 - EVD Probe S1 error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 83,
   "documented": "83",
   "name": "AL113 - EVD Probe S2 Error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 84,
   "documented": "84",
   "name": "AL114 - EVD Engine Error EEV",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 85,
   "documented": "85",
   "name": "AL115 - EVD Eeprom error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 86,
   "documented": "86",
   "name": "AL116 - Low Liquid Level",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 87,
   "documented": "87",
   "name": "AL117 - High Liquid Level",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 88,
   "documented": "88",
   "name": "AL118 - Disconnected Modbus master (communication with Turbocor)",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 89,
   "documented": "89",
   "name": "AL119 - Thermal compressor 2",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 90,
   "documented": "90",
   "name": "AL120 - EEV, Battery Low",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 93,
   "documented": "93",
   "name": "AL123 - Fuga Gas (ID16 Open)",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 100,
   "documented": "100",
   "name": "Sum of all alarms",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 101,
   "documented": "101",
   "name": "AL001 - Digital input",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 102,
   "documented": "102",
   "name": "AL002 - Voltage or phase monitor",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 103,
   "documented": "103",
   "name": "AL003 - Evaporator Antifreeze",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 104,
   "documented": "104",
   "name": "AL004 - Compressor Thermal 1",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 105,
   "documented": "105",
   "name": "AL005 - Plant Flow Switch",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 106,
   "documented": "106",
   "name": "AL006 - Digital input, EEV",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 107,
   "documented": "107",
   "name": "AL007 - Pressure High Pressure",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 108,
   "documented": "108",
   "name": "AL008 - High Pressure Transducer",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 109,
   "documented": "109",
   "name": "AL009 - Low Pressure Pressure Switch",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 110,
   "documented": "110",
   "name": "AL010 - Low Pressure Transducer",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 111,
   "documented": "111",
   "name": "AL011 - Low pressure",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 112,
   "documented": "112",
   "name": "AL012 - Fan heat / condenser pump",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 113,
   "documented": "113",
   "name": "AL013 - Heat pump 1 plant",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 114,
   "documented": "114",
   "name": "AL014 - Heat pump 2 plant",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 115,
   "documented": "115",
   "name": "AL015 - Maintenance of pump 1 plant",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 116,
   "documented": "116",
   "name": "AL016 - Maintenance of pump 2 plant",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 117,
   "documented": "117",
   "name": "AL017 - Compressor Maintenance 1",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 118,
   "documented": "118",
   "name": "AL018 - Compressor Maintenance 2",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 119,
   "documented": "119",
   "name": "AL019 - Probe U1 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 120,
   "documented": "120",
   "name": "AL020 - Probe U2 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 121,
   "documented": "121",
   "name": "AL021 - Probe U3 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 122,
   "documented": "122",
   "name": "AL022 - Probe U4 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 123,
   "documented": "123",
   "name": "AL023 - Probe U5 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 124,
   "documented": "124",
   "name": "AL024 - Probe U6 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 125,
   "documented": "125",
   "name": "AL025 - Probe U7 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 126,
   "documented": "126",
   "name": "AL026 - Probe U8 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 127,
   "documented": "127",
   "name": "AL027 - Probe U9 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 128,
   "documented": "128",
   "name": "AL028 - Probe U10 faulty or disconnected",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 129,
   "documented": "129",
   "name": "AL029 - Turbocor1 High Temperature Gas Pressed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 130,
   "documented": "130",
   "name": "AL030 - Turbocor2 High Pressure Gas Temperature",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 131,
   "documented": "131",
   "name": "AL031 - Turbocor1 Inverter temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 132,
   "documented": "132",
   "name": "AL032 - Turbocor1 Discharge temp",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 133,
   "documented": "133",
   "name": "AL033 - Turbocor1 Suction press.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 134,
