 "manufacturer": "Carlo Gavazzi",
 "manufacturer_slug": "carlo-gavazzi",
 "model": "DCM1 DC energy meter for EV chargers (Modbus RTU / TCP)",
 "model_slug": "dcm1",
 "short_model": "DCM1",
 "aliases": [
  "DCM1A60V10L20S1PFA",
  "DCM1A60V10L20S1PFB",
  "DCM1A60V10L20S2DEB",
  "DCM1A60V10L20S3DEB",
  "DCM1A60V10L20S2DEBF",
  "DCM1A60V10L20S3DEBF",
  "DCM1A30V10L20S1PFA",
  "DCM1A30V10L20S1PFB",
  "DCM1A30V10L20S2DEB",
  "DCM1A30V10L20S3DEB",
  "DCM1A30V10L20S2DEBF",
  "DCM1A30V10L20S3DEBF",
  "DCM1A60V10L20S1ULB",
  "DCM1A30V10L20S1ULB"
 ],
 "equipment_type": "Energy meter (DC)",
 "applies_to": "DCM1 300 A / 600 A, 1000 V DC meters (MID, Eichrecht and LNE variants) with RS485 and Ethernet, protocol version 1.11.",
 "summary": "The DCM1 is a two-part DC meter (DCM-D display/meter plus DCM-T transducer) for DC fast chargers, with RS485 Modbus RTU and Modbus TCP. Readings are 32-bit integers sent low word first with fixed weights. This map covers voltage, current, power, energy and Ah counters, run hours, shunt temperatures, serial and Ethernet settings, resets, the device state word and the main OCMF charging-session registers.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Rows give a 6-digit Modicon number (3xxxxx for function 04, 4xxxxx for function 03) and the hex physical address that goes in the frame. 300001 / 0000h is wire address 0. Functions 03 and 04 return the same data."
 },
 "default_word_order": "CDAB",
 "firmware": "OCMF display/string registers need firmware 1.5.3 onward",
 "source": {
  "title": "DCM1 Modbus Communication Protocol - Public version",
  "doc_number": "Version 1.11",
  "revision_date": "2025-07-30",
  "url": "https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/DCM1_CPP.pdf",
  "pages": "Data format p. 12; tables pp. 14-45 (PDF pp. 15-46); charging-session procedure PDF pp. 35-36"
 },
 "notes": [
  "Word order: the protocol says INT32, UINT32 and UINT64 are sent least significant word first with bytes MSB first, so those values are CDAB here.",
  "Left out: the FLOAT block at 0200h (no word order stated for IEEE 754), INT64 energy blocks at 0500h/0600h and the INT64 UTC timestamp at 7032h (word order stated only for unsigned 64-bit), the mirror block at 0100h, the signed OBIS maps at 0700h/0800h, public keys, signatures, display page filters, MAC address, OCMF identification fields, custom display strings, the OCMF file buffer, maintenance mode and the cable-loss datalogger.",
  "When the DCM-T transducer is unplugged, its values read 0x7FFF or 0x7FFFFFFF and the device state flags it.",
  "The part-number table gives code 1832 for both ULB variants, with hex 0x0728 and 0x0729; check the code on the unit.",
  "The charging-session procedure (sync clock at 7031h/7032h, write 'B' to 7040h, read 7A00h-7A08h, write 'E', read and acknowledge the OCMF file at 7100h-7110h) is described in the source."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "300001 / 0000h",
   "name": "Voltage",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "300003 / 0002h",
   "name": "Current",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "300005 / 0004h",
   "name": "Power",
   "description": "Signed DC power.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "300012 / 000Bh",
   "name": "Carlo Gavazzi identification code",
   "description": "Model code, e.g. 1824 = DCM1A60V10L20S1PFA; see the part-number table.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "300017 / 0010h",
   "name": "kWh (+) TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "300019 / 0012h",
   "name": "Ah (+) TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "300021 / 0014h",
   "name": "kWh (+) PAR",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "300023 / 0016h",
   "name": "Ah (+) PAR",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "300033 / 0020h",
   "name": "kWh (-) TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "300035 / 0022h",
   "name": "Ah (-) TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "300037 / 0024h",
   "name": "kWh (-) PAR",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "300039 / 0026h",
   "name": "Ah (-) PAR",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "Ah",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "300045 / 002Ch",
   "name": "Run hour meter",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 46,
   "documented": "300047 / 002Eh",
   "name": "Run hour meter kWh-",
   "description": "Hours counted while energy flows in the negative direction.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "300049 / 0030h",
   "name": "Run hour meter ON time",
   "description": "Hours the meter has been powered.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "300051 / 0032h",
   "name": "Run hour meter PAR",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 52,
   "documented": "300053 / 0034h",
   "name": "Run hour meter kWh- PAR",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "300055 / 0036h",
   "name": "Run hour meter ON time PAR",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "300081 / 0050h",
   "name": "T1 (shunt terminal 1 temperature)",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 82,
   "documented": "300083 / 0052h",
   "name": "T2 (shunt terminal 2 temperature)",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 770,
   "documented": "300771 / 0302h",
   "name": "Firmware version DCM-D (meter)",
   "description": "High byte: bits 0-3 minor, bits 4-7 major; low byte: revision.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 771,
   "documented": "300772 / 0303h",
   "name": "Firmware version DCM-D (cryptography)",
   "description": "High byte: bits 0-3 minor, bits 4-7 major; low byte: revision.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 772,
