 "manufacturer": "AutomationDirect",
 "manufacturer_slug": "automationdirect",
 "model": "DURApulse GS10 AC drive",
 "model_slug": "gs10",
 "short_model": "GS10",
 "aliases": [
  "DURApulse GS10",
  "GS10 micro drive"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "GS10 drives (built-in RS-485 port) per the GS10 user manual, 1st edition rev. C, chapter 5.",
 "summary": "The DURApulse GS10 is AutomationDirect's micro general-purpose drive with a built-in RS-485 Modbus RTU/ASCII port. Control goes through command words at 2000h-2002h and status is read from 2100h upward; every parameter Pxx.yy is also a register. This map covers the command and status words, frequency, voltages, the main serial setup parameters and the block-transfer registers.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 38400,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed in hex with the matching Modicon number (2000h = 48193, 2100h = 48449, 0900h = 42305). The hex value is the wire address; the manual's RTU examples send 21 02 to read 2102h and 20 00 to write 2000h."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "DURApulse GS10 Drive User Manual - Chapter 5: Serial Communications",
  "doc_number": "GS10-M 1st Edition, Rev. C (chapter 5)",
  "revision_date": null,
  "url": "https://cdn.automationdirect.com/static/manuals/gs10m/ch5.pdf",
  "pages": "communication parameters pp. 5-2 to 5-3; status and command addresses pp. 5-4 to 5-6; RTU examples pp. 5-13 to 5-14"
 },
 "notes": [
  "AutomationDirect's own manual chapter (cdn.automationdirect.com).",
  "Parameter-to-register rule: Pxx.yy is at hex xx*256 + yy (P09.00 = 0900h = 42305; the block-transfer example P02.22 = 0216h). Only selected P09 communication parameters are listed; the rest are in chapter 4.",
  "Values printed as XXX.XX carry two implied decimals (scale 0.01) and XXX.X one (scale 0.1).",
  "Left out: output current (2104h), whose decimal places shift with the current and depend on 211Fh; output torque (210Bh), because its sign handling is not stated; P09.01 baud rate, P09.03 time-out and P09.09 response delay, whose raw encodings of decimal values are not given in this chapter.",
  "Factory serial settings from the P09 summary: address 1, 38.4 kbps, protocol 13 (8 data bits, no parity, 2 stop bits, RTU).",
  "Up to 12 words can be read in one request (function 03).",
  "Control word 1 (2000h): bits 1-0 = 01 stop, 10 run, 11 jog + run; bits 5-4 = 01 forward, 10 reverse, 11 change direction; bits 7-6 accel/decel set; bits 11-8 multi-step speed; bit 12 enables bits 6-11; bits 14-13 = 01 keypad, 10 per P00.21, 11 change operation source."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 1553,
   "documented": "0611h (41554)",
   "name": "P06.17 Fault record 1",
   "description": "Most recent fault code (same coding as status monitor 1).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2304,
   "documented": "0900h (42305)",
   "name": "P09.00 Communication address",
   "description": "RS-485 station address, 1-254.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2306,
   "documented": "0902h (42307)",
   "name": "P09.02 COM1 transmission fault treatment",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Warn and continue",
    "1": "Fault and ramp to stop",
    "2": "Fault and coast to stop",
    "3": "No warning, no fault, continue"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2308,
   "documented": "0904h (42309)",
   "name": "P09.04 COM1 communication protocol",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "7N2 ASCII",
    "2": "7E1 ASCII",
    "3": "7O1 ASCII",
    "4": "7E2 ASCII",
    "5": "7O2 ASCII",
    "6": "8N1 ASCII",
    "7": "8N2 ASCII",
    "8": "8E1 ASCII",
    "9": "8O1 ASCII",
    "10": "8E2 ASCII",
    "11": "8O2 ASCII",
    "12": "8N1 RTU",
    "13": "8N2 RTU",
    "14": "8E1 RTU",
    "15": "8O1 RTU",
    "16": "8E2 RTU",
    "17": "8O2 RTU"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2315,
   "documented": "090Bh (42316)",
   "name": "P09.11 Block transfer 1",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2316,
   "documented": "090Ch (42317)",
   "name": "P09.12 Block transfer 2",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2317,
   "documented": "090Dh (42318)",
   "name": "P09.13 Block transfer 3",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2318,
   "documented": "090Eh (42319)",
   "name": "P09.14 Block transfer 4",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2319,
   "documented": "090Fh (42320)",
   "name": "P09.15 Block transfer 5",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2320,
   "documented": "0910h (42321)",
   "name": "P09.16 Block transfer 6",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2321,
   "documented": "0911h (42322)",
   "name": "P09.17 Block transfer 7",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2322,
   "documented": "0912h (42323)",
   "name": "P09.18 Block transfer 8",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2323,
   "documented": "0913h (42324)",
   "name": "P09.19 Block transfer 9",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2324,
   "documented": "0914h (42325)",
   "name": "P09.20 Block transfer 10",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2325,
   "documented": "0915h (42326)",
