 "manufacturer": "Berner",
 "manufacturer_slug": "berner",
 "model": "Air curtain with IntelliSwitch Gen 5 controller (AIR BMS package)",
 "model_slug": "intelliswitch-gen5-air-bms",
 "short_model": "IntelliSwitch Gen 5",
 "aliases": [
  "IntelliSwitch Gen 5",
  "Berner AIR BMS",
  "AIR BMS Package"
 ],
 "equipment_type": "Air curtain controller (Air handler / door heater)",
 "applies_to": "Berner air curtains with the IntelliSwitch Gen 5 control and the AIR BMS package; register document 3.1.0212 (January 2025).",
 "summary": "Berner's IntelliSwitch Gen 5 air-curtain control exposes a small Modbus map over RS-485 (RTU or ASCII) and Ethernet/Wi-Fi (TCP). Input registers report door temperature, door switch, heater and motor state, E-stop lock and error codes; holding registers set mode (including a BMS mode), fan speed, target temperature, delays and BMS calls for heat and fan.",
 "transport": [
  "RTU",
  "ASCII",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "Berner lists addresses from 1 and says to send the offset from address 1: address 101 is requested as 100. Input and holding registers use separate address ranges (1-11/201-206 and 101-109)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Berner AIR BMS Package - Modbus Registers",
  "doc_number": "3.1.0212",
  "revision_date": "2025-01",
  "url": "https://berner.com/wp-content/uploads/2025/07/Berner-AIR-BMS-Modbus-Registers-3.1.0212.pdf",
  "pages": "p. 1 (communication settings), p. 2 (input registers), p. 3 (holding registers and addressing note)"
 },
 "notes": [
  "All registers are signed 16-bit (INT16); temperatures are x10 (215 = 21.5 °C).",
  "Serial settings are configurable (300-115200 bps, 5-8 data bits, 1-2 stop bits, none/odd/even/space/mark parity, ID 1-247, timeout 1-999 s with no stated purpose); the document does not state factory defaults. TCP defaults to DHCP and port 502.",
  "Error code registers 201-206 hold codes without a code list in this document."
 ],
 "integration": {
  "summary": "Put the controller in BMS mode (holding 101 = 5), then drive it with call for heat (107) and call for fan (108). Monitor door temperature (input 1), door switch (3), heater and motor state (6, 7) and E-stop (11).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 100,
    "why": "Mode (5 = BMS)"
   },
   {
    "table": "holding_register",
    "address": 106,
    "why": "Call for heat in BMS mode"
   },
   {
    "table": "holding_register",
    "address": 107,
    "why": "Call for fan in BMS mode"
   },
   {
    "table": "holding_register",
    "address": 102,
    "why": "Target temperature °C"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "Door temperature °C"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Door switch"
   },
   {
    "table": "input_register",
    "address": 10,
    "why": "E-stop locked"
   }
  ],
  "enable": "The document points to the IntelliSwitch Gen 5 Quick Start Guide or the Berner app for Ethernet setup; it does not say where the serial settings are made.",
  "watchdog": "The serial settings include a timeout of 1-999 s; the document does not say what it does.",
  "quirks": [
   "Input and holding registers do not share addresses, by design.",
   "Temperatures exist in both °C and °F registers."
  ],
  "setup": [
   "RS-485 for RTU/ASCII; Ethernet or Wi-Fi for TCP (DHCP by default)."
  ],
  "gotchas": [
   "While E-stop locked (input 11) is 1, mode and the BMS call registers are forced to 0 and read-only."
  ]
 },
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "1",
   "name": "Temperature at the door (°C)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "2",
   "name": "Temperature at the door (°F)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "3",
   "name": "Door switch status",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "4",
   "name": "Door open count since midnight",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "5",
   "name": "External thermostat status",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "6",
   "name": "Heater status",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "7",
   "name": "Motor state",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "Low",
    "2": "Default"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "8",
   "name": "Motor speed",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "9",
   "name": "Number of available motor speeds",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "10",
   "name": "Heating supported",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "11",
   "name": "E-stop locked",
   "description": "When 1, marked holding registers reset to 0 and become read-only.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 200,
   "documented": "201",
   "name": "Error code 1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 201,
   "documented": "202",
   "name": "Error code 2",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 202,
   "documented": "203",
   "name": "Error code 3",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 203,
   "documented": "204",
   "name": "Error code 4",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 204,
   "documented": "205",
   "name": "Error code 5",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 205,
   "documented": "206",
   "name": "Error code 6",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "101",
   "name": "Mode",
   "description": "Locked while E-stop is active.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On",
    "2": "Auto",
    "4": "Comfort+",
    "5": "BMS"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 101,
   "documented": "102",
   "name": "Fan speed",
   "description": "1 to N, where N is the number of speeds (1, 2, 3 or 10).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 102,
   "documented": "103",
   "name": "Target temperature (°C)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "104",
   "name": "Target temperature (°F)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "scale_factor_ref": null,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 104,
   "documented": "105",
   "name": "Time delay",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "106",
   "name": "Cool down delay",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "107",
   "name": "Call for heat (BMS mode)",
   "description": "Locked while E-stop is active.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "108",
   "name": "Call for fan (BMS mode)",
   "description": "Locked while E-stop is active.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 108,
   "documented": "109",
   "name": "Heater disabled",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "page": "https://easymodbus.com/modbus-register-maps/berner/intelliswitch-gen5-air-bms",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}