   "documented": "300773 / 0304h",
   "name": "Firmware version DCM-T (transducer)",
   "description": "High byte: bits 0-3 minor, bits 4-7 major; low byte: revision.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4096,
   "documented": "304097 / 1000h",
   "name": "Password",
   "description": "0 = no password (default), up to 9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4355,
   "documented": "304356 / 1103h",
   "name": "Easy connection",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (default)",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4361,
   "documented": "304362 / 1109h",
   "name": "Quick set up at next power on",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Menu disabled",
    "1": "Menu enabled (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4363,
   "documented": "304364 / 110Bh",
   "name": "Start-up current of run hour counter",
   "description": "Default 480 (0.48 A); A30 models 160-300000, A60 models up to 600000.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "308193 / 2000h",
   "name": "RS485 instrument address",
   "description": "1-247, default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "308194 / 2001h",
   "name": "RS485 baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "9.6 kbps (default)",
    "2": "19.2 kbps",
    "3": "38.4 kbps",
    "4": "57.6 kbps",
    "5": "115.2 kbps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "308195 / 2002h",
   "name": "RS485 parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "No parity (default)",
    "2": "Even parity"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8195,
   "documented": "308196 / 2003h",
   "name": "Stop bit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "1 (default)",
    "2": "2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8196,
   "documented": "308197 / 2004h",
   "name": "RS485 delay on reply",
   "description": "0-1000, default 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8208,
   "documented": "308209 / 2010h",
   "name": "Update serial communication settings",
   "description": "Write 1 to apply new serial settings.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8448,
   "documented": "308449 / 2100h",
   "name": "Stored IP address octet A",
   "description": "Default 192.168.1.10; used when DHCP is off.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8449,
   "documented": "308450 / 2101h",
   "name": "Stored IP address octet B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8450,
   "documented": "308451 / 2102h",
   "name": "Stored IP address octet C",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8451,
   "documented": "308452 / 2103h",
   "name": "Stored IP address octet D",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8452,
   "documented": "308453 / 2104h",
   "name": "Stored subnet mask octet A",
   "description": "Default 255.255.255.0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8453,
   "documented": "308454 / 2105h",
   "name": "Stored subnet mask octet B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8454,
   "documented": "308455 / 2106h",
   "name": "Stored subnet mask octet C",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8455,
   "documented": "308456 / 2107h",
   "name": "Stored subnet mask octet D",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8456,
   "documented": "308457 / 2108h",
   "name": "Stored default gateway octet A",
   "description": "Default 192.168.1.1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8457,
   "documented": "308458 / 2109h",
   "name": "Stored default gateway octet B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8458,
   "documented": "308459 / 210Ah",
   "name": "Stored default gateway octet C",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8459,
   "documented": "308460 / 210Bh",
   "name": "Stored default gateway octet D",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8460,
   "documented": "308461 / 210Ch",
   "name": "Modbus TCP/IP port",
   "description": "1-9999, default 502.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8461,
   "documented": "308462 / 210Dh",
   "name": "DHCP enabled",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "DHCP off (default)",
    "1": "DHCP on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8462,
   "documented": "210Eh",
   "name": "Update TCP/IP communication settings",
   "description": "Write 1 to apply new Ethernet settings (or power-cycle).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8480,
   "documented": "308481 / 2120h",
   "name": "Actual IP address octet A",
   "description": "Reads 0xFFFF while DHCP has not assigned an address.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8481,
   "documented": "308482 / 2121h",
   "name": "Actual IP address octet B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8482,
   "documented": "308483 / 2122h",
   "name": "Actual IP address octet C",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8483,
   "documented": "308484 / 2123h",
   "name": "Actual IP address octet D",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9471,
   "documented": "309472 / 24FFh",
   "name": "Signature type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "256-bit signature",
    "1": "384-bit signature",
    "2": "No signature"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16387,
   "documented": "316388 / 4003h",
   "name": "Reset total counters",
   "description": "Write 1. Non-certified: totals, Ah, run hours. Certified: Ah and run hours only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16388,
   "documented": "316389 / 4004h",
   "name": "Reset partial counters",
