 "manufacturer": "Autonics",
 "manufacturer_slug": "autonics",
 "model": "TK series PID temperature controller (Modbus RTU)",
 "model_slug": "tk-series",
 "short_model": "Autonics TK",
 "aliases": [
  "TK4S",
  "TK4M",
  "TK4H",
  "TK4W",
  "TK4L",
  "TK4S-14RR",
  "TK4"
 ],
 "equipment_type": "Sensor / controller (PID temperature controller)",
 "applies_to": "Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.",
 "summary": "Panel-mount heating and cooling PID temperature controller with Modbus RTU. Coils start/stop control and auto-tuning; input registers report PV, active SV, decimal point, heating/cooling MV, heater current and indicator bits; holding registers carry setpoints, multi-SV, alarm limits, PID parameters, input and output setup and communication settings.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 2,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Rows print a 6-digit reference (000001/100001/300001/400001 style) and the hex protocol address in brackets, e.g. 301001 (03E8); the bracketed hex value is the wire address."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "TK Series Communication Manual (Simultaneous Heating & Cooling Output PID Temperature Controllers)",
  "doc_number": "MCT-TKC1-V2.2-EN",
  "revision_date": null,
  "url": "https://cdn.automationdirect.com/static/manuals/autonics/autonicstkcommunicationsmanual.pdf",
  "unofficial": true,
  "pages": "pp. 23-41 (mapping tables)"
 },
 "notes": [
  "Autonics does not publish a static public link to this manual; this is the unaltered Autonics document hosted by distributor AutomationDirect.",
  "PV, SV, alarm limits and multi-SV values are signed display counts whose decimal point depends on the input type; read 301002 (decimal point) and scale accordingly. They are listed with scale 1.",
  "Default communication settings (address 1, 9600 bps, no parity, 2 stop bits, writes enabled) are the defaults printed in the communication parameter rows.",
  "Left out: hysteresis, dead band, OFF offset, input correction, scaling and alarm-mode registers whose scale depends on the input range, plus the input-type code table.",
  "Registers 400301-400330 are the user-parameter group (copies of chosen parameters).",
  "Left out: heater current monitoring input register 301008, because the manual prints only the display range 0.0..50.0 and not the raw value scaling."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "000001 (0000)",
   "name": "RUN/STOP",
   "description": "Control output run/stop.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RUN",
    "1": "STOP"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "000002 (0001)",
   "name": "Auto-tuning execute",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "100001 (0000)",
   "name": "°C unit indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "100002 (0001)",
   "name": "°F unit indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "100003 (0002)",
   "name": "% unit indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 3,
   "documented": "100004 (0003)",
   "name": "OUT1 indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "100005 (0004)",
   "name": "OUT2 indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "100006 (0005)",
   "name": "AT indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "100007 (0006)",
   "name": "SV1 indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "100008 (0007)",
   "name": "SV2 indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 8,
   "documented": "100009 (0008)",
   "name": "SV3 indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 9,
   "documented": "100010 (0009)",
   "name": "AL1 indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 10,
   "documented": "100011 (000A)",
   "name": "AL2 indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 11,
   "documented": "100012 (000B)",
   "name": "MAN indicator",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 12,
   "documented": "100013 (000C)",
   "name": "DI-1 input",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 13,
   "documented": "100014 (000D)",
   "name": "DI-2 input",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 100,
   "documented": "300101 (0064)",
   "name": "Product number H",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 101,
   "documented": "300102 (0065)",
   "name": "Product number L",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 102,
   "documented": "300103 (0066)",
   "name": "Hardware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 103,
   "documented": "300104 (0067)",
   "name": "Software version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 104,
   "documented": "300105-300114 (0068-0071)",
   "name": "Model name",
   "description": "ASCII model text, e.g. 'TK4 14RR'.",
   "data_type": "STRING",
   "length": 10,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1000,
   "documented": "301001 (03E8)",
   "name": "PV (present value)",
   "description": "-1999..9999; Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "31000": "OPEN (sensor break)",
    "30000": "HHHH (over range)",
    "-30000": "LLLL (under range)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1001,
   "documented": "301002 (03E9)",
   "name": "Decimal point location",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "0",
    "1": "0.0",
    "2": "0.00",
    "3": "0.000"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1002,
   "documented": "301003 (03EA)",
   "name": "Indicator unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "°C",
    "1": "°F",
    "2": "%",
    "3": "OFF"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1003,
   "documented": "301004 (03EB)",
   "name": "SV setting value",
   "description": "Active setpoint. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1004,
   "documented": "301005 (03EC)",
   "name": "Heating side MV",
   "description": "0..1000 = 0.0..100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1005,
   "documented": "301006 (03ED)",
   "name": "Cooling side MV",
   "description": "0..1000 = 0.0..100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1006,
   "documented": "301007 (03EE)",
   "name": "Indicator / input status bits",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "°C unit indicator",
    "1": "°F unit indicator",
    "2": "% unit indicator",
    "3": "OUT1 indicator",
    "4": "OUT2 indicator",
    "5": "AT indicator",
    "6": "SV1 indicator",
    "7": "SV2 indicator",
    "8": "SV3 indicator",
    "9": "AL1 indicator",
    "10": "AL2 indicator",
    "11": "MAN indicator",
    "12": "DI-1 input",
    "13": "DI-2 input"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "400001 (0000)",
   "name": "SV set value",
