 "manufacturer": "Circutor",
 "manufacturer_slug": "circutor",
 "model": "Computer SMART III FAST",
 "model_slug": "computer-smart-iii-fast",
 "short_model": "SMART III FAST",
 "aliases": [
  "Computer SMART III FAST 6",
  "Computer SMART III FAST 12"
 ],
 "equipment_type": "Power meter (static reactive energy regulator)",
 "applies_to": "Circutor Computer SMART III FAST static reactive power regulators (6 and 12 stage), manual M021B01-03-21A.",
 "summary": "The Computer SMART III FAST is a power factor regulator that switches capacitor stages with static (thyristor) outputs and measures the network like an analyzer. Its RS-485 port speaks Modbus RTU; measurements are 32-bit integer register pairs read with function 04 and the setup block at 0x1071-0x1190 is read with 04 and written with 0x10. This map covers currents, reactive and apparent power, frequency, leakage current, energies, stage and output status, and the main setup registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "All Modbus tables print hexadecimal wire addresses. The manual's example reads initial log 0000 with function 04 and gets 0000 084D back for L1 phase voltage, which confirms that table addresses go on the wire unchanged."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Computer SMART III FAST (Static operation) Reactive Energy Regulator - Instruction Manual",
  "doc_number": "M021B01-03-21A",
  "revision_date": null,
  "url": "https://docs.circutor.com/docs/M021B01-03.pdf",
  "pages": "Section 4.9, PDF pp. 55-66 (Tables 13-45)"
 },
 "notes": [
  "Word order: the function 04 example returns 0000 then 084D for one 2-register value, so 32-bit values are high word first (ABCD).",
  "Left out: all voltage registers. The table prints the unit V/100 but the worked example decodes the same register as V x10 (212.5 V), so the scaling is contradictory.",
  "Left out: active power, the signed reactive power rows, power factor and cos phi. The manual pairs PF and cos phi with separate kW/kvar sign registers but gives no type or scale for them and does not say whether the power values carry a sign.",
  "Left out: THD (unit printed as % with no scale), temperature (signedness not stated), harmonics, the 32-bit alarm word at 605-606 (its bit numbering is printed inconsistently), alarm thresholds, the deleting-parameters commands (the value is printed only as FF with no function code) and identification registers.",
  "Left out: registers 98-99 and 9A-9B. The table labels them active energy consumed (kWh and Wh), the same label as 88-89 and 8A-8B, although they sit in the generated-energy block; the manual does not say which they are.",
  "Currents and leakage current are printed in mA; they are given here in A with scale 0.001.",
  "The kW/kvar sign registers are typed INT32 because their documented values are +1 and -1.",
  "The 12Vdc version has its own manual (M100B01-03-21A) whose tables are numbered differently; it was not checked register by register, so it is not covered here.",
  "Setup registers are read with function 04 and written with function 0x10; they are listed as holding registers. Frames longer than 80 bytes are rejected."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 2,
   "documented": "02-03",
   "name": "L1 Current",
   "description": "Instantaneous value; the manual prints the unit as mA.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "06-07",
   "name": "L1 Inductive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "08-09",
   "name": "L1 Capacitive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "0C-0D",
   "name": "L1 Apparent power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "0E-0F",
   "name": "L1 Reactive power consumed",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "10-11",
   "name": "L1 Reactive power generated",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "16-17",
   "name": "L1 kW sign",
   "description": "Sign that goes with the power factor and cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Positive",
    "-1": "Negative"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "18-19",
   "name": "L1 kvar sign",
   "description": "Sign that goes with the power factor and cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Positive",
    "-1": "Negative"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "1C-1D",
   "name": "L2 Current",
   "description": "Instantaneous value; the manual prints the unit as mA.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "20-21",
   "name": "L2 Inductive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "22-23",
   "name": "L2 Capacitive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "26-27",
   "name": "L2 Apparent power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "28-29",
   "name": "L2 Reactive power consumed",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "2A-2B",
   "name": "L2 Reactive power generated",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "30-31",
   "name": "L2 kW sign",
   "description": "Sign that goes with the power factor and cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Positive",
    "-1": "Negative"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "32-33",
   "name": "L2 kvar sign",
   "description": "Sign that goes with the power factor and cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Positive",
    "-1": "Negative"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "36-37",
   "name": "L3 Current",
   "description": "Instantaneous value; the manual prints the unit as mA.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "3A-3B",
   "name": "L3 Inductive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "3C-3D",
   "name": "L3 Capacitive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "40-41",
   "name": "L3 Apparent power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "42-43",
   "name": "L3 Reactive power consumed",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 68,
   "documented": "44-45",
   "name": "L3 Reactive power generated",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 74,
   "documented": "4A-4B",
   "name": "L3 kW sign",
   "description": "Sign that goes with the power factor and cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Positive",
    "-1": "Negative"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "4C-4D",
   "name": "L3 kvar sign",
   "description": "Sign that goes with the power factor and cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Positive",
    "-1": "Negative"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "50-51",