   "description": "Write 1 to clear partial energy, Ah and run-hour counters.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20498,
   "documented": "320499 / 5012h",
   "name": "Device state",
   "description": "Bits 11-12: 00 DCM-T OK, 01 warning (over range), 11 failure.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Voltage over range (beyond ±1150.1 V)",
    "1": "Current over range (beyond ±600.1 A)",
    "2": "Terminal 1 temperature below -25.1 °C",
    "3": "Terminal 1 temperature above 120.1 °C",
    "4": "Terminal 2 temperature below -25.1 °C",
    "5": "Terminal 2 temperature above 120.1 °C",
    "11": "DCM-T status, low bit",
    "12": "DCM-T status, high bit",
    "13": "Transducer disconnected",
    "14": "Invalid transducer connected",
    "15": "Internal device fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20499,
   "documented": "320500 / 5013h",
   "name": "Shunt temperature position 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20500,
   "documented": "320501 / 5014h",
   "name": "Shunt temperature position 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20736,
   "documented": "320737 / 5100h",
   "name": "Cable loss value",
   "description": "Cable resistance used to correct energy; max 500.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "mOhm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28721,
   "documented": "328722 / 7031h",
   "name": "Local time delta",
   "description": "Offset from UTC, -1440 to 1440.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28726,
   "documented": "328727 / 7036h",
   "name": "Display charging direction",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Charging vehicle",
    "1": "Vehicle to grid",
    "2": "Bidirectional"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28736,
   "documented": "328737 / 7040h",
   "name": "OCMF command",
   "description": "Write ASCII 'B' to begin, 'E' to end, 'A' to abort a transaction.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28741,
   "documented": "328742 / 7045h",
   "name": "Charging status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No charging",
    "1": "Charging",
    "2": "End of last transaction",
    "3": "End of last transaction with error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28752,
   "documented": "328753 / 7050h",
   "name": "Charging session end page duration",
   "description": "60-300, default 300.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28768,
   "documented": "328769 / 7060h",
   "name": "Time synchronization status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Time not synchronized",
    "1": "Time synchronized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28928,
   "documented": "328929 / 7100h",
   "name": "OCMF state",
   "description": "Write 0 after reading the OCMF file to allow a new session.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ready for new transaction",
    "1": "Running",
    "2": "Session completed, OCMF file ready",
    "3": "Session completed with internal error, OCMF file corrupted"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28929,
   "documented": "328930 / 7101h",
   "name": "OCMF file length",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "words",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 28930,
   "documented": "328931 / 7102h",
   "name": "OCMF last transaction id",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31232,
   "documented": "331233 / 7A00h",
   "name": "Session delta kWh+",
   "description": "Energy delivered in the current/last charging session.",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31236,
   "documented": "331237 / 7A04h",
   "name": "Session delta kWh-",
   "description": "",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31240,
   "documented": "331241 / 7A08h",
   "name": "Session duration",
   "description": "",
   "data_type": "UINT64",
   "length": 4,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll input registers 0000h-0005h (function 04 or 03) for V, A and W and 0010h-0027h for energy; values are INT32 low word first with fixed weights. For signed charging sessions follow the OCMF procedure around 7040h and 7100h.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "DC voltage"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "DC current"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "DC power"
   },
   {
    "table": "input_register",
    "address": 16,
    "why": "Imported energy total"
   },
   {
    "table": "input_register",
    "address": 32,
    "why": "Exported energy total"
   },
   {
    "table": "holding_register",
    "address": 20498,
    "why": "Device state / transducer health"
   },
   {
    "table": "holding_register",
    "address": 28741,
    "why": "Charging session status"
   }
  ],
  "enable": "RS485 and Ethernet are both active. Serial settings at 2000h-2004h take effect after writing 1 to 2010h; Ethernet settings at 2100h-210Dh after writing 1 to 210Eh or a power cycle.",
  "watchdog": null,
  "quirks": [
   "32-bit and 64-bit unsigned values are low word first.",
   "Totals are 0.1 kWh resolution; run hours are in 1/100 h.",
   "Certified versions block the total-energy reset."
  ],
  "setup": [
   "Serial defaults: address 1, 9600 baud, no parity, 1 stop bit.",
   "Ethernet defaults: 192.168.1.10 / 255.255.255.0, gateway 192.168.1.1, port 502, DHCP off.",
   "With DHCP on, read the assigned address at 2120h-2123h."
  ],
  "gotchas": [
   "Max RS485 answer time is 500 ms; use a long enough timeout.",
   "After reading an OCMF file, write 0 to 7100h or no new session can start."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/carlo-gavazzi/dcm1",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}