 "manufacturer": "Airzone",
 "manufacturer_slug": "airzone",
 "model": "Aidoo Pro Modbus control for direct-expansion (split / VRF) air conditioners",
 "model_slug": "aidoo-pro-modbus-dx",
 "short_model": "Aidoo Pro Modbus DX",
 "aliases": [
  "Aidoo Pro",
  "Aidoo Pro Modbus",
  "Airzone Aidoo Modbus"
 ],
 "equipment_type": "VRF / split AC gateway",
 "applies_to": "Airzone Aidoo Pro units configured for Modbus output and connected to a direct-expansion AC unit; register table 'Registers for Direct Expansion units' of the Aidoo - Modbus integration manual (v. 201). The air-to-water table in the same manual is not covered.",
 "summary": "Aidoo Pro is a small Airzone interface for an air-conditioning unit that can serve Modbus RTU on RS-485 to a BMS. The direct-expansion map gives on/off, mode, setpoint, fan, louvres, room and refrigerant-circuit temperatures, pressures, current, error codes and 32-bit energy counters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Registers are numbered from 0 (unit on/off is register 0) and the command description puts this number in the 'register address' field, so the printed number is the wire address."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "Integration Manual Aidoo - Modbus",
  "doc_number": "v. 201",
  "revision_date": null,
  "url": "https://thermosilesia.pl/assets/default/system_object_files/4bc5a150b45a2a7401add97664eff2aa.pdf",
  "pages": "pp. 4-13 (serial settings, function codes, frames, direct-expansion registers)",
  "unofficial": true
 },
 "notes": [
  "Distributor copy: airzonecontrol.com answers automated requests with a bot check (not bypassed) and no other Airzone-hosted copy was found; this multilingual PDF carries Airzone's own layout and address.",
  "32-bit energy counters span two registers with the low word first: the manual's worked example reads (1) 0x1215 and (2) 0x0001 as 0x00011215 = 70165 kWh, so CDAB.",
  "The manual does not state signed or unsigned for 16-bit values; the remaining registers are listed as UINT16 because their normal values are not negative.",
  "The Modbus slave address is set in the Airzone Cloud app (Airtools > Integration > Modbus) or via register 56.",
  "Function codes 03, 04, 06 and 16 are supported.",
  "External (outdoor) temperature (35) and outdoor heat exchanger temperature (39) are left out: these routinely go below 0 °C and the manual gives no sign convention for 16-bit values."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Unit status on/off",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Setpoint",
   "description": "°C x 10 (230 = 23 °C). Limits depend on the AC unit.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2",
   "name": "Local (room) temperature",
   "description": "°C x 10 (230 = 23 °C). Must be above 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3",
   "name": "Mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "Cool",
    "3": "Heat",
    "4": "Fan",
    "5": "Dry"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Fan speed (percentage)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "25": "Silent",
    "50": "Low",
    "75": "Medium",
    "100": "High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "5",
   "name": "Louver vertical",
   "description": "4 bits per louver: 0-7 position, 8 auto, 9 swing, 10 swirl. Louver 1 = bits 0-3.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Louver 1 position nibble (bits 0-3)",
    "4": "Louver 2 position nibble (bits 4-7)",
    "8": "Louver 3 position nibble (bits 8-11)",
    "12": "Louver 4 position nibble (bits 12-15)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Louver horizontal",
   "description": "4 bits per louver: 0-7 position, 8 auto, 9 swing, 10 swirl. Louver 1 = bits 0-3.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Louver 1 position nibble (bits 0-3)",
    "4": "Louver 2 position nibble (bits 4-7)",
    "8": "Louver 3 position nibble (bits 8-11)",
    "12": "Louver 4 position nibble (bits 12-15)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7",
   "name": "Unit error code part 1",
   "description": "ASCII characters of the indoor unit error code (first part).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Unit error code part 2",
   "description": "ASCII characters of the indoor unit error code (second part).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "14",
   "name": "Available modes",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Auto",
    "1": "Cool",
    "2": "Heat",
    "3": "Ventilation",
    "4": "Dry"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "15",
   "name": "Available speeds",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Auto",
    "1": "Super-low",
    "2": "Low",
    "3": "Medium-low",
    "4": "Medium",
    "5": "Medium-high",
    "6": "High",
    "7": "Super-high"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "16",
   "name": "Available louvers",
   "description": "Bits 8-11 / 12-15 give the number of vertical / horizontal positions (0-7).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Auto up/down",
    "3": "Swing up/down",
    "4": "Swing left/right",
    "5": "Swirl"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "17",
   "name": "Setpoint limit max air cool",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "18",
   "name": "Setpoint limit min air cool",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "19",
   "name": "Setpoint limit max air heat",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "20",
   "name": "Setpoint limit min air heat",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "21",
   "name": "Setpoint limit max air auto",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "22",
   "name": "Setpoint limit min air auto",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "23",
   "name": "Setpoint limit max air ventilation",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "24",
   "name": "Setpoint limit min air ventilation",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "25",
   "name": "Setpoint limit max air dry",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 26,
   "documented": "26",
   "name": "Setpoint limit min air dry",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 36,
   "documented": "36",
   "name": "Return temperature",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 37,
   "documented": "37",
   "name": "Indoor heat exchanger temperature",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 38,
   "documented": "38",
   "name": "Indoor gas pipe temperature",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40",
