 "manufacturer": "Armstrong International",
 "manufacturer_slug": "armstrong-international",
 "model": "Brain DRV25 / DRV40 / DRV80 digital recirculation valve (Modbus RTU)",
 "model_slug": "brain-drv",
 "short_model": "Brain DRV",
 "aliases": [
  "DRV25",
  "DRV40",
  "DRV80",
  "Brain",
  "IOM-776"
 ],
 "equipment_type": "Actuator / valve",
 "applies_to": "Armstrong International Brain digital recirculation (thermostatic mixing) valves DRV25, DRV40 and DRV80 on their RS-485 Modbus RTU port, per IOM-776 Brain Modbus Networking (2024).",
 "summary": "Microprocessor-controlled hot-water mixing/recirculation valve that blends hot and cold water to a setpoint, with high/low alerts, an over-temperature error and a thermal-disinfection cycle. Over Modbus RTU it exposes holding registers for setpoint, status, outlet and inlet temperatures (0.1 °C), error codes, alarm limits, disinfection commands and an error log.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "IOM-776 lists plain register numbers starting at 0 (Unit Address is register 0) and supports function codes 03, 06 and 16. A register numbered 0 can only be a protocol (PDU) address, so the listed numbers are used as wire addresses."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Guide to The Brain Networking Installation and Operation - Brain Modbus Networking",
  "doc_number": "IOM-776 (1345022-W2-E)",
  "revision_date": "2024",
  "url": "https://armstronginternational.com/wp-content/uploads/IOM_TheBrain_DRV_Networking_IOM_NA_EN_20241209.pdf",
  "pages": "pp. 11 (Modbus format and functions), 12-14 (Table 1 registers), 15 (programming and disinfection sequence), 17 (enumerations)"
 },
 "notes": [
  "Armstrong International (hot-water group) is a different company from Armstrong Fluid Technology (pumps).",
  "Addressing: resolved as 0-based because the table includes a real register 0 (Unit Address), which only exists in 0-based numbering; the guide gives no example frame.",
  "Temperatures are listed as '0.1 Deg C' and are used with scale 0.1. Signedness is not stated; they are typed UINT16 (hot-water temperatures). Offset Temperature (407, 0.1 Deg C, R/W) is left out because an offset can be negative and the guide does not say whether it is signed.",
  "Left out: all two-part 'Long' values (serial number 106-107, manufacture date 108-109, commissioning date 116-117, operation count 121-122, on time 123-124, unused hours 128-129, disinfection dates 156-157, clock 288-289 and the error log dates), because the guide does not say which half is high; the 16-register Valve Identity/Location string (139-154), because character order is not stated; and register 114, printed with two conflicting rows.",
  "The DRV25/DRV40/DRV80 support columns in the table are graphical marks and are not reproduced; some registers (alerts, relay) apply only to DRV40/80.",
  "Allow at least 5 s between a write and the next read."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0",
   "name": "Unit Address",
   "description": "Modbus address 1-31.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1",
   "name": "Setpoint Temperature",
   "description": "Blend (outlet) setpoint.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4",
   "name": "Valve Status",
   "description": "Write 0/1/2 only; set Off before changing registers 400-411.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off (R/W)",
    "1": "On (R/W)",
    "2": "Full cold (R/W)",
    "6": "Disinfection (read only)",
    "7": "Error (read only)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6",
   "name": "Valve Outlet Temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8",
   "name": "Valve Error Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Hot Inlet Temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "11",
   "name": "Cold Inlet Temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "23",
   "name": "Disinfection Target Temperature",
   "description": "From the DRV maximum setpoint up to 99.9 °C.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "110",
   "name": "Valve Firmware Type Number",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "111",
   "name": "Valve Firmware Version Number",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "112",
   "name": "Valve Configuration ID",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "113",
   "name": "Valve Configuration Version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 115,
   "documented": "115",
   "name": "Adaptor (Bluetooth) Firmware Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 127,
   "documented": "127",
   "name": "ID of Valve Service Engineer",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 155,
   "documented": "155",
   "name": "Hours Since Last Disinfection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 159,
   "documented": "159",
   "name": "Last Completed Disinfection Result",
   "description": "Logic value; meaning not listed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "306",
   "name": "Arm Disinfection Command",
   "description": "Write 0x6172 to arm; trigger within 10 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 307,
   "documented": "307",
   "name": "Trigger Disinfection Command",
   "description": "Write 0x5452 after arming to start disinfection.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "308",
   "name": "Abort Disinfection Command",
   "description": "Write any value to stop disinfection; from full hot the valve goes full cold (Error Temp).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 309,
   "documented": "309",
   "name": "Soft Valve Reset Command",
   "description": "Write 0x1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "314",
   "name": "Disinfection Cool Down",
