 "manufacturer": "Bonfiglioli",
 "manufacturer_slug": "bonfiglioli",
 "model": "ACTIVE / ACTIVE Cube inverter with CM-232 / CM-485 (Modbus RTU/ASCII)",
 "model_slug": "active-cube",
 "short_model": "ACTIVE Cube",
 "aliases": [
  "ACTIVE Cube",
  "ACU",
  "ACU 201",
  "ACU 401",
  "ACU 210",
  "ACU 410",
  "ACTIVE",
  "ACT",
  "CM-232",
  "CM-485",
  "CM-MODBUS"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Bonfiglioli ACTIVE (ACT) and ACTIVE Cube (ACU 201/401/210/410) inverters with a CM-232 or CM-485 communication module set to Modbus, per manual VEC 383 R4 (04/23).",
 "summary": "Bonfiglioli's ACTIVE and ACTIVE Cube inverters speak Modbus RTU or ASCII through a CM-232 or CM-485 communication module. As on the Agile, the register address is the parameter number plus the data set number in the top 4 bits, and 32-bit parameters are read as two registers at one parameter address. This map covers the control and status words, RAM references, error and warning readouts and the module's Modbus settings.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The start address field carries the parameter number (0-1599) in bits 0-11 and the data set (0-9) in bits 12-15, sent as-is: parameter 481 in data set 1 is 0x11E1, in data set 0 it is 0x01E1 (= 481). This map lists data set 0 addresses (parameter number). For another data set add 0x1000 x data set (data set 2 of parameter 372 = 0x2174)."
 },
 "default_word_order": "ABCD",
 "firmware": "32-bit access with functions 3/16: ACU 5.1.12 or later",
 "source": {
  "title": "Active Cube - MODBUS Communication Module CM-MODBUS / CM2-MODBUS, Frequency Inverter 230 V / 400 V",
  "doc_number": "VEC 383 R4",
  "revision_date": "2023-04",
  "url": "https://www.bonfiglioli.com/_default_upload_bucket/ACT_ACU_CM232_485_Modbus_VEC383R4.pdf",
  "pages": "5.2 commissioning pp. 19-21 (baud 10, parity 1375, address 1376, protocol 395, watchdog 413); 6.3 function codes and start-address layout; 32-bit write examples; 9 control/reference pp. 57-69; 10-11 actual values and parameter list pp. 70-71"
 },
 "notes": [
  "Word order comes from the manual's 32-bit write examples (44.50 Hz to parameter 482 sends 00 00 11 62; an out-of-range value sends 00 03 0D 40): high word first.",
  "A 32-bit parameter occupies one parameter number: request 2 registers starting at that number.",
  "Values with decimals are sent as integers; the scale for 484 and 524 follows their two-decimal ranges.",
  "The data set of 410, 484 and 524 is always zero; they are RAM values and are not written to EEPROM.",
  "Parameters stored in four data sets return error 9 in register 11 when read with data set 0 and the sets differ; register 11 must be read before the next write is accepted.",
  "In control via remote contacts (412 = 2) the control word bits act as virtual digital inputs (bit 0 = STOA+STOB on ACU, S1IND on ACT); a software-only release is not possible.",
  "Left out: 282/283 reference bus/ramp frequency (data type not stated) and 392 (selection list not given).",
  "Application warnings 274 exist on ACU only; on ACT bit 15 of 270 is the V-belt warning instead.",
  "Function codes 3/16 for 32-bit values need ACU firmware 5.1.12 or later; ACT must use functions 100/101 (same high-word-first layout in the manual's examples)."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10",
   "name": "Baud rate",
   "description": "Factory 4 = 19200; active after reset (P34 = 123) or power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "2400",
    "2": "4800",
    "3": "9600",
    "4": "19200",
    "5": "57600",
    "6": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "11",
   "name": "VABus SST error register",
   "description": "Modbus/VABus error code (0-15); read it to acknowledge write errors.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 249,
   "documented": "249",
   "name": "Active data set",
   "description": "Currently active data set 1-4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 260,
   "documented": "260",
   "name": "Actual error",
   "description": "Code of the current fault; reachable over the bus only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 270,
   "documented": "270",
   "name": "Warnings",
   "description": "Bit-coded warnings; several can be set at once.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Warning Ixt (set with bit 1 or 2)",
    "1": "Short-time Ixt",
    "2": "Long-time Ixt",
    "3": "Heat sink temperature",
    "4": "Inside temperature",
    "5": "Current limit",
    "6": "Init",
    "7": "Motor temperature",
    "8": "Mains phase failure",
    "9": "Motor protective switch",
    "10": "Fmax",
    "11": "Analog input MFI1A",
    "12": "Analog input MFI2A",
    "13": "Systembus slave in fault",
    "14": "DC link voltage (Udc)",
    "15": "ACU: application warning (see 274); ACT: V-belt"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 274,
   "documented": "274",
   "name": "Application warnings",
   "description": "Application warning bits (ACU only).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 395,
   "documented": "395",
   "name": "Protocol",
   "description": "Factory 0 (VABus); takes effect immediately.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "VABus",
