 "manufacturer": "Carlo Gavazzi",
 "manufacturer_slug": "carlo-gavazzi",
 "model": "EM511 single-phase energy meter (Modbus RTU)",
 "model_slug": "em511",
 "short_model": "EM511",
 "aliases": [
  "EM511-IS",
  "EM511DINAV81XS1X",
  "EM511DINAV81XS1PFA",
  "EM511DINAV81XS1PFB",
  "EM511DINAV81XS1SFA"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "EM511 direct-connected single-phase DIN meters with RS485 and digital input (X, PFA, PFB, SFA versions), protocol rev. 1.8.",
 "summary": "The EM511 is a one-module single-phase energy meter (up to 45 A direct) with an RS485 Modbus RTU port and a digital input. Readings are 32-bit integers sent low word first with fixed weights. This map covers V, A, W, VA, var, PF, frequency, demand, THD, import/export and tariff energy, run hours, I/O and alarm status, alarm and tariff setup, serial settings and resets.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Rows give a 6-digit Modicon number (3xxxxx, function 04) and the hex physical address used in the frame; 300001 / 0000h is wire address 0. Function 03 reads the same values (replace the leading 3 with 4)."
 },
 "default_word_order": "CDAB",
 "firmware": "Rows apply to all firmware unless noted (X 1.0, PFx 1.0)",
 "source": {
  "title": "EM511 Communication Protocol",
  "doc_number": "rev. 1.8",
  "revision_date": "2023-05-23",
  "url": "https://www.gavazziautomation.com/fileadmin/images/PIM/OTHERSTUFF/COMPRO/EM511%20CP%20Rev1.8.pdf",
  "pages": "Data format p. 10; tables PDF pp. 12-22"
 },
 "notes": [
  "Word order: INT32, UINT32 and UINT64 values are sent least significant word first, bytes MSB first (CDAB).",
  "The document is labelled 'internal version' but is published on Carlo Gavazzi's own site.",
  "Rows marked n.a. in the source always read 0 and are left out.",
  "Left out: the mirror block at 0100h-017Eh, the INT64 energy block at 0500h-0532h (no word order stated for INT64), the run-hour/frequency rows that sit inside that block (0534h-053Eh), energy offsets (4100h-4210h), page filter and display settings, serial-number and name ASCII words, and reserved rows.",
  "The part-number table shows hex 0702 for both PFB (1794) and SFA (1795); the decimal codes are used here.",
  "4020h is factory reset: write 0x0A0A then 0xC1A0 within one second.",
  "Start-up current of run hour counter is printed as Modicon 304360 next to hex 110Bh; the hex address (wire 4363) is used."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "300001 / 0000h",
   "name": "V L-N",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "300003 / 0002h",
   "name": "A",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "300005 / 0004h",
   "name": "W",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "300007 / 0006h",
   "name": "VA",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "300009 / 0008h",
   "name": "var",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "300011 / 000Ah",
   "name": "W dmd",
   "description": "Demand active power.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 11,
   "documented": "300012 / 000Bh",
   "name": "Carlo Gavazzi identification code",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1792": "EM511DINAV81XS1X",
    "1793": "EM511DINAV81XS1PFA",
    "1794": "EM511DINAV81XS1PFB",
    "1795": "EM511DINAV81XS1SFA"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "300013 / 000Ch",
   "name": "W dmd peak",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "300015 / 000Eh",
   "name": "PF (IEC convention)",
   "description": "Positive when consuming, negative when generating.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "300016 / 000Fh",
   "name": "Frequency",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "300017 / 0010h",
   "name": "kWh (+) TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "300019 / 0012h",
   "name": "kvarh (+) TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "300021 / 0014h",
   "name": "kWh (+) PARTIAL",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "300023 / 0016h",
   "name": "kvarh (+) PARTIAL",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "300025 / 0018h",
   "name": "kWh (+) tariff 1",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "300027 / 001Ah",
   "name": "kWh (+) tariff 2",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "300033 / 0020h",
   "name": "kWh (-) TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "300035 / 0022h",
   "name": "kvarh (-) TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "300037 / 0024h",
   "name": "kWh (-) PARTIAL",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "300039 / 0026h",
   "name": "kvarh (-) PARTIAL",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "300041 / 0028h",
   "name": "kVAh TOT",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "300043 / 002Ah",
   "name": "kVAh PARTIAL",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "300045 / 002Ch",
   "name": "Hour counter",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 46,
   "documented": "300047 / 002Eh",
   "name": "Hour counter negative energy",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "300049 / 0030h",
   "name": "Lifetime counter",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "300051 / 0032h",
   "name": "THD A",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 52,
   "documented": "300053 / 0034h",
   "name": "THD V L-N",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "300055 / 0036h",
   "name": "Hour counter PARTIAL",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 56,
   "documented": "300057 / 0038h",
   "name": "Hour counter negative PARTIAL",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "300059 / 003Ah",
   "name": "A dmd",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "300061 / 003Ch",
   "name": "A dmd peak",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "300065 / 0040h",
   "name": "VA dmd",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "300067 / 0042h",
   "name": "VA dmd peak",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 112,
   "documented": "300113 / 0070h",
   "name": "PF (L/C convention)",
   "description": "Positive for inductive, negative for capacitive load.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 113,
   "documented": "300114 / 0071h",
   "name": "Inductive/capacitive load",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Inductive (L)",
    "-1": "Capacitive (C)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 768,
   "documented": "300769 / 0300h",
   "name": "Digital input status",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Input open",
    "1": "Input closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 769,
   "documented": "300770 / 0301h",
   "name": "Active tariff",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "None",
    "1": "Tariff 1",
    "2": "Tariff 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 770,
   "documented": "300771 / 0302h",
   "name": "Firmware version and revision",
   "description": "High byte: bits 0-3 minor, bits 4-7 major; low byte: revision.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 774,