   "description": "Write any value to end disinfection with full cold flow.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "400",
   "name": "DRV Serial Line Address",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Standard",
    "1": "Alternate"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "401",
   "name": "Disinfection Enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "64": "Enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "402",
   "name": "Disinfection Timeout",
   "description": "Alerts/errors suppressed for this time; max 1800 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 403,
   "documented": "403",
   "name": "High Alert",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 404,
   "documented": "404",
   "name": "Low Alert",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 405,
   "documented": "405",
   "name": "Error Temperature",
   "description": "Outlet above this drives the valve full cold and latches an error.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 406,
   "documented": "406",
   "name": "Relay Active",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 408,
   "documented": "408",
   "name": "Valve Temperature Units",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°F",
    "1": "°C"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 409,
   "documented": "409",
   "name": "DRV Maximum Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 410,
   "documented": "410",
   "name": "DRV Minimum Setpoint",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 411,
   "documented": "411",
   "name": "DRV Default Setpoint",
   "description": "Setpoint used after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "412",
   "name": "Spare/Remote Thermistor 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 413,
   "documented": "413",
   "name": "Thermistor 2",
   "description": "Printed as 'DRV Default Setpoint Thermistor 2'.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 433,
   "documented": "433",
   "name": "Reset Usage Logs Command",
   "description": "Write any value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 434,
   "documented": "434",
   "name": "Reset Error Logs",
   "description": "Write any value.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 435,
   "documented": "435",
   "name": "Error 1 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 438,
   "documented": "438",
   "name": "Error 2 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 441,
   "documented": "441",
   "name": "Error 3 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 444,
   "documented": "444",
   "name": "Error 4 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 447,
   "documented": "447",
   "name": "Error 5 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 450,
   "documented": "450",
   "name": "Error 6 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 453,
   "documented": "453",
   "name": "Error 7 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 456,
   "documented": "456",
   "name": "Error 8 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 459,
   "documented": "459",
   "name": "Error 9 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 462,
   "documented": "462",
   "name": "Error 10 Code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Over temperature",
    "2": "Stuck motor",
    "3": "Motor calibration",
    "4": "Valve failure",
    "5": "Thermistor failure",
    "6": "Unconfigured",
    "7": "A to D error",
    "8": "RAM error",
    "9": "EE error",
    "10": "Flash error",
    "11": "Algorithm error",
    "12": "Controller error",
    "13": "Battery error",
    "14": "Scheduler error"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Wire the DRV's RS-485 port at 9600 8N1, then read registers 4 (status), 6 (outlet temperature) and 8 (error code). Write the setpoint to register 1 in tenths of °C; set register 4 to Off before changing configuration registers 400-411 and back to On afterwards.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 6,
    "why": "Outlet (blended) temperature"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Setpoint"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Valve status / on-off-full cold"
   },
   {
    "table": "holding_register",
    "address": 8,
    "why": "Active error code"
   },
   {
    "table": "holding_register",
    "address": 10,
    "why": "Hot inlet temperature"
   },
   {
    "table": "holding_register",
    "address": 11,
    "why": "Cold inlet temperature"
   }
  ],
  "enable": "Modbus RTU is fixed at 9600 bps, no parity, 8 data bits, 1 stop bit. Set the unit address (1-31, read back in register 0) before connecting to the network: on DRV40/80 with the DRV Programming Software through the CN3 port (valve Off), on DRV25 with the SAGE mobile app over Bluetooth. The same software switches the CN2 network port from SAGE BS to Modbus.",
  "watchdog": null,
  "quirks": [
   "Disinfection needs registers 23, 401 and 402 set up, then 0x6172 to 306 and 0x5452 to 307 within 10 seconds; writes out of order are rejected.",
   "DRV25: fit the CN10 jumper to switch in the end-of-line termination resistor if long cables or reflections make communication unreliable."
  ],
  "setup": [
   "Function codes 03, 06 and 16 only.",
   "Modbus is 9600 bps only (BACnet supports higher rates).",
   "Use Cat5 twisted pair in a daisy chain; do not wire the valves in a star."
  ],
  "gotchas": [
   "An over-temperature error drives the valve full cold and stays latched until power is cycled.",
   "Abort (308) while the cycle is at full hot sends the valve full cold and shows Error Temp until power is cycled."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/armstrong-international/brain-drv",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}