    "1": "P-Bus (special applications)",
    "2": "Modbus RTU",
    "3": "Modbus ASCII"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 410,
   "documented": "410",
   "name": "Control word",
   "description": "Used when Local/Remote 412 = 1 (statemachine); write in data set 0.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Switch on",
    "1": "Enable voltage",
    "2": "Quick stop (0 = quick stop)",
    "3": "Enable operation",
    "7": "Reset fault (rising edge)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 411,
   "documented": "411",
   "name": "Status word",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Ready to switch on",
    "1": "Switched on",
    "2": "Operation enabled",
    "3": "Error",
    "4": "Voltage enabled (mains present)",
    "5": "Quick stop",
    "6": "Switch on disabled",
    "7": "Warning (see 270)",
    "9": "Remote",
    "10": "Reference value reached",
    "11": "Limit value reached",
    "15": "Warning 2 (fault switch-off imminent)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "412",
   "name": "Local/Remote",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Control via contacts",
    "1": "Control via statemachine (control word 410)",
    "2": "Control via remote contacts"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 413,
   "documented": "413",
   "name": "RS232/RS485 watchdog timer",
   "description": "0 = off (factory); fault F2010 if no valid exchange in this time.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 414,
   "documented": "414",
   "name": "Data set selection",
   "description": "0 = digital inputs; 1-4 = set by bus; 5 = switch only when not released.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 484,
   "documented": "484",
   "name": "Reference frequency RAM",
   "description": "Long, two decimals: -999.99 to 999.99 Hz. Read/write 2 registers at 484.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 524,
   "documented": "524",
   "name": "Reference percentage RAM",
   "description": "Long, two decimals: -300.00 to 300.00 %. Read/write 2 registers at 524.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1375,
   "documented": "1375",
   "name": "Modbus parity",
   "description": "Factory 0 = even.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even",
    "1": "Odd",
    "2": "None"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1376,
   "documented": "1376",
   "name": "Modbus address",
   "description": "1-247, factory 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set 395 = 2 (Modbus RTU), baud 10 and parity 1375, address 1376, reset the inverter, then 412 = 1. Write 484 (2 registers, 0.01 Hz) and step control word 410 through 0x0006, 0x0007, 0x000F; poll 411 and 260.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 410,
    "why": "Control word"
   },
   {
    "table": "holding_register",
    "address": 411,
    "why": "Status word"
   },
   {
    "table": "holding_register",
    "address": 484,
    "why": "Frequency reference, 0.01 Hz (32-bit)"
   },
   {
    "table": "holding_register",
    "address": 412,
    "why": "Local/Remote: 1 = statemachine"
   },
   {
    "table": "holding_register",
    "address": 260,
    "why": "Actual error"
   },
   {
    "table": "holding_register",
    "address": 395,
    "why": "Protocol: 2 = Modbus RTU"
   },
   {
    "table": "holding_register",
    "address": 11,
    "why": "Modbus error register"
   }
  ],
  "enable": "The CM module ships in VABus (395 = 0): set 395 = 2 (RTU) or 3 (ASCII) with the keypad or VPlus. Baud rate 10 (factory 19200) applies only after a reset (parameter 34 = 123) or mains off/on. For parity 1375 (factory even) the manual contradicts itself (reset needed in 5.2.1, immediate in 5.2.2), so reset after changing it. Address 1376 (factory 1) applies at once. Set 412 = 1 for control-word operation; the hardware release (STOA/STOB on ACU, S1IND on ACT) plus a Start Right/Left input are still needed.",
  "watchdog": "413 RS232/RS485 watchdog timer, 0-10000 s (factory 0 = off). When it expires the inverter trips with F2010 Watchdog RS232/RS485.",
  "quirks": [
   "Address = parameter number + 0x1000 x data set. Data set 0 writes all four EEPROM sets; data sets 5-9 write RAM only (set + 5). Control word 410 and references 484/524 always use data set 0.",
   "32-bit values are high word first and are read as 2 registers at one parameter number.",
   "Reading or writing a 32-bit parameter with function 3/16 needs ACU firmware 5.1.12 or later; on ACT the manual says this is still in preparation, so use functions 100/101 there.",
   "Picking the wrong protocol in 395 cuts off the CM port; fix it with the keypad or VPlus."
  ],
  "setup": [
   "CM-485 has a termination switch; switch it on only at the two ends of the bus.",
   "Recommended cable lengths for CM-485: 1200 m at 19200, 300 m at 115200 baud."
  ],
  "gotchas": [
   "A write error blocks further writes until register 11 is read.",
   "A baud rate change does nothing until the inverter is reset; reset after a parity change too."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/bonfiglioli/active-cube",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}