   "documented": "300775 / 0306h",
   "name": "Alarm status",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not active (or waiting for delay)",
    "1": "Active"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4096,
   "documented": "304097 / 1000h",
   "name": "Password",
   "description": "0 = no password (default), up to 9999.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4112,
   "documented": "304113 / 1010h",
   "name": "Demand integration time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1 min",
    "1": "5 min",
    "2": "10 min",
    "3": "15 min (default)",
    "4": "20 min",
    "5": "30 min",
    "6": "60 min"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4116,
   "documented": "304117 / 1014h",
   "name": "Alarm enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (default)",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4117,
   "documented": "304118 / 1015h",
   "name": "Alarm linked variable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Active power (default)",
    "2": "Apparent power",
    "3": "Reactive power",
    "4": "Power factor",
    "5": "Current",
    "6": "Voltage"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4118,
   "documented": "304119 / 1016h",
   "name": "Alarm set point 1 (on)",
   "description": "-1000.00 to +1000.00 in units of the linked variable.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4120,
   "documented": "304121 / 1018h",
   "name": "Alarm set point 2 (off)",
   "description": "-1000.00 to +1000.00.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4122,
   "documented": "304123 / 101Ah",
   "name": "Alarm delay",
   "description": "0-3600 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4353,
   "documented": "304354 / 1101h",
   "name": "Tariff management via Modbus",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4355,
   "documented": "304356 / 1103h",
   "name": "Measurement mode",
   "description": "Fixed on MID versions.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "A mode - absolute (default)",
    "1": "B mode - bidirectional"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4361,
   "documented": "304362 / 1109h",
   "name": "Quick set up at next power on",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Menu disabled",
    "1": "Menu enabled (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4363,
   "documented": "304360 / 110Bh",
   "name": "Start-up current of run hour counter",
   "description": "20 (0.02 A, default) to 45000 (45 A).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.001,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4438,
   "documented": "304439 / 1156h",
   "name": "Current direction",
   "description": "X (non-MID) version only.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Direct (default)",
    "1": "Inverse"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4608,
   "documented": "304609 / 1200h",
   "name": "Digital input function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Tariff selection",
    "1": "Remote status input only (default)",
    "2": "Partial meter enable",
    "3": "Reset partial counters"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4609,
   "documented": "304610 / 1201h",
   "name": "Tariff selection via serial",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Tariff 1 (default)",
    "2": "Tariff 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8192,
   "documented": "308193 / 2000h",
   "name": "RS485 instrument address",
   "description": "1-247, default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8193,
   "documented": "308194 / 2001h",
   "name": "RS485 baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "9.6 kbps (default)",
    "2": "19.2 kbps",
    "3": "38.4 kbps",
    "4": "57.6 kbps",
    "5": "115.2 kbps"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8194,
   "documented": "308195 / 2002h",
   "name": "RS485 parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "No parity (default)",
    "2": "Even parity"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8195,
   "documented": "308196 / 2003h",
   "name": "RS485 stop bit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1 stop bit (default)",
    "1": "2 stop bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8196,
   "documented": "308197 / 2004h",
   "name": "RS485 delay on reply",
   "description": "0-1000, default 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16387,
   "documented": "316388 / 4003h",
   "name": "Reset total counters",
   "description": "Write 1: totals, run hours and offsets (not lifetime). Not on MID versions.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16388,
   "documented": "316389 / 4004h",
   "name": "Reset partial counters",
   "description": "Write 1: partial energy and partial run hours.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16389,
   "documented": "316390 / 4005h",
   "name": "Reset demand values",
   "description": "Write 1: demand and demand max.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16390,
   "documented": "316391 / 4006h",
   "name": "Reset tariff counters",
   "description": "Write 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20487,
   "documented": "320488 / 5007h",
   "name": "Production year",
   "description": "Four digits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20498,
   "documented": "320499 / 5012h",
   "name": "Device state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Run",
    "1": "Fault"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read input registers 0000h-0043h in one request (function 04 or 03). Decode INT32 low word first; V/W/VA/var x10, A x1000, energy x10, hours x100; PF and Hz are INT16 x1000 and x10.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Voltage"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "Current"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "Active power"
   },
   {
    "table": "input_register",
    "address": 14,
    "why": "Power factor"
   },
   {
    "table": "input_register",
    "address": 15,
    "why": "Frequency"
   },
   {
    "table": "input_register",
    "address": 16,
    "why": "Imported kWh total"
   },
   {
    "table": "input_register",
    "address": 32,
    "why": "Exported kWh total"
   }
  ],
  "enable": "Modbus RTU on RS485 is always active; serial settings are at 2000h-2004h.",
  "watchdog": null,
  "quirks": [
   "32-bit values are CDAB.",
   "Stop-bit register uses 0 = 1 stop bit, 1 = 2 stop bits (unlike other Gavazzi meters).",
   "Two PF conventions are published: 000Eh (IEC sign) and 0070h (L/C sign)."
  ],
  "setup": [
   "Defaults: address 1, 9600 baud, no parity, 1 stop bit.",
   "Max answer time 500 ms."
  ],
  "gotchas": [
   "Total reset (4003h) is not available on MID versions.",
   "Tariff selection by Modbus needs 1101h on and the digital input not set to tariff mode."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/carlo-gavazzi/em511",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}