 "manufacturer": "Brainboxes",
 "manufacturer_slug": "brainboxes",
 "model": "ED-588 Ethernet digital I/O (Modbus TCP)",
 "model_slug": "ed-588",
 "short_model": "ED-588",
 "aliases": [
  "ED-588",
  "ED588"
 ],
 "equipment_type": "Sensor / remote I/O module",
 "applies_to": "Brainboxes ED-588 Ethernet I/O module with the protocol set to Modbus TCP.",
 "summary": "The ED-588 is a Brainboxes Ethernet I/O module with 8 digital inputs with pulse counters and 8 digital outputs. It ships speaking the Brainboxes ASCII protocol; once its web page is switched to Modbus TCP, the I/O is exposed as coils, discrete inputs and registers. This map lists every object in the manufacturer's product table.",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "The table prints logical (on-the-wire) addresses in hex next to 984-style numbers. Use the hex value directly: input register 0x0020 is requested at address 32 and corresponds to 30033."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Using Modbus TCP with Brainboxes products",
  "doc_number": null,
  "revision_date": null,
  "url": "https://www.brainboxes.com/files/catalog/product/ED/ED-516/documents/Brainboxes%20Modbus%20TCP%20Manual.pdf",
  "pages": "p. 3 (web settings), p. 5 (address conventions), section 9.1 on p. 7 (product table)"
 },
 "notes": [
  "The product table gives every object twice: as a logical (wire) address in hex and as a 984-style address (logical + 1 with a 0/1/3/4 prefix). The two columns agree, so the hex logical address is used here.",
  "Channel numbers in register names count from 0, matching the order of the logical addresses (channel 0 = first address of each block).",
  "The manual does not state the counter width; each counter occupies one 16-bit register in the table, so it is listed as UINT16.",
  "Brainboxes' own Node-RED guide (docs.brainboxes.com, 'Using Modbus TCP with Node-RED', ED-588) writes coil address 0 for output 0 and reads input registers from address 0 for inputs 0-7, which matches the product table. The manual's section 10 worked example (ED-527 only) instead puts the outputs at 0x0001-0x0010; that example also labels a 0xFF00 write as 'low', so it is treated as an error here.",
  "The same objects can also be reached with IEC 61131 %M/%MW addresses in some PLCs; those are listed in the manual and not repeated here.",
  "The manual does not say which bit of a packed register belongs to which channel, so no bit list is given; check against the per-channel objects on site."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "00001",
   "name": "Digital output 0",
   "description": "Set or read output 0 (FC1/FC5/FC15).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "00002",
   "name": "Digital output 1",
   "description": "Set or read output 1 (FC1/FC5/FC15).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "00003",
   "name": "Digital output 2",
   "description": "Set or read output 2 (FC1/FC5/FC15).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "00004",
   "name": "Digital output 3",
   "description": "Set or read output 3 (FC1/FC5/FC15).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "00005",
   "name": "Digital output 4",
   "description": "Set or read output 4 (FC1/FC5/FC15).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "00006",
   "name": "Digital output 5",
   "description": "Set or read output 5 (FC1/FC5/FC15).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "00007",
   "name": "Digital output 6",
   "description": "Set or read output 6 (FC1/FC5/FC15).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "00008",
   "name": "Digital output 7",
   "description": "Set or read output 7 (FC1/FC5/FC15).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 32,
   "documented": "00033",
   "name": "Digital input 0 (coil view)",
   "description": "Input state, readable as a coil with FC1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "00034",
   "name": "Digital input 1 (coil view)",
   "description": "Input state, readable as a coil with FC1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "00035",
   "name": "Digital input 2 (coil view)",
   "description": "Input state, readable as a coil with FC1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "00036",
   "name": "Digital input 3 (coil view)",
   "description": "Input state, readable as a coil with FC1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 36,
   "documented": "00037",
   "name": "Digital input 4 (coil view)",
   "description": "Input state, readable as a coil with FC1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 37,
   "documented": "00038",
   "name": "Digital input 5 (coil view)",
   "description": "Input state, readable as a coil with FC1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 38,
   "documented": "00039",
   "name": "Digital input 6 (coil view)",
   "description": "Input state, readable as a coil with FC1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 39,
   "documented": "00040",
   "name": "Digital input 7 (coil view)",
   "description": "Input state, readable as a coil with FC1.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 512,
   "documented": "00513",
   "name": "Clear DI 0 counter",
   "description": "Write to clear this input's counter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 513,
   "documented": "00514",
   "name": "Clear DI 1 counter",
   "description": "Write to clear this input's counter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 514,
   "documented": "00515",
   "name": "Clear DI 2 counter",
   "description": "Write to clear this input's counter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 515,
   "documented": "00516",
   "name": "Clear DI 3 counter",
   "description": "Write to clear this input's counter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 516,
   "documented": "00517",
   "name": "Clear DI 4 counter",
   "description": "Write to clear this input's counter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 517,
   "documented": "00518",
   "name": "Clear DI 5 counter",
   "description": "Write to clear this input's counter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 518,
   "documented": "00519",
   "name": "Clear DI 6 counter",
   "description": "Write to clear this input's counter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "coil",
   "address": 519,
   "documented": "00520",
   "name": "Clear DI 7 counter",
   "description": "Write to clear this input's counter.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "W",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "10001",
   "name": "Digital input 0",
   "description": "Input state via FC2.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "10002",
   "name": "Digital input 1",
   "description": "Input state via FC2.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "10003",
   "name": "Digital input 2",
