 "manufacturer": "Circutor",
 "model": "Computer SMART III",
 "short_model": "Computer SMART III",
 "aliases": [
  "Computer SMART III 6",
  "Computer SMART III 12",
  "SMART III"
 ],
 "equipment_type": "Power meter (power factor regulator with network analyzer)",
 "applies_to": "Circutor Computer SMART III reactive energy regulators (6 and 12 step models), RS-485 Modbus RTU, manual M015B01-03-25B.",
 "summary": "The Computer SMART III is Circutor's power factor (capacitor bank) regulator with a built-in three-phase network analyzer and an RS-485 Modbus RTU port. Measurements are 32-bit integers in register pairs read with function 04. This map covers currents, reactive power split into consumed/generated and inductive/capacitive parts, apparent power, frequency, THD, energy counters and the quadrant sign registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "All addresses in the memory map are hexadecimal wire addresses; the manual's query example reads two registers from 0000 for L1 voltage."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Computer SMART III Instruction Manual",
  "doc_number": "M015B01-03-25B",
  "revision_date": null,
  "url": "https://docs.circutor.com/docs/M015B01-03.pdf",
  "pages": "Section 4.9, PDF pp. 59-70 (tables 13-15)"
 },
 "notes": [
  "Word order: the manual's function 04 example returns 0000 then 084D (high word first), so 32-bit values are ABCD.",
  "Left out: all voltage registers. The table gives the unit as V/100 but the worked example decodes the same register as V x10 (212.5 V), so the scaling is contradictory.",
  "Left out: active power, signed reactive power, power factor and cos phi. The manual pairs PF/cos phi with separate kW/kvar sign registers but does not state the type or scaling of the PF values or whether the power values are signed.",
  "Left out: THD (unit printed as % with no scaling factor), temperature (signedness not stated), harmonics, relay/alarm/output words and the configuration registers.",
  "The kW/kvar sign registers are typed INT32 because the documented values are +1 and -1.",
  "Communication defaults come from the programming-variables table (Table 17): peripheral number 1, speed code 1 = 19200, parity 0 = none, 8 data bits, 1 stop bit. Frames longer than 80 bytes are rejected."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 2,
   "documented": "02-03",
   "name": "L1 Current",
   "description": "Max at 202-203, min at 302-303.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "06-07",
   "name": "L1 Inductive Reactive Power",
   "description": "Max at 206-207, min at 306-307.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "08-09",
   "name": "L1 Capacitive Reactive Power",
   "description": "Max at 208-209, min at 308-309.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "0C-0D",
   "name": "L1 Apparent Power",
   "description": "Max at 20C-20D, min at 30C-30D.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "0E-0F",
   "name": "L1 Reactive Power Consumed",
   "description": "Max at 20E-20F, min at 30E-30F.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "10-11",
   "name": "L1 Reactive Power Generated",
   "description": "Max at 210-211, min at 310-311.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "16-17",
   "name": "L1 kW sign",
   "description": "+1 or -1; gives the quadrant together with PF/