   "documented": "134",
   "name": "AL034 - Turbocor1 Discharge press.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 135,
   "documented": "135",
   "name": "AL035 - Turbocor1 Rotor Lock",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 136,
   "documented": "136",
   "name": "AL036 - Turbocor1 Phase current",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 137,
   "documented": "137",
   "name": "AL037 - Turbocor1 Cavity temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 138,
   "documented": "138",
   "name": "AL038 - Turbocor1 overcurrent",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 139,
   "documented": "139",
   "name": "AL039 - Turbocor1 Compressor ratio",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 140,
   "documented": "140",
   "name": "AL040 - Turbocor1 DC Low Voltage",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 141,
   "documented": "141",
   "name": "AL041 - Turbocor1 SCR temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 142,
   "documented": "142",
   "name": "AL042 - Turbocor1 System Locked out",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 143,
   "documented": "143",
   "name": "AL043 - Turbocor1 Calibration failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 144,
   "documented": "144",
   "name": "AL044 - Turbocor1 Startup failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 145,
   "documented": "145",
   "name": "AL045 - Turbocor1 Axial displacement",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 146,
   "documented": "146",
   "name": "AL046 - Turbocor1 Axial static load",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 147,
   "documented": "147",
   "name": "AL047 - Turbocor1 Front radial disp X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 148,
   "documented": "148",
   "name": "AL048 - Turbocor1 Front radial disp Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 149,
   "documented": "149",
   "name": "AL049 - Turbocor1 Front radial load X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 150,
   "documented": "150",
   "name": "AL050 - Turbocor1 Front radial load Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 151,
   "documented": "151",
   "name": "AL051 - Turbocor1 Back radial disp X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 152,
   "documented": "152",
   "name": "AL052 - Turbocor1 Back radial disp Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 153,
   "documented": "153",
   "name": "AL053 - Turbocor1 Back radial load X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 154,
   "documented": "154",
   "name": "AL054 - Turbocor1 Back radial load Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 155,
   "documented": "155",
   "name": "AL055 - Turbocor1 Single phase Overcurrent",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 156,
   "documented": "156",
   "name": "AL056 - Turbocor1 DC High voltage",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 157,
   "documented": "157",
   "name": "AL057 - Turbocor1 High current",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 158,
   "documented": "158",
   "name": "AL058 - Turbocor1 Sensors error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 159,
   "documented": "159",
   "name": "AL059 - Turbocor1 IGBT error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 160,
   "documented": "160",
   "name": "AL060 - Turbocor1 High winding temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 161,
   "documented": "161",
   "name": "AL061 - Turbocor1 Bearing error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 162,
   "documented": "162",
   "name": "AL062 - Turbocor1 Superheat",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 163,
   "documented": "163",
   "name": "AL063 - Turbocor1 Inverter error signal",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 164,
   "documented": "164",
   "name": "AL064 - Turbocor1 AVC data missing",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 165,
   "documented": "165",
   "name": "AL065 - Turbocor1 Motor Back EMF low",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 166,
   "documented": "166",
   "name": "AL066 - Turbocor1 EEprom error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 167,
   "documented": "167",
   "name": "AL067 - Turbocor1 Generator mode",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 168,
   "documented": "168",
   "name": "AL068 - Turbocor1 SCR phase",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 169,
   "documented": "169",
   "name": "AL069 - Turbocor1 Offline",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 170,
   "documented": "170",
   "name": "AL070 - Turbocor1 Startup failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 171,
   "documented": "171",
   "name": "AL071 - Turbocor2 Inverter temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 172,
   "documented": "172",
   "name": "AL072 - Turbocor2 Discharge temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 173,
   "documented": "173",
   "name": "AL073 - Turbocor2 Suction Press.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 174,
   "documented": "174",
   "name": "AL074 - Turbocor2 Discharge press.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 175,
   "documented": "175",
