 "manufacturer": "AutomationDirect",
 "manufacturer_slug": "automationdirect",
 "model": "DURApulse GS3 AC drive",
 "model_slug": "gs3",
 "short_model": "GS3",
 "aliases": [
  "DURApulse GS3",
  "GS3-21P0",
  "GS3-22P0",
  "GS3-23P0",
  "GS3-25P0",
  "GS3-27P5",
  "GS3-2010",
  "GS3-2015",
  "GS3-2020",
  "GS3-2025"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "All GS3 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.",
 "summary": "The GS3 is an AutomationDirect AC drive with a built-in RS-485 port running Modbus ASCII or RTU. Drive parameters P0.00-P9.xx map to holding registers (parameter group x 256 + number), and read-only status registers at 2100h report fault code, run state, frequencies, voltages and load. This map covers the status block and the P9 serial control parameters used to run the drive over Modbus.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The manual lists each register in hex and as a Modicon number: hex 0000h = 40001, 2100h = 48449. The hex value is the wire address. CLICK PLCs need a six-digit form (402331 instead of 42331)."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "DURApulse GS3 AC Drives User Manual - Chapter 5: GS3 Modbus Communications",
  "doc_number": "GS3-M 2nd Edition (chapter 5)",
  "revision_date": null,
  "url": "https://cdn.automationdirect.com/static/manuals/gs3m/ch5.pdf",
  "pages": "Comm parameter summary pp. 5-2 to 5-3; parameter addresses pp. 5-4 to 5-8; status addresses pp. 5-9 to 5-11; example message near the end of the chapter"
 },
 "notes": [
  "AutomationDirect's own manual chapter (cdn.automationdirect.com).",
  "Parameter-to-register rule: Px.yy is at hex x*256 + yy (e.g. P9.26 = 091Ah = 42331); the full list is in the chapter's parameter address tables. Only the P9 communication/control parameters are included here.",
  "Status values marked XXX.X in the manual carry one implied decimal (scale 0.1).",
  "Scale Frequency is split into low word (2108h) and high word (2109h), so it is listed as a 32-bit value with the low word first (CDAB); its unit depends on P8.01.",
  "P9.05 (communication time-out, 0.1-60.0 s) is left out because its raw encoding is not stated in this chapter.",
  "The factory protocol (P9.02 = 0) is Modbus ASCII 7N2; set 3, 4 or 5 for RTU.",
  "Speed reference scaling: the manual's example frame 01 10 09 1B 00 02 04 02 58 00 01 writes 0258h (600) for 60 Hz; it starts at 091Bh although the table puts P9.26 at 091Ah (42331). The table address is used here.",
  "Left out: Output Current (2104h), Power Factor Angle (210Ah) and PID setpoint/feedback (210Ch/210Dh) because no decimal format is given for them.",
  "P9.01 baud codes are not readable in the chapter's summary table; the setup example uses 01 = 9600 baud.",
  "The P9.00/P9.01 rows of the chapter's summary table are not readable, so their factory defaults are not given here."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 2304,
   "documented": "0900h (42305)",
   "name": "P9.00 Communication Address",
   "description": "Drive address 1-254.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2305,
   "documented": "0901h (42306)",
   "name": "P9.01 Transmission Speed",
   "description": "Baud rate code; the setup example uses 01 = 9600 baud.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2306,
   "documented": "0902h (42307)",
   "name": "P9.02 Communication Protocol",
   "description": "Factory default 0 is Modbus ASCII.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "ASCII 7N2",
    "1": "ASCII 7E1",
    "2": "ASCII 7O1",
    "3": "RTU 8N2",
    "4": "RTU 8E1",
    "5": "RTU 8O1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2307,
   "documented": "0903h (42308)",
   "name": "P9.03 Transmission Fault Treatment",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Display fault, keep running",
    "1": "Display fault, ramp to stop",
    "2": "Display fault, coast to stop",
    "3": "No fault, keep running"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2308,
   "documented": "0904h (42309)",
   "name": "P9.04 Time Out Detection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2330,
   "documented": "091Ah (42331)",
   "name": "P9.26 Serial Comm Speed Reference",
   "description": "0.0-400.0 Hz with implied decimal (600 = 60.0 Hz).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2331,
   "documented": "091Bh (42332)",
   "name": "P9.27 Serial Comm RUN Command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Run"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2332,
   "documented": "091Ch (42333)",
   "name": "P9.28 Serial Comm Direction Command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Forward",
    "1": "Reverse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2333,
   "documented": "091Dh (42334)",
   "name": "P9.29 Serial Comm External Fault",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No fault",
    "1": "External fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2334,
   "documented": "091Eh (42335)",
