 "manufacturer": "BTicino",
 "manufacturer_slug": "bticino",
 "model": "M7000CBNCU03 automatic transfer switch controller (Modbus)",
 "model_slug": "m7000cbncu03",
 "short_model": "M7000CBNCU03",
 "aliases": [
  "M7000CBNCU03",
  "4 226 82",
  "422682",
  "Legrand 4 226 82"
 ],
 "equipment_type": "Transfer switch controller",
 "applies_to": "BTicino M7000CBNCU03 (Legrand cat. no. 4 226 82) automatic changeover controller, Modbus RTU/ASCII via the M7000CBNRS485 expansion module or the IR-USB / IR-WiFi front interfaces, per document LE09509AA-01/17-01.",
 "summary": "The M7000CBNCU03 is BTicino's automatic transfer (changeover) controller for two supply lines. With the RS485 expansion module, or the front optical USB/WiFi interface, it speaks Modbus RTU or ASCII. This map covers both lines' voltages and frequencies, battery voltage, run-time and switching counters, the alarm word, keypad, input, line, breaker and output-function status words and the global status double word.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 5,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Table addresses are hex and one higher than the wire address. The manual says the request address is the table address minus 1, and its example reads breaker-1 switching alarms (table 3A hex) with the frame 01 04 00 39 00 02."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "M7000CBNCU03 Centralina di commutazione automatica - Protocollo di comunicazione Modbus",
  "doc_number": "LE09509AA-01/17-01",
  "revision_date": "2017-01",
  "url": "https://assets.legrand.com/pim/NP-FT-GT/LE09509AA.pdf",
  "pages": "Parameters (menu M08) p. 4; functions and example p. 6; measures p. 11-12; status bits pp. 13-16; commands pp. 16-17; global status p. 18"
 },
 "notes": [
  "The source is in Italian; names here are our English translations.",
  "Word order: the manual's example answers 00 00 00 07 for 7 alarms, so 2-word values are high word first (ABCD).",
  "Measurements are read with function 04 (input registers) or 03; the manual also lists 06, 07, 16 and 17. Function 06 works only on addresses above 1000 hex.",
  "Defaults of the COM parameters (P08.n.01-05) as printed: node address 05, 19200 baud, 8 bits even parity, 1 stop bit, Modbus RTU.",
  "Left out: line 2 voltage/breaker status, printed at 2176/2177 hex while the line 1 rows are 2074/2075 (probably 2076/2077, but not certain); the input-functions status at 2078 (listed as 2 words of 'unsigned integer'); display-message and LED status words; the generic counters CNT1-4 and limits LIM1-4; and all command registers (2F00-2FF0, 4F00), whose wiring into this map would need the full parameter manual.",
  "Left out: the digital-outputs status word. The status table puts it at 2140 hex, but the bit table below it reads the outputs at 2072 hex, so the address is uncertain."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 1,
   "documented": "02 hex",
   "name": "Line 1 voltage L1-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "04 hex",
   "name": "Line 1 voltage L2-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "06 hex",
   "name": "Line 1 voltage L3-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "08 hex",
   "name": "Line 1 voltage L1-L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "0A hex",
   "name": "Line 1 voltage L2-L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "0C hex",
   "name": "Line 1 voltage L3-L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 13,
   "documented": "0E hex",
   "name": "Line 2 voltage L1-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "10 hex",
   "name": "Line 2 voltage L2-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 17,
   "documented": "12 hex",
   "name": "Line 2 voltage L3-N",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 19,
   "documented": "14 hex",
   "name": "Line 2 voltage L1-L2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "16 hex",
   "name": "Line 2 voltage L2-L3",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 23,
   "documented": "18 hex",
   "name": "Line 2 voltage L3-L1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "1A hex",
   "name": "Line 1 frequency",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 27,
   "documented": "1C hex",
   "name": "Line 2 frequency",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 29,
   "documented": "1E hex",
   "name": "Battery (DC supply) voltage",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 31,