   "name": "Three-phase current",
   "description": "Instantaneous value; the manual prints the unit as mA.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 84,
   "documented": "54-55",
   "name": "Three-phase inductive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 86,
   "documented": "56-57",
   "name": "Three-phase capacitive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 90,
   "documented": "5A-5B",
   "name": "Three-phase apparent power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 92,
   "documented": "5C-5D",
   "name": "Three-phase reactive power consumed",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 94,
   "documented": "5E-5F",
   "name": "Three-phase reactive power generated",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 100,
   "documented": "64-65",
   "name": "Three-phase kW sign",
   "description": "Sign that goes with the power factor and cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Positive",
    "-1": "Negative"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 102,
   "documented": "66-67",
   "name": "Three-phase kvar sign",
   "description": "Sign that goes with the power factor and cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Positive",
    "-1": "Negative"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 104,
   "documented": "68-69",
   "name": "Frequency",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 112,
   "documented": "70-71",
   "name": "Neutral current",
   "description": "Instantaneous value; the manual prints the unit as mA.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 114,
   "documented": "72-73",
   "name": "Leakage current",
   "description": "Instantaneous value; the manual prints the unit as mA.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 136,
   "documented": "88-89",
   "name": "Active energy consumed",
   "description": "Whole-unit counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 138,
   "documented": "8A-8B",
   "name": "Active energy consumed (Wh part)",
   "description": "Remainder below one whole unit.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 140,
   "documented": "8C-8D",
   "name": "Inductive energy consumed",
   "description": "Whole-unit counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 142,
   "documented": "8E-8F",
   "name": "Inductive energy consumed (varh part)",
   "description": "Remainder below one whole unit.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 144,
   "documented": "90-91",
   "name": "Capacitive energy consumed",
   "description": "Whole-unit counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 146,
   "documented": "92-93",
   "name": "Capacitive energy consumed (varh part)",
   "description": "Remainder below one whole unit.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 148,
   "documented": "94-95",
   "name": "Apparent energy consumed",
   "description": "Whole-unit counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 150,
   "documented": "96-97",
   "name": "Apparent energy consumed (VAh part)",
   "description": "Remainder below one whole unit.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 156,
   "documented": "9C-9D",
   "name": "Inductive energy generated",
   "description": "Whole-unit counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 158,
   "documented": "9E-9F",
   "name": "Inductive energy generated (varh part)",
   "description": "Remainder below one whole unit.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 160,
   "documented": "A0-A1",
   "name": "Capacitive energy generated",
   "description": "Whole-unit counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 162,
   "documented": "A2-A3",
   "name": "Capacitive energy generated (varh part)",
   "description": "Remainder below one whole unit.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 164,
   "documented": "A4-A5",
   "name": "Apparent energy generated",
   "description": "Whole-unit counter.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 166,
   "documented": "A6-A7",
   "name": "Apparent energy generated (VAh part)",
   "description": "Remainder below one whole unit.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1536,
   "documented": "600",
   "name": "Relay variable",
   "description": "Capacitor stage relays; bit set = relay on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Stage relay 1",
    "1": "Stage relay 2",
    "2": "Stage relay 3",
    "3": "Stage relay 4",
    "4": "Stage relay 5",
    "5": "Stage relay 6",
    "6": "Stage relay 7",
    "7": "Stage relay 8",
    "8": "Stage relay 9",
    "9": "Stage relay 10",
    "10": "Stage relay 11",
    "11": "Stage relay 12"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1552,
   "documented": "610",
   "name": "Status of the outputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Fan relay ON",
    "1": "Alarm relay ON",
    "2": "Digital output 1 OFF (0 = ON)",
    "3": "Digital output 2 OFF (0 = ON)"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1557,
   "documented": "615",
   "name": "Status of the digital inputs",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Digital input 1 ON",
    "1": "Digital input 2 ON"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4209,
   "documented": "1071",
   "name": "Peripheral number",
   "description": "1-254, default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4210,
   "documented": "1072",
   "name": "RS-485 speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9600",
    "1": "19200 (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4211,
   "documented": "1073",
   "name": "RS-485 parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None (default)",
    "1": "Odd",
    "2": "Even"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4212,
   "documented": "1074",
   "name": "RS-485 data length",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "8 bits (default)",
    "1": "7 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4213,
   "documented": "1075",
   "name": "RS-485 stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1 bit (default)",
    "1": "2 bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4240,
   "documented": "1090",
   "name": "Current primary",
   "description": "1-10000, default 5.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4241,
   "documented": "1091",
   "name": "Current secondary",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1 A",
    "1": "5 A (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4245,