   "name": "AL075 - Turbocor2 Rotor Lock",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 176,
   "documented": "176",
   "name": "AL076 - Turbocor2 Phase current",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 177,
   "documented": "177",
   "name": "AL077 - Turbocor2 Cavity temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 178,
   "documented": "178",
   "name": "AL078 - Turbocor2 overcurrent",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 179,
   "documented": "179",
   "name": "AL079 - Turbocor2 Compressor ratio",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 180,
   "documented": "180",
   "name": "AL080 - Turbocor2 DC Low Voltage",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 181,
   "documented": "181",
   "name": "AL081 - Turbocor2 SCR temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 182,
   "documented": "182",
   "name": "AL082 - Turbocor2 System Locked out",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 183,
   "documented": "183",
   "name": "AL083 - Turbocor2 Calibration failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 184,
   "documented": "184",
   "name": "AL084 - Turbocor2 Startup failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 185,
   "documented": "185",
   "name": "AL085 - Turbocor2 Axial displacement",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 186,
   "documented": "186",
   "name": "AL086 - Turbocor2 Axial static load",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 187,
   "documented": "187",
   "name": "AL087 - Turbocor2 Front radial disp X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 188,
   "documented": "188",
   "name": "AL088 - Turbocor2 Front radial disp Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 189,
   "documented": "189",
   "name": "AL089 - Turbocor2 Front radial load X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 190,
   "documented": "190",
   "name": "AL090 - Turbocor2 Front radial load Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 191,
   "documented": "191",
   "name": "AL091 - Turbocor2 Back radial disp X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 192,
   "documented": "192",
   "name": "AL092 - Turbocor2 Back radial disp Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 193,
   "documented": "193",
   "name": "AL093 - Turbocor2 Back radial load X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 194,
   "documented": "194",
   "name": "AL094 - Turbocor2 Back radial load Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 195,
   "documented": "195",
   "name": "AL095 - Turbocor2 Single phase Overcurrent",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 196,
   "documented": "196",
   "name": "AL096 - Turbocor2 DC High Voltage",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 197,
   "documented": "197",
   "name": "AL097 - Turbocor2 High current",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 198,
   "documented": "198",
   "name": "AL098 - Turbocor2 Sensors error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 199,
   "documented": "199",
   "name": "AL099 - Turbocor2 IGBT error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 200,
   "documented": "200",
   "name": "AL100 - Turbocor2 High winding temp",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 201,
   "documented": "201",
   "name": "AL101 - Turbocor2 Bearing error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 202,
   "documented": "202",
   "name": "AL102 - Turbocor2 Superheat",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 203,
   "documented": "203",
   "name": "AL103 - Turbocor2 Inverter error signal",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 204,
   "documented": "204",
   "name": "AL104 - Turbocor2 AVC data missing",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 205,
   "documented": "205",
   "name": "AL105 - Turbocor2 Motor Back EMF low",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 206,
   "documented": "206",
   "name": "AL106 - Turbocor2 EEprom error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 207,
   "documented": "207",
   "name": "AL107 - Turbocor2 Generator mode",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 225,
   "documented": "225",
   "name": "AL125 - Compressor Maintenance 3",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 226,
   "documented": "226",
   "name": "AL126 - Compressor Maintenance 4",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 227,
   "documented": "227",
   "name": "AL127 - Reset Parameters ... Reboot Card!",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 228,
   "documented": "228",
   "name": "AL128 - Turbocor3 High Temperature Gas Pressed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 229,
   "documented": "229",
   "name": "AL129 - Turbocor4 High Temperature Gas Pressed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 230,
   "documented": "230",
   "name": "Compressor Alarm 3",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 231,
   "documented": "231",
   "name": "Compressor Alarm 4",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 232,
   "documented": "232",
   "name": "AL130 - Compressor Thermal 3",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 233,
   "documented": "233",
   "name": "AL131 - Compressor Thermal 4",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 251,
   "documented": "251",