   "documented": "20 hex",
   "name": "Total operating time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 33,
   "documented": "22 hex",
   "name": "Total time line 1 OK",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 35,
   "documented": "24 hex",
   "name": "Total time line 2 OK",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 37,
   "documented": "26 hex",
   "name": "Total time line 1 not OK",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 39,
   "documented": "28 hex",
   "name": "Total time line 2 not OK",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 41,
   "documented": "2A hex",
   "name": "Total time breaker line 1 closed",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 43,
   "documented": "2C hex",
   "name": "Total time breaker line 2 closed",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 45,
   "documented": "2E hex",
   "name": "Total time both breakers open",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 49,
   "documented": "32 hex",
   "name": "Breaker 1 operations in AUT",
   "description": "Count.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 51,
   "documented": "34 hex",
   "name": "Breaker 2 operations in AUT",
   "description": "Count.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 53,
   "documented": "36 hex",
   "name": "Breaker 1 operations in MAN",
   "description": "Count.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 55,
   "documented": "38 hex",
   "name": "Breaker 2 operations in MAN",
   "description": "Count.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 57,
   "documented": "3A hex",
   "name": "Breaker 1 switching alarms",
   "description": "Count. The manual's example reads 7 here.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 59,
   "documented": "3C hex",
   "name": "Breaker 2 switching alarms",
   "description": "Count.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 63,
   "documented": "40 hex",
   "name": "Alarms",
   "description": "32-bit alarm flags; bit set = alarm active.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "A01 Battery voltage too low",
    "1": "A02 Battery voltage too high",
    "2": "A03 Line 1 breaker timeout",
    "3": "A04 Line 2 breaker timeout",
    "4": "A05 Line 1 wrong phase sequence",
    "5": "A06 Line 2 wrong phase sequence",
    "6": "A07 Load not supplied timeout",
    "7": "A08 External charger fault",
    "8": "A09 Emergency",
    "9": "A10 Line 1 breaker protection trip",
    "10": "A11 Line 2 breaker protection trip",
    "11": "A12 Line 1 generator not available",
    "12": "A13 Line 2 generator not available",
    "13": "A14 Hour maintenance 1",
    "14": "A15 Hour maintenance 2",
    "15": "A16 Operation maintenance 1",
    "16": "A17 Operation maintenance 2",
    "17": "A18 Auxiliary voltage alarm",
    "18": "UA1 User alarm",
    "19": "UA2 User alarm",
    "20": "UA3 User alarm",
    "21": "UA4 User alarm"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 79,
   "documented": "50 hex",
   "name": "Battery voltage minimum",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 81,
   "documented": "52 hex",
   "name": "Battery voltage maximum",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 83,
   "documented": "54 hex",
   "name": "Hour maintenance line 1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 85,
   "documented": "56 hex",
   "name": "Hour maintenance line 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 87,
   "documented": "58 hex",
   "name": "Operations left to maintenance, line 1",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 89,
   "documented": "5A hex",
   "name": "Operations left to maintenance, line 2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8303,
   "documented": "2070 hex",
   "name": "Front keypad status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Up arrow",
    "1": "OFF/RESET",
    "2": "MAN",
    "3": "Down arrow",
    "4": "AUT/ENTER"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8307,
   "documented": "2074 hex",
   "name": "Line 1 voltage status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Line within limits",
    "1": "Line within limits + delay",
    "2": "Voltage within limits",
    "3": "Voltage OK",
    "4": "Frequency within limits",
    "5": "Frequency OK",
    "6": "Voltage below minimum",
    "7": "Voltage above maximum",