   "name": "P9.30 Serial Comm Fault Reset",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No action",
    "1": "Fault reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2335,
   "documented": "091Fh (42336)",
   "name": "P9.31 Serial Comm JOG Command",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Stop",
    "1": "Jog"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8448,
   "documented": "2100h (48449)",
   "name": "Status Monitor 1",
   "description": "Present fault code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Over-current (oc)",
    "2": "Over-voltage (ov)",
    "3": "Overheat (oH)",
    "4": "Overload (oL)",
    "5": "Thermal overload 1 (oL1)",
    "6": "Over-torque (oL2)",
    "7": "External fault (EF)",
    "8": "CPU failure 1 (cF1)",
    "9": "CPU failure 2 (cF2)",
    "10": "CPU failure 3 (cF3)",
    "11": "Hardware protection failure (HPF)",
    "12": "Over-current during accel (ocA)",
    "13": "Over-current during decel (ocd)",
    "14": "Over-current at steady state (ocn)",
    "16": "Low voltage (Lv)",
    "18": "External base-block (bb)",
    "19": "Auto adjust accel/decel failure (cFA)",
    "20": "Software protection code (codE)",
    "15": "Ground fault or fuse failure (GFF)",
    "17": "Input power 3-phase loss (PHL)",
    "21": "PID feedback loss (FbE)",
    "22": "Encoder feedback loss",
    "23": "Output shorted (occ)",
    "24": "Momentary power loss"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8449,
   "documented": "2101h (48450)",
   "name": "Status Monitor 2",
   "description": "Bits 0-1 run state (0 stop..3 run); bits 3-4 direction (0 FWD..3 REV).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "JOG active",
    "8": "Frequency source = serial comm (P4.00 = 5)",
    "9": "Frequency source = AI terminal",
    "10": "Operation source = serial comm (P3.00 = 3 or 4)",
    "11": "Parameters locked (P9.07 = 1)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8450,
   "documented": "2102h (48451)",
   "name": "Frequency Command F",
   "description": "Frequency setpoint (XXX.X).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8451,
   "documented": "2103h (48452)",
   "name": "Output Frequency H",
   "description": "Output frequency (XXX.X).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8453,
   "documented": "2105h (48454)",
   "name": "DC Bus Voltage d",
   "description": "(XXX.X)",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8454,
   "documented": "2106h (48455)",
   "name": "Output Voltage U",
   "description": "RMS line-to-line output voltage (XXX.X).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8455,
   "documented": "2107h (48456)",
   "name": "Motor RPM",
   "description": "Estimated motor speed.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8456,
   "documented": "2108h (48457)",
   "name": "Scale Frequency",
   "description": "Output frequency x P8.01; low word at 2108h, high word at 2109h.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8459,
   "documented": "210Bh (48460)",
   "name": "% Load",
   "description": "Output current / drive rated current x 100.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8464,
   "documented": "2110h (48465)",
   "name": "Firmware Version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set P9.02 to an RTU mode, P3.00 to serial operation and P4.00 = 5 for serial frequency source, then write speed (P9.26, x10) and run (P9.27). Monitor Status Monitor 1/2 and output frequency at 2100h-2103h.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2330,
    "why": "Speed reference"
   },
   {
    "table": "holding_register",
    "address": 2331,
    "why": "Run/stop"
   },
   {
    "table": "holding_register",
    "address": 2332,
    "why": "Direction"
   },
   {
    "table": "holding_register",
    "address": 8448,
    "why": "Fault code"
   },
   {
    "table": "holding_register",
    "address": 8449,
    "why": "Run state bits"
   },
   {
    "table": "holding_register",
    "address": 8451,
    "why": "Output frequency"
   }
  ],
  "enable": "Set P3.00 (source of operation) to 3 or 4 and P4.00 (source of frequency) to 5 for serial control, as referenced in Status Monitor 2; set P9.00-P9.02 for address, baud and protocol from the keypad.",
  "watchdog": "P9.04 enables communication time-out detection, P9.05 sets the time (0.1-60.0 s) and P9.03 selects the reaction (keep running, ramp stop, coast stop).",
  "quirks": [
   "Factory protocol is Modbus ASCII, not RTU.",
   "Speed reference has an implied decimal: write 600 for 60.0 Hz.",
   "Hex addresses are wire addresses: 091Ah = 2330 decimal = 42331 Modicon."
  ],
  "setup": [
   "P9.00 address 1-254, P9.01 baud code (the setup example uses 01 = 9600 baud), P9.02 protocol/format.",
   "Writes to P0-P8 parameters can be grouped through the block transfer parameters P9.11 onward."
  ],
  "gotchas": [
   "Some faults only show in Status Monitor 1 after a hard trip; warnings may not appear there."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/automationdirect/gs3",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}