   "description": "Within L-SV..H-SV. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "400002 (0001)",
   "name": "Heating MV (manual)",
   "description": "0..1000 = 0.0..100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "400003 (0002)",
   "name": "Cooling MV (manual)",
   "description": "0..1000 = 0.0..100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "400004 (0003)",
   "name": "Auto/Manual control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "AUTO",
    "1": "MAN"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "400051 (0032)",
   "name": "R-S control output run/stop",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RUN",
    "1": "STOP"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "400052 (0033)",
   "name": "SV-N multi SV number",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "SV-0",
    "1": "SV-1",
    "2": "SV-2",
    "3": "SV-3"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "400053 (0034)",
   "name": "CT-A heater current monitoring",
   "description": "0..500 = 0.0..50.0 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "400054 (0035)",
   "name": "AL1.L alarm 1 low limit",
   "description": "Deviation or absolute value per alarm mode. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "400055 (0036)",
   "name": "AL1.H alarm 1 high limit",
   "description": "Deviation or absolute value per alarm mode. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "400056 (0037)",
   "name": "AL2.L alarm 2 low limit",
   "description": "Deviation or absolute value per alarm mode. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "400057 (0038)",
   "name": "AL2.H alarm 2 high limit",
   "description": "Deviation or absolute value per alarm mode. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "400058 (0039)",
   "name": "SV-0 set value",
   "description": "Multi-SV setpoint. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "400059 (003A)",
   "name": "SV-1 set value",
   "description": "Multi-SV setpoint. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "400060 (003B)",
   "name": "SV-2 set value",
   "description": "Multi-SV setpoint. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "400061 (003C)",
   "name": "SV-3 set value",
   "description": "Multi-SV setpoint. Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "400062 (003D)",
   "name": "AL3.L alarm 3 low limit",
   "description": "Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "400063 (003E)",
   "name": "AL3.H alarm 3 high limit",
   "description": "Raw count; decimal point from 301002.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "400101 (0064)",
   "name": "AT auto-tuning run/stop",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "OFF",
    "1": "ON"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "400102 (0065)",
   "name": "H-P heating proportional band",
   "description": "1..9999 = 0.1..999.9 (°C/°F or %).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "400103 (0066)",
   "name": "C-P cooling proportional band",
   "description": "1..9999 = 0.1..999.9.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "400104 (0067)",
   "name": "H-I heating integral time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "400105 (0068)",
   "name": "C-I cooling integral time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "400106 (0069)",
   "name": "H-D heating derivative time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "400107 (006A)",
   "name": "C-D cooling derivative time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "400109 (006C)",
   "name": "REST manual reset",
   "description": "0..1000 = 0.0..100.0 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 151,
   "documented": "400152 (0097)",
   "name": "UNIT sensor temperature unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 157,
   "documented": "400158 (009D)",
   "name": "D.UNT display unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "°F",
    "2": "%",
    "3": "OFF"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 163,
   "documented": "400164 (00A3)",
   "name": "C-MD control type",
   "description": "Standard: 0 PID, 1 ON/OFF. Heat&cool: 0 P.P, 1 P.ON, 2 ON.P, 3 ON.ON.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 218,
   "documented": "400219 (00DA)",
   "name": "ADRS communication address",
   "description": "1..99.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 219,
   "documented": "400220 (00DB)",
   "name": "BPS communication speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "2400",
    "1": "4800",
    "2": "9600",
    "3": "19200",
    "4": "38400"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 220,
   "documented": "400221 (00DC)",
   "name": "PRTY parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "Even",
    "2": "Odd"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 221,
   "documented": "400222 (00DD)",
   "name": "STP stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1",
    "1": "2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 222,
   "documented": "400223 (00DE)",
   "name": "RSW.T response waiting time",
   "description": "5..99 ms, default 20.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 223,
   "documented": "400224 (00DF)",
   "name": "COMW communication write",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Enabled",
    "1": "Disabled"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 301001-301008 with FC04 for PV, decimal point, SV and MV; write the setpoint to 400001 and use coil 0 for run/stop. Check 301002 to place the decimal point.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 1000,
    "why": "Process value"
   },
   {
    "table": "input_register",
    "address": 1001,
    "why": "Decimal point"
   },
   {
    "table": "input_register",
    "address": 1003,
    "why": "Active setpoint"
   },
   {
    "table": "input_register",
    "address": 1004,
    "why": "Heating output %"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Write setpoint"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "Run/stop"
   }
  ],
  "enable": "Communication write (400224) must be Enabled (default) for Modbus writes.",
  "watchdog": null,
  "quirks": [
   "PV reports 31000 for sensor open, 30000 / -30000 for over/under range.",
   "The bracketed hex is the wire address."
  ],
  "setup": [
   "Address 1..99 (default 1), 2400-38400 bps (default 9600), parity none, 2 stop bits."
  ],
  "gotchas": [
   "Display values carry no fixed scale; Temp.L input types report one decimal place, so always apply the decimal point from 301002."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/autonics/tk-series",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}