   "name": "P09.21 Block transfer 11",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2326,
   "documented": "0916h (42327)",
   "name": "P09.22 Block transfer 12",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2327,
   "documented": "0917h (42328)",
   "name": "P09.23 Block transfer 13",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2328,
   "documented": "0918h (42329)",
   "name": "P09.24 Block transfer 14",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2329,
   "documented": "0919h (42330)",
   "name": "P09.25 Block transfer 15",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2330,
   "documented": "091Ah (42331)",
   "name": "P09.26 Block transfer 16",
   "description": "Holds the address of another register; reads/writes go through to it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "2000h (48193)",
   "name": "Control word 1",
   "description": "Run/stop and direction codes; see notes.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "Run/stop code bit 0 (with bit 1)",
    "1": "Run/stop code bit 1",
    "4": "Direction code bit 0 (with bit 5)",
    "5": "Direction code bit 1",
    "12": "Enable bits 6-11 (accel set, step speed)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "2001h (48194)",
   "name": "Frequency command",
   "description": "Speed reference in 0.01 Hz.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "2002h (48195)",
   "name": "Control word 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": null,
   "bits": {
    "0": "External fault (EF) on",
    "1": "Fault reset",
    "2": "Base block (BB) on",
    "5": "Enable fire mode"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8448,
   "documented": "2100h (48449)",
   "name": "Status monitor 1",
   "description": "High byte warning code, low byte error code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8449,
   "documented": "2101h (48450)",
   "name": "Status monitor 2",
   "description": "Bits 1-0 run state (00 stop, 01 decel, 10 standby, 11 running); bits 4-3 direction.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Run state bit 0",
    "1": "Run state bit 1",
    "2": "JOG command",
    "3": "Direction bit 0",
    "4": "Direction bit 1",
    "8": "Frequency from communication",
    "9": "Frequency from analog/terminal",
    "10": "Run command from communication",
    "11": "Parameters locked",
    "12": "Copy parameters from keypad enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8450,
   "documented": "2102h (48451)",
   "name": "Frequency command (status)",
   "description": "Active frequency command.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8451,
   "documented": "2103h (48452)",
   "name": "Output frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8453,
   "documented": "2105h (48454)",
   "name": "DC bus voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8454,
   "documented": "2106h (48455)",
   "name": "Output voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8455,
   "documented": "2107h (48456)",
   "name": "Multi-step speed step",
   "description": "Current multi-step speed step number.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8457,
   "documented": "2109h (48458)",
   "name": "Counter value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8458,
   "documented": "210Ah (48459)",
   "name": "Output power factor angle",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8460,
   "documented": "210Ch (48461)",
   "name": "Actual motor speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the drive's run source and frequency source to RS-485, then write 2000h (run/stop/direction) and 2001h (frequency in 0.01 Hz) in one function-16 write. Poll 2100h-2106h for fault, state and frequency.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 8192,
    "why": "Run/stop/direction command"
   },
   {
    "table": "holding_register",
    "address": 8193,
    "why": "Frequency command 0.01 Hz"
   },
   {
    "table": "holding_register",
    "address": 8448,
    "why": "Warning/error code"
   },
   {
    "table": "holding_register",
    "address": 8449,
    "why": "Drive state"
   },
   {
    "table": "holding_register",
    "address": 8451,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 8453,
    "why": "DC bus voltage"
   }
  ],
  "enable": "Set P09.00 address and P09.04 protocol (codes 12-17 are RTU), then select RS-485 as the frequency reference (P00.20 = 1 in Remote/Auto or P00.30 = 1 in Local/Hand, per the manual's note) and as the run-command source (see chapter 4).",
  "watchdog": "P09.03 COM1 time-out detection (0.0-100.0 s, factory 0.0) sets the loss timeout; P09.02 selects warn, ramp-stop, coast-stop or no action on loss.",
  "quirks": [
   "Hex addresses are the wire addresses.",
   "2000h-2002h are write-only command words.",
   "If the RS-485 frequency reference exceeds P01.00, the drive runs at maximum output frequency."
  ],
  "setup": [
   "Use P09.04 to pick RTU framing (e.g. 13 = 8N2 RTU); all nodes must match."
  ],
  "gotchas": [
   "Block transfer registers P09.11-P09.26 let one read/write reach scattered parameters: write the target address (e.g. 8448 for 2100h) into a block-transfer slot.",
   "Run command bits are a 2-bit code, not independent flags."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/automationdirect/gs10",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}