   "documented": "1095-1096",
   "name": "Voltage primary",
   "description": "1-99999, default 400.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4247,
   "documented": "1097-1098",
   "name": "Voltage secondary",
   "description": "1-99999, default 400.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4352,
   "documented": "1100",
   "name": "Connection type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "3U.3C (default)",
    "1": "3U.1C",
    "2": "2U.1C"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4368,
   "documented": "1110",
   "name": "Stage C1 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4369,
   "documented": "1111",
   "name": "Stage C2 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4370,
   "documented": "1112",
   "name": "Stage C3 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4371,
   "documented": "1113",
   "name": "Stage C4 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4372,
   "documented": "1114",
   "name": "Stage C5 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4373,
   "documented": "1115",
   "name": "Stage C6 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4374,
   "documented": "1116",
   "name": "Stage C7 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4375,
   "documented": "1117",
   "name": "Stage C8 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4376,
   "documented": "1118",
   "name": "Stage C9 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4377,
   "documented": "1119",
   "name": "Stage C10 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4378,
   "documented": "111A",
   "name": "Stage C11 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4379,
   "documented": "111B",
   "name": "Stage C12 status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto (default)",
    "1": "On",
    "2": "OFF",
    "3": "OnNc"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4385,
   "documented": "1121",
   "name": "Voltage level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Low voltage (default)",
    "1": "Medium/High voltage"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4400,
   "documented": "1130",
   "name": "Target cos phi 1",
   "description": "50-100 raw (value x100), default 100 = 1.00.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4401,
   "documented": "1131",
   "name": "Target cos phi 2",
   "description": "50-100 raw (value x100), default 100 = 1.00.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4402,
   "documented": "1132",
   "name": "Target cos phi 3",
   "description": "50-100 raw (value x100), default 100 = 1.00.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4403,
   "documented": "1133",
   "name": "Target cos phi 4",
   "description": "50-100 raw (value x100), default 100 = 1.00.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4404,
   "documented": "1134",
   "name": "Target cos phi 1 type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Capacitive",
    "1": "Inductive (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4405,
   "documented": "1135",
   "name": "Target cos phi 2 type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Capacitive",
    "1": "Inductive (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4406,
   "documented": "1136",
   "name": "Target cos phi 3 type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Capacitive",
    "1": "Inductive (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4407,
   "documented": "1137",
   "name": "Target cos phi 4 type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Capacitive",
    "1": "Inductive (default)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4408,
   "documented": "1138",
   "name": "C/K factor",
   "description": "0-100 raw (value x100), default 100 = 1.00.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4409,
   "documented": "1139",
   "name": "Program",
   "description": "Stage ratio program 1111-1999, default 1111.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4410,
   "documented": "113A",
   "name": "Operation type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "FCP (default)",
    "1": "Total",
    "2": "Sim"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4411,
   "documented": "113B",
   "name": "Number of stages",
   "description": "0-6 (FAST 6) or 0-12 (FAST 12).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4412,
   "documented": "113C",
   "name": "Connection time",
   "description": "0-999 network cycles, default 10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4413,
   "documented": "113D",
   "name": "Reconnection time",
   "description": "0-999 network cycles, default 50.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read the measurement block from 0x0000 with function 04, keeping each frame at or under 80 bytes (at most 37 registers per read). Values are 32-bit integers, high word first; currents are in mA.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 80,
    "why": "Three-phase current"
   },
   {
    "table": "input_register",
    "address": 90,
    "why": "Three-phase apparent power"
   },
   {
    "table": "input_register",
    "address": 92,
    "why": "Three-phase reactive power consumed"
   },
   {
    "table": "input_register",
    "address": 104,
    "why": "Frequency (Hz x10)"
   },
   {
    "table": "input_register",
    "address": 136,
    "why": "Active energy consumed (kWh)"
   },
   {
    "table": "input_register",
    "address": 1536,
    "why": "Which capacitor stages are switched in"
   },
   {
    "table": "input_register",
    "address": 114,
    "why": "Leakage current"
   }
  ],
  "enable": "Set the peripheral number, speed, parity and stop bits in the RS-485 communications setup screen or with registers 0x1071-0x1075.",
  "watchdog": null,
  "quirks": [
   "Frames longer than 80 bytes in either direction are rejected, so split large reads.",
   "Energies are a whole-unit register plus a remainder register; combine both.",
   "Digital output bits in the output status word read 1 when the output is OFF."
  ],
  "setup": [
   "Defaults: peripheral 1, 19200 baud, no parity, 8 data bits, 1 stop bit.",
   "Only 9600 and 19200 baud are offered on the RS-485 Modbus port."
  ],
  "gotchas": [
   "Writing the stage status registers (0x1110-0x111B) forces capacitor stages on or off; return them to Auto (0) afterwards."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/circutor/computer-smart-iii-fast",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}