   "description": "Input state via FC2.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 3,
   "documented": "10004",
   "name": "Digital input 3",
   "description": "Input state via FC2.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "10005",
   "name": "Digital input 4",
   "description": "Input state via FC2.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "10006",
   "name": "Digital input 5",
   "description": "Input state via FC2.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "10007",
   "name": "Digital input 6",
   "description": "Input state via FC2.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "10008",
   "name": "Digital input 7",
   "description": "Input state via FC2.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1024,
   "documented": "11025",
   "name": "Output 0 overload flag",
   "description": "Set when output 0 is overloaded.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1025,
   "documented": "11026",
   "name": "Output 1 overload flag",
   "description": "Set when output 1 is overloaded.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1026,
   "documented": "11027",
   "name": "Output 2 overload flag",
   "description": "Set when output 2 is overloaded.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1027,
   "documented": "11028",
   "name": "Output 3 overload flag",
   "description": "Set when output 3 is overloaded.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1028,
   "documented": "11029",
   "name": "Output 4 overload flag",
   "description": "Set when output 4 is overloaded.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1029,
   "documented": "11030",
   "name": "Output 5 overload flag",
   "description": "Set when output 5 is overloaded.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1030,
   "documented": "11031",
   "name": "Output 6 overload flag",
   "description": "Set when output 6 is overloaded.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "discrete_input",
   "address": 1031,
   "documented": "11032",
   "name": "Output 7 overload flag",
   "description": "Set when output 7 is overloaded.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "30001",
   "name": "DI 0 counter",
   "description": "Pulse counter for input 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "30002",
   "name": "DI 1 counter",
   "description": "Pulse counter for input 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "30003",
   "name": "DI 2 counter",
   "description": "Pulse counter for input 2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "30004",
   "name": "DI 3 counter",
   "description": "Pulse counter for input 3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "30005",
   "name": "DI 4 counter",
   "description": "Pulse counter for input 4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "30006",
   "name": "DI 5 counter",
   "description": "Pulse counter for input 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "30007",
   "name": "DI 6 counter",
   "description": "Pulse counter for input 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "30008",
   "name": "DI 7 counter",
   "description": "Pulse counter for input 7.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "30033",
   "name": "Digital inputs (packed)",
   "description": "All inputs in one register; packed bits, layout not given in the manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "input_register",
   "address": 1024,
   "documented": "31025",
   "name": "Output overload flags (packed)",
   "description": "Overload flags in one register; packed bits, layout not given in the manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40001",
   "name": "DI 0 counter (holding view)",
   "description": "Same counter read with FC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40002",
   "name": "DI 1 counter (holding view)",
   "description": "Same counter read with FC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40003",
   "name": "DI 2 counter (holding view)",
   "description": "Same counter read with FC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40004",
   "name": "DI 3 counter (holding view)",
   "description": "Same counter read with FC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40005",
   "name": "DI 4 counter (holding view)",
   "description": "Same counter read with FC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40006",
   "name": "DI 5 counter (holding view)",
   "description": "Same counter read with FC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40007",
   "name": "DI 6 counter (holding view)",
   "description": "Same counter read with FC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40008",
   "name": "DI 7 counter (holding view)",
   "description": "Same counter read with FC3.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "40033",
   "name": "Digital outputs (packed)",
   "description": "All outputs in one register; packed bits, layout not given in the manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Switch the module to Modbus TCP on its web page, then read the packed input or output register for a whole-module snapshot, or use the per-channel coils and discrete inputs. All values are single 16-bit registers or bits, so there is no word-order question.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 32,
    "why": "All digital input states in one read"
   },
   {
    "table": "discrete_input",
    "address": 0,
    "why": "First digital input"
   },
   {
    "table": "input_register",
    "address": 0,
    "why": "First input's pulse counter"
   },
   {
    "table": "coil",
    "address": 512,
    "why": "Clear the first counter"
   },
   {
    "table": "holding_register",
    "address": 32,
    "why": "Read or write all outputs at once"
   },
   {
    "table": "coil",
    "address": 0,
    "why": "Switch the first output"
   },
   {
    "table": "input_register",
    "address": 1024,
    "why": "Output overload flags"
   }
  ],
  "enable": "Open the module's web page (http://<ip>/#/protocol) and change Current Protocol from ASCII to Modbus TCP. The factory IP is 192.168.127.254 unless DHCP assigned one.",
  "watchdog": null,
  "quirks": [
   "Inputs appear three ways (coils from 0x0020, discrete inputs from 0x0000, packed input register 0x0020); they carry the same states.",
   "Counters can be read as input registers or holding registers at the same addresses."
  ],
  "setup": [
   "TCP port defaults to 502, idle timeout 0 (never drop), up to 8 simultaneous connections; all set on the protocol web page."
  ],
  "gotchas": [
   "The module answers ASCII, not Modbus, until the protocol is changed on the web page.",
   "An idle timeout other than 0 closes quiet connections; poll faster than the timeout or leave it at 0."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/brainboxes/ed-588",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}