 "manufacturer": "Airflow Developments",
 "manufacturer_slug": "airflow-developments",
 "model": "Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)",
 "model_slug": "entro-v",
 "short_model": "Entro-V",
 "aliases": [
  "Entro-V Basic Controller",
  "Entro-V Digital Controller",
  "90001308",
  "90001299",
  "DuplexVent Entro-V"
 ],
 "equipment_type": "Air handler (heat recovery ventilation unit)",
 "applies_to": "Airflow Entro-V MVHR units with the Entro-V control board (Basic controller 90001308 / Digital controller 90001299), per controls manual 80001022 Issue 1 (08/20).",
 "summary": "The Entro-V is a heat recovery ventilation unit whose control board acts as a Modbus RTU slave on RS-485. Only function 03 (read) and 06 (write single) are supported and every point is a single 16-bit register. The map covers on/off, fan speed stages and mode, temperatures and sensor values, output and input states, the set point and the alarm code.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The register list's ID column is the wire address. The manual's example frame reads the '2nd register' with register ID bytes 0x00 0x02, and the list starts at ID 0 (program version), so use the ID unchanged in the request."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Entro-V Controls - Basic Controller, Digital Controller and Other Control Options - User Manual",
  "doc_number": "80001022 Issue 1",
  "revision_date": "2020-08",
  "url": "https://www.specifiedby.com/airflow/entro-v-basic-controller/airflow_entro-v-basic-controller_operations_1_entro-v20controls20user20manual.pdf",
  "pages": "pp. 21-23 (section 9, Modbus function and register list), p. 25 (fault code list), pp. 28-32 (full parameter list)",
  "unofficial": true
 },
 "notes": [
  "Airflow does not host this manual as a direct PDF on airflow.com that we could find; this copy sits in Airflow's product listing on the SpecifiedBy library and is the unaltered Airflow document (Airflow Developments Ltd footer).",
  "Registers listed here are those in section 9.4 'Modbus Register List' (the IDs flagged for Modbus in the full parameter list). The full list on pp. 28-32 has more IDs (service settings, I/O assignment, timers); they are not flagged as Modbus points and are left out.",
  "Temperatures have a -40 to 80 °C range with multiplier 0.1, so they are treated as signed 16-bit; the manual does not spell out the signed encoding.",
  "The CO2 register (30) is printed with multiplier 0.1 and unit ppm; check against a known reading before relying on it.",
  "Alarm code values come from the fault code list (Part III, p. 25)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Version of program",
   "description": "Installed program version as MMYY.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Unit on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Alarm code",
   "description": "Active fault number; 0 when running normally.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Normal operation",
    "1": "ERR 1 Fire alarm (FRE input)",
    "2": "ERR 2 Electric heater failure (HTI)",
    "3": "ERR 3 Fresh air fan failure",
    "4": "ERR 4 Exhaust air fan failure",
    "5": "ERR 5 Outdoor air temperature sensor failure (T_OA)",
    "6": "ERR 6 Return air temperature sensor failure (T_RA)",
    "7": "ERR 7 Panel temperature sensor failure (T_PA)",
    "8": "ERR 8 Supply air temperature sensor failure (T_SA)",
    "9": "ERR 9 Sensor-1 failure (SE1)",
    "10": "ERR 10 Sensor-2 failure (SE2)",
    "11": "ERR 11 Freon pressure failure (DXH/DXL)",
    "12": "ERR 12 Filter dirty alarm (FIL)",
    "13": "ERR 13 Clock malfunction",
    "14": "ERR 14 RF communication failure",
    "15": "ERR 15 Digital controller communication failure",
    "16": "ERR 16 Constant flow maximum limit failure"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3",
   "name": "Fresh air fan speed",
   "description": "Measured fan speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Exhaust air fan speed",
   "description": "Measured fan speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "5",
   "name": "PWM value of fresh air fan",
   "description": "0-100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "PWM value of exhaust air fan",
   "description": "0-100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "20",
   "name": "Outdoor air temperature",
   "description": "Sensor T_OA, -40 to 80 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "21",
   "name": "Return air temperature",
   "description": "Sensor T_RA, -40 to 80 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "22",
   "name": "Supply air temperature",
   "description": "Sensor T_SA, -40 to 80 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "23",
   "name": "Panel temperature",
   "description": "Controller panel sensor T_PA, -40 to 80 °C; listed read/write.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "24",
   "name": "Sensor 1 value",
   "description": "Input voltage on SE1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "25",
   "name": "Sensor 2 value",
   "description": "Input voltage on SE2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "26",
   "name": "RF sensor 1 value",
   "description": "Voltage value of wireless sensor SR1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "27",
   "name": "RF sensor 2 value",
   "description": "Voltage value of the second wireless sensor (table labels it SR1).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "29",
   "name": "Relative humidity",
   "description": "Processed humidity sensor reading.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "30",
   "name": "CO2 value",
   "description": "Processed CO2 sensor reading; multiplier 0.1 as printed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "31",
   "name": "Pressure value",
   "description": "Processed pressure sensor reading.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "hPa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "60",
   "name": "DO1 output [RUN]",
   "description": "Run indication relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "61",
   "name": "DO2 output [FLT]",
   "description": "Fault indication relay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "62",
   "name": "LP0 output [BYP]",
   "description": "Bypass output.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "63",
   "name": "LP1 output [HT1]",
   "description": "Electric heater stage 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "64",
   "name": "LP2 output [HT2]",
   "description": "Electric heater stage 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "65",
   "name": "LP3 output [PH1]",
   "description": "Electric preheater stage 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "66",
   "name": "LP4 output [PH2]",
   "description": "Electric preheater stage 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 80,
   "documented": "80",
   "name": "DI1 input [BST]",
   "description": "Boost input.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 81,
   "documented": "81",
   "name": "DI2 input [BMS]",
   "description": "External BMS on/off input.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "82",
   "name": "DI3 input [FRE]",
   "description": "Fire input.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "83",
   "name": "DI4 input [HTI]",
   "description": "Heater failure input.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 84,
   "documented": "84",
   "name": "DI5 input [FIL]",
   "description": "Filter alarm input.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "100",
   "name": "Mode selection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Standard fan speed",
    "1": "VOD"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "101",
   "name": "Fresh air fan speed stage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Low",
    "1": "Mid",
    "2": "High",
    "3": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "102",
   "name": "Exhaust air fan speed stage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Low",
    "1": "Mid",
    "2": "High",
    "3": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 128,
   "documented": "128",
   "name": "Set temperature",
   "description": "Temperature set point, 18-28 °C, default 22.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Wire RS-485 to the MODBUS connector on the control board, poll address 1 at 9600 8N1 with FC03, and use FC06 to write. Start/stop with ID 1, set fan stages with IDs 101/102 and the set point with ID 128; watch ID 2 for faults.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1,
    "why": "Unit on/off"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Alarm code"
   },
   {
    "table": "holding_register",
    "address": 101,
    "why": "Fresh air fan speed stage"
   },
   {
    "table": "holding_register",
    "address": 102,
    "why": "Exhaust air fan speed stage"
   },
   {
    "table": "holding_register",
    "address": 22,
    "why": "Supply air temperature"
   },
   {
    "table": "holding_register",
    "address": 20,
    "why": "Outdoor air temperature"
   },
   {
    "table": "holding_register",
    "address": 21,
    "why": "Return air temperature"
   },
   {
    "table": "holding_register",
    "address": 128,
    "why": "Set temperature"
   }
  ],
  "enable": "Modbus is built into the control board. Slave address (ID 153), link speed (ID 154, 0 = 9600) and frame type (ID 155, 0 = N81 RTU) are service-level parameters in the full list.",
  "watchdog": null,
  "quirks": [
   "Only FC03 and FC06 are supported: no FC04, no FC16 multi-register writes.",
   "IDs are 0-based wire addresses.",
   "Fan speed stage values run 0 = Low, 1 = Mid, 2 = High, 3 = Stop."
  ],
  "setup": [
   "Defaults: address 1, 9600 baud, no parity, 8 data bits, 1 stop bit.",
   "Fit a 120 ohm terminating resistor at each end of a long RS-485 line, as the manual advises.",
   "Avoid duplicate addresses when several units share the bus."
  ],
  "gotchas": [
   "The link to the digital controller panel uses its own Modbus address parameters (IDs 235/236), separate from the BMS slave address (ID 153)."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/airflow-developments/entro-v",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}