   "name": "AL151 - Turbocor3 Inverter temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 252,
   "documented": "252",
   "name": "AL152 - Turbocor3 Discharge temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 253,
   "documented": "253",
   "name": "AL153 - Turbocor3 Suction Press.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 254,
   "documented": "254",
   "name": "AL154 - Turbocor3 Discharge press.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 255,
   "documented": "255",
   "name": "AL155 - Turbocor3 Rotor Lock",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 256,
   "documented": "256",
   "name": "AL156 - Turbocor3 Phase current",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 257,
   "documented": "257",
   "name": "AL157 - Turbocor3 Cavity temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 258,
   "documented": "258",
   "name": "AL158 - Turbocor3 overcurrent",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 259,
   "documented": "259",
   "name": "AL159 - Turbocor3 Compressor ratio",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 260,
   "documented": "260",
   "name": "AL160 - Turbocor3 DC Low Voltage",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 261,
   "documented": "261",
   "name": "AL161 - Turbocor3 SCR temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 262,
   "documented": "262",
   "name": "AL162 - Turbocor3 System Locked out",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 263,
   "documented": "263",
   "name": "AL163 - Turbocor3 Calibration failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 264,
   "documented": "264",
   "name": "AL164 - Turbocor3 Startup failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 265,
   "documented": "265",
   "name": "AL165 - Turbocor3 Axial displacement",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 266,
   "documented": "266",
   "name": "AL166 - Turbocor3 Axial static load",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 267,
   "documented": "267",
   "name": "AL167 - Turbocor3 Front radial disp X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 268,
   "documented": "268",
   "name": "AL168 - Turbocor3 Front radial disp Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 269,
   "documented": "269",
   "name": "AL169 - Turbocor3 Front radial load X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 270,
   "documented": "270",
   "name": "AL170 - Turbocor3 Front radial load Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 271,
   "documented": "271",
   "name": "AL171 - Turbocor3 Back radial disp X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 272,
   "documented": "272",
   "name": "AL172 - Turbocor3 Back radial disp Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 273,
   "documented": "273",
   "name": "AL173 - Turbocor3 Back radial load X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 274,
   "documented": "274",
   "name": "AL174 - Turbocor3 Back radial load Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 275,
   "documented": "275",
   "name": "AL175 - Turbocor3 Single phase Overcurrent",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 276,
   "documented": "276",
   "name": "AL176 - Turbocor3 DC High Voltage",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 277,
   "documented": "277",
   "name": "AL177 - Turbocor3 High current",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 278,
   "documented": "278",
   "name": "AL178 - Turbocor3 Sensors error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 279,
   "documented": "279",
   "name": "AL179 - Turbocor3 IGBT error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 280,
   "documented": "280",
   "name": "AL180 - Turbocor3 High winding temp",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 281,
   "documented": "281",
   "name": "AL181 - Turbocor3 Bearing error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 282,
   "documented": "282",
   "name": "AL182 - Turbocor3 Superheat",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 283,
   "documented": "283",
   "name": "AL183 - Turbocor3 Inverter error signal",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 284,
   "documented": "284",
   "name": "AL184 - Turbocor3 24Vdc fault",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 285,
   "documented": "285",
   "name": "AL185 - Turbocor3 Motor Back EMF low",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 286,
   "documented": "286",
   "name": "AL186 - Turbocor3 EEprom error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 287,
   "documented": "287",
   "name": "AL187 - Turbocor3 Generator mode",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 288,
   "documented": "288",
   "name": "AL188 - Turbocor3 SCR phase",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 289,
   "documented": "289",
   "name": "AL189 - Turbocor3 Offline",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 290,
   "documented": "290",
   "name": "AL190 - Turbocor3 Startup failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 291,
   "documented": "291",
   "name": "AL191 - Turbocor4 Inverter temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 292,
   "documented": "292",
   "name": "AL192 - Turbocor4 Discharge temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 293,