    "8": "Voltage asymmetry out of threshold",
    "9": "Voltage below phase-loss threshold",
    "10": "Frequency below minimum",
    "11": "Frequency above maximum",
    "12": "Wrong phase sequence",
    "13": "All line parameters OK"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8308,
   "documented": "2075 hex",
   "name": "Line 1 breaker status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Breaker closed",
    "1": "Trip alarm",
    "3": "Commanded state (1 = closed)",
    "4": "Close command output",
    "5": "Open command output"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8313,
   "documented": "207A hex",
   "name": "Output functions status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Open line 1",
    "1": "Open line 2",
    "2": "Close line 1",
    "3": "Close line 2",
    "4": "Global alarm",
    "5": "Start generator 1",
    "6": "Start generator 2",
    "7": "ATS ready",
    "8": "Load shed",
    "11": "Open all",
    "12": "Undervoltage coil 1",
    "13": "Undervoltage coil 2",
    "14": "Line 1 OK",
    "15": "Line 2 OK"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8315,
   "documented": "207C hex",
   "name": "Controller general status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Mode OFF/Reset",
    "1": "Mode MAN",
    "2": "Mode AUT",
    "3": "Mode TEST",
    "4": "In error",
    "5": "AC supply present",
    "6": "DC supply present",
    "7": "Global alarm active"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8447,
   "documented": "2100 hex",
   "name": "Digital inputs status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input 1",
    "1": "Input 2",
    "2": "Input 3",
    "3": "Input 4",
    "4": "Input 5",
    "5": "Input 6",
    "6": "Input 7",
    "7": "Input 8",
    "8": "Input 9",
    "9": "Input 10",
    "10": "Input 11",
    "11": "Input 12",
    "12": "Input 13",
    "13": "Input 14"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8719,
   "documented": "2210 hex",
   "name": "Global device status",
   "description": "32-bit status flags (bit 0-31).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Device in OFF",
    "1": "Device in MAN",
    "2": "Device in AUT",
    "3": "Device in TEST",
    "4": "Line 1 voltage OK",
    "5": "Line 2 voltage OK",
    "6": "Line 1 LED on",
    "7": "Line 2 LED on",
    "10": "Mains contactor closed",
    "11": "Generator contactor closed",
    "12": "Global alarm",
    "13": "AC supply",
    "14": "Start generator 1",
    "15": "Start generator 2",
    "16": "Line 1 max volt",
    "17": "Line 1 min volt",
    "18": "Line 1 max Hz",
    "19": "Line 1 min Hz",
    "20": "Line 1 phase loss",
    "21": "Line 1 asymmetry",
    "22": "Line 2 max volt",
    "23": "Line 2 min volt",
    "24": "Line 2 max Hz",
    "25": "Line 2 min Hz",
    "26": "Line 2 phase loss",
    "27": "Line 2 asymmetry"
   },
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read input registers (function 04) at table address minus 1: 0x0001 for line 1 L1-N voltage, 0x003F for the alarm double word and 0x220F for the global status flags.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 1,
    "why": "Line 1 voltage L1-N"
   },
   {
    "table": "input_register",
    "address": 13,
    "why": "Line 2 voltage L1-N"
   },
   {
    "table": "input_register",
    "address": 25,
    "why": "Line 1 frequency"
   },
   {
    "table": "input_register",
    "address": 63,
    "why": "Alarm flags"
   },
   {
    "table": "input_register",
    "address": 8719,
    "why": "Global status (mode, which line feeds the load)"
   },
   {
    "table": "input_register",
    "address": 8315,
    "why": "Controller mode and error"
   }
  ],
  "enable": "Fit the M7000CBNRS485 module, then in the Settings menu open M08 Communication for COM1 or COM2 and set node address, baud, data format, stop bits and protocol. The front IR-USB/IR-WiFi interfaces need no setup.",
  "watchdog": null,
  "quirks": [
   "Table addresses minus 1 on the wire.",
   "Voltages are whole volts; frequency and battery voltage in tenths."
  ],
  "setup": [
   "Address 1-247 (248-255 internal).",
   "Baud 1200-115200; 7-bit formats only for Modbus ASCII."
  ],
  "gotchas": [
   "Writes with function 06 are accepted only above 1000 hex.",
   "Up to 80 registers per request."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/bticino/m7000cbncu03",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}