   "name": "Outdoor compressor discharge temperature",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 41,
   "documented": "41",
   "name": "Outdoor expansion valve position",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "pulses",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "42",
   "name": "Indoor expansion valve position",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "pulses",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "43",
   "name": "Evaporation pressure",
   "description": "MPa x 100 (127 = 1.27 MPa).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "MPa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "44",
   "name": "Condensation pressure",
   "description": "MPa x 100 (127 = 1.27 MPa).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "MPa",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "45",
   "name": "Current consumption",
   "description": "A x 10 (70 = 7 A).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "53",
   "name": "Work temperature",
   "description": "°C x 10 (230 = 23 °C).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "54",
   "name": "Fan speed (numeric)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Silent",
    "2": "Low",
    "3": "Medium",
    "4": "High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "55",
   "name": "Error value",
   "description": "Numeric indoor unit error value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "56",
   "name": "Modbus slave address",
   "description": "Default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "57",
   "name": "Port baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "100",
    "1": "300",
    "2": "500",
    "3": "1200",
    "4": "2400",
    "5": "4800",
    "6": "7800",
    "7": "9600",
    "8": "19200",
    "9": "57600",
    "10": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "58",
   "name": "Port parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Odd",
    "2": "Even"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "59",
   "name": "Emergency heat status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Deactivated",
    "1": "Activated"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "60",
   "name": "Input T1T2 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Deactivated",
    "1": "Activated"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 73,
   "documented": "73 / 74",
   "name": "Total energy generated in heating",
   "description": "Low word at 73, high word at 74 (manual example 0x1215 + 0x0001 = 70165).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 75,
   "documented": "75",
   "name": "Actual power generated in heating",
   "description": "Example 0x1CAC = 7340 W.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 76,
   "documented": "76 / 77",
   "name": "Total energy generated in cooling",
   "description": "Low word at 76, high word at 77 (manual example 0x1215 + 0x0001 = 70165).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 78,
   "documented": "78",
   "name": "Actual power generated in cooling",
   "description": "Example 0x1CAC = 7340 W.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 82,
   "documented": "82",
   "name": "Actual power generated by photovoltaic",
   "description": "Example 0x1CAC = 7340 W.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 83,
   "documented": "83 / 84",
   "name": "Total energy produced",
   "description": "Low word at 83, high word at 84 (manual example 0x1215 + 0x0001 = 70165).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 85,
   "documented": "85 / 86",
   "name": "Total energy consumed by heat pump",
   "description": "Low word at 85, high word at 86 (manual example 0x1215 + 0x0001 = 70165).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 87,
   "documented": "87",
   "name": "Actual power consumed by heat pump",
   "description": "Example 0x1CAC = 7340 W.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 88,
   "documented": "88",
   "name": "Actual power consumed by whole building",
   "description": "Example 0x1CAC = 7340 W.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 89,
   "documented": "89 / 90",
   "name": "Electric resistor consumption in heating",
   "description": "Low word at 89, high word at 90 (manual example 0x1215 + 0x0001 = 70165).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 93,
   "documented": "93 / 94",
   "name": "Compressor consumption in heating",
   "description": "Low word at 93, high word at 94 (manual example 0x1215 + 0x0001 = 70165).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 95,
   "documented": "95 / 96",
   "name": "Compressor consumption in cooling",
   "description": "Low word at 95, high word at 96 (manual example 0x1215 + 0x0001 = 70165).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 99,
   "documented": "99 / 100",
   "name": "Total consumption",
   "description": "Low word at 99, high word at 100 (manual example 0x1215 + 0x0001 = 70165).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the Aidoo output to Modbus and the slave ID in the Airzone Cloud app, connect RS-485 at 19200 8E1, then use registers 0-4 for on/off, setpoint (x10), mode and fan and poll 2, 7-8 and 55 for room temperature and errors.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "On/off"
   },
   {
    "table": "holding_register",
    "address": 3,
    "why": "Mode"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Setpoint (x10)"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Fan speed"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Room temperature (x10)"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Error code (ASCII)"
   },
   {
    "table": "holding_register",
    "address": 14,
    "why": "Modes the unit supports"
   }
  ],
  "enable": "In the Airzone Cloud app: Airtools > advanced configuration via Bluetooth > Integration > output Modbus, set the Modbus ID.",
  "watchdog": null,
  "quirks": [
   "Mode codes start at 1 (1 Auto, 2 Cool, 3 Heat, 4 Fan, 5 Dry).",
   "Fan speed can be set as a percentage (register 4) or a step number (register 54).",
   "Energy counters are low word first (CDAB)."
  ],
  "setup": [
   "Factory serial settings 19200 baud, 8 data bits, even parity, 1 stop bit, half duplex.",
   "Slave address default 1."
  ],
  "gotchas": [
   "The manual footnotes that the local temperature (register 2) must be greater than 0."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/airzone/aidoo-pro-modbus-dx",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}