   "documented": "293",
   "name": "AL193 - Turbocor4 Suction Press.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 294,
   "documented": "294",
   "name": "AL194 - Turbocor4 Discharge press.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 295,
   "documented": "295",
   "name": "AL195 - Turbocor4 Rotor Lock",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 296,
   "documented": "296",
   "name": "AL196 - Turbocor4 Phase current",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 297,
   "documented": "297",
   "name": "AL197 - Turbocor4 Cavity temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 298,
   "documented": "298",
   "name": "AL198 - Turbocor4 overcurrent",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 299,
   "documented": "299",
   "name": "AL199 - Turbocor4 Compressor ratio",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 300,
   "documented": "300",
   "name": "AL200 - Turbocor4 DC Low Voltage",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 301,
   "documented": "301",
   "name": "AL201 - Turbocor4 SCR temp.",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 302,
   "documented": "302",
   "name": "AL202 - Turbocor4 System Locked out",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 303,
   "documented": "303",
   "name": "AL203 - Turbocor4 Calibration failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 304,
   "documented": "304",
   "name": "AL204 - Turbocor4 Startup failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 305,
   "documented": "305",
   "name": "AL205 - Turbocor4 Axial displacement",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 306,
   "documented": "306",
   "name": "AL206 - Turbocor4 Axial static load",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 307,
   "documented": "307",
   "name": "AL207 - Turbocor4 Front radial disp X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 308,
   "documented": "308",
   "name": "AL208 - Turbocor4 Front radial disp Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 309,
   "documented": "309",
   "name": "AL209 - Turbocor4 Front radial load X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 310,
   "documented": "310",
   "name": "AL210 - Turbocor4 Front radial load Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 311,
   "documented": "311",
   "name": "AL211 - Turbocor4 Back radial disp X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 312,
   "documented": "312",
   "name": "AL212 - Turbocor4 Back radial disp Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 313,
   "documented": "313",
   "name": "AL213 - Turbocor4 Back radial load X",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 314,
   "documented": "314",
   "name": "AL214 - Turbocor4 Back radial load Y",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 315,
   "documented": "315",
   "name": "AL215 - Turbocor4 Single phase Overcurrent",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 316,
   "documented": "316",
   "name": "AL216 - Turbocor4 DC High Voltage",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 317,
   "documented": "317",
   "name": "AL217 - Turbocor4 High current",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 318,
   "documented": "318",
   "name": "AL218 - Turbocor4 Sensors error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 319,
   "documented": "319",
   "name": "AL219 - Turbocor4 IGBT error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 320,
   "documented": "320",
   "name": "AL220 - Turbocor4 High winding temp",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 321,
   "documented": "321",
   "name": "AL221 - Turbocor4 Bearing error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 322,
   "documented": "322",
   "name": "AL222 - Turbocor4 Superheat",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 323,
   "documented": "323",
   "name": "AL223 - Turbocor4 Inverter error signal",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 324,
   "documented": "324",
   "name": "AL224 - Turbocor4 24Vdc fault",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 325,
   "documented": "325",
   "name": "AL225 - Turbocor4 Motor Back EMF low",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 326,
   "documented": "326",
   "name": "AL226 - Turbocor4 EEprom error",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 327,
   "documented": "327",
   "name": "AL227 - Turbocor4 Generator mode",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 328,
   "documented": "328",
   "name": "AL228 - Turbocor4 SCR phase",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 329,
   "documented": "329",
   "name": "AL229 - Turbocor4 Offline",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 330,
   "documented": "330",
   "name": "AL230 - Turbocor4 Startup failed",
   "description": "1 = alarm active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5002,
   "documented": "5002",
   "name": "Chiller Mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Comfort",
    "1": "Economy",
    "2": "From button"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5004,
   "documented": "5004",
   "name": "Compressor state 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Lockout",
    "2": "Resetting",
    "3": "Ramping up",
    "4": "Partially closed",
    "5": "Normal",
    "6": "Max flow",
    "7": "Min IGV",
    "8": "Interlock open",
    "9": "Fault waiting",
    "10": "High temp stop",
    "11": "Loading up"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5005,
   "documented": "5005",
   "name": "Compressor state 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Lockout",
    "2": "Resetting",
    "3": "Ramping up",
    "4": "Partially closed",
    "5": "Normal",
    "6": "Max flow",
    "7": "Min IGV",
    "8": "Interlock open",
    "9": "Fault waiting",
    "10": "High temp stop",
    "11": "Loading up"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5008,
   "documented": "5008",
   "name": "Pump pump 2 plant, top part",
   "description": "Thousands of hours; add the matching lower-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "x1000 h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5009,
   "documented": "5009",
   "name": "Pump counter 1 plant, top part",
   "description": "Thousands of hours; add the matching lower-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "x1000 h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5010,
   "documented": "5010",
   "name": "Pump pump 1 plant, lower part",
   "description": "Hours below 1000; add to the matching upper-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5011,
   "documented": "5011",
   "name": "Pump pump 2 plant, lower part",
   "description": "Hours below 1000; add to the matching upper-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5012,
   "documented": "5012",
   "name": "Cold demand limit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5013,
   "documented": "5013",
   "name": "Upper part counters, comp.1",
   "description": "Thousands of hours; add the matching lower-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "x1000 h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5014,
   "documented": "5014",
   "name": "Lower part counters, comp.1",
   "description": "Hours below 1000; add to the matching upper-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5015,
   "documented": "5015",
   "name": "Upper part counters, comp.2",
   "description": "Thousands of hours; add the matching lower-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "x1000 h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5016,
   "documented": "5016",
   "name": "Lower part counters, comp.2",
   "description": "Hours below 1000; add to the matching upper-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5017,
   "documented": "5017",
   "name": "Thermostatic request",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5018,
   "documented": "5018",
   "name": "Thermostatic demand limit (from multiplier U7 power limitation)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5020,
   "documented": "5020",
   "name": "Required Limit Turbocor 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5021,
   "documented": "5021",
   "name": "Required Limit Turbocor 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5025,
   "documented": "5025",
   "name": "Total plant request",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5026,
   "documented": "5026",
   "name": "Required power Compressor 1 (%)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5027,
   "documented": "5027",
   "name": "Required Power Compressor 2 (%)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5028,
   "documented": "5028",
   "name": "Speed fans condenser pump",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5029,
   "documented": "5029",
   "name": "EEV_A, liquid electronic valve opening A (stp)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "steps",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5030,
   "documented": "5030",
   "name": "EEV_A, liquid electronic valve opening A (%)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5031,
   "documented": "5031",
   "name": "Current Compressor Power 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5032,
   "documented": "5032",
   "name": "Current compressor power 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5033,
   "documented": "5033",
   "name": "Compressor Current 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5034,
   "documented": "5034",
   "name": "Compressor Current 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5035,
   "documented": "5035",
   "name": "Compressor Voltage 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5036,
   "documented": "5036",
   "name": "Compressor Voltage 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5048,
   "documented": "5048",
   "name": "Upper part counters, comp.3",
   "description": "Thousands of hours; add the matching lower-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "x1000 h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5049,
   "documented": "5049",
   "name": "Lower part counters, comp.3",
   "description": "Hours below 1000; add to the matching upper-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5050,
   "documented": "5050",
   "name": "Upper part counters, comp.4",
   "description": "Thousands of hours; add the matching lower-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "x1000 h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5051,
   "documented": "5051",
   "name": "Lower part counters, comp.4",
   "description": "Hours below 1000; add to the matching upper-part register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5052,
   "documented": "5052",
   "name": "Software version Z (final part)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5071,
   "documented": "5071",
   "name": "Configurator - Chiller Signal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "TBX",
    "1": "WTX"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5072,
   "documented": "5072",
   "name": "WTX-Size Configurator",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5073,
   "documented": "5073",
   "name": "WTX Configurator - Efficiency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5074,
   "documented": "5074",
   "name": "WTX Configurator - Exchanger",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5075,
   "documented": "5075",
   "name": "WTX Configurator - Version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5076,
   "documented": "5076",
   "name": "WTX Configurator - Power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5102,
   "documented": "5102",
   "name": "Compressor state 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Lockout",
    "2": "Resetting",
    "3": "Ramping up",
    "4": "Partially closed",
    "5": "Normal",
    "6": "Max flow",
    "7": "Min IGV",
    "8": "Interlock open",
    "9": "Fault waiting",
    "10": "High temp stop",
    "11": "Loading up"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5103,
   "documented": "5103",
   "name": "Compressor state 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Lockout",
    "2": "Resetting",
    "3": "Ramping up",
    "4": "Partially closed",
    "5": "Normal",
    "6": "Max flow",
    "7": "Min IGV",
    "8": "Interlock open",
    "9": "Fault waiting",
    "10": "High temp stop",
    "11": "Loading up"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5106,
   "documented": "5106",
   "name": "Required Limit Turbocor 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5107,
   "documented": "5107",
   "name": "Required Limit Turbocor 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5108,
   "documented": "5108",
   "name": "Required power Compressor 3 (%)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5109,
   "documented": "5109",
   "name": "Required power Compressor 4 (%)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5110,
   "documented": "5110",
   "name": "Current compressor power 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5111,
   "documented": "5111",
   "name": "Current compressor power 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5112,
   "documented": "5112",
   "name": "Compressor Current 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5113,
   "documented": "5113",
   "name": "Compressor Current 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5114,
   "documented": "5114",
   "name": "Compressor Voltage 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5115,
   "documented": "5115",
   "name": "Compressor Voltage 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5206,
   "documented": "5206",
   "name": "Units Status",
   "description": "Value 9 is cut off in the source.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "On",
    "2": "Alarm",
    "3": "Reboot",
    "4": "Off BMS",
    "5": "Off scheduler",
    "6": "Off digital input",
    "7": "Off touch display",
    "8": "Not used"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6240,
   "documented": "6240",
   "name": "EEV_B, liquid electronic valve opening B (%)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6241,
   "documented": "6241",
   "name": "EEV_B, liquid electronic valve opening B (stp)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "steps",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read coil 1 for unit on, coil 100 (sum of all alarms) and integer 5206 for unit status; write coil 10 to switch the plant from the BMS and coil 2 to reset alarms. Demand limit is integer 5012 (R/W).",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 1,
    "why": "Unit on/off status"
   },
   {
    "table": "coil",
    "address": 10,
    "why": "Plant on/off by BMS"
   },
   {
    "table": "coil",
    "address": 2,
    "why": "Alarm reset"
   },
   {
    "table": "holding_register",
    "address": 5206,
    "why": "Unit status"
   },
   {
    "table": "holding_register",
    "address": 5012,
    "why": "Cooling demand limit %"
   },
   {
    "table": "holding_register",
    "address": 5025,
    "why": "Total plant request %"
   },
   {
    "table": "holding_register",
    "address": 5002,
    "why": "Chiller mode"
   },
   {
    "table": "coil",
    "address": 100,
    "why": "Sum of all alarms"
   }
  ],
  "enable": "Fit the AER485P1 card (RS485) or AERNET (Ethernet) in the pCO5+ BMS slot; BMS card defaults are 19200 baud, no parity, 2 stop bits.",
  "watchdog": null,
  "quirks": [
   "Addresses are protocol (base 0) addresses; do not subtract 1.",
   "Integers live at 5001 + Carel index; digitals and analogues use the plain index."
  ],
  "setup": [
   "Set the BMS address and serial settings on the pCO5+ to match the master (default 19200 baud, 8N2 as listed)."
  ],
  "gotchas": [
   "Without a stated scale, verify any analogue value you add against the unit display before using it."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/aermec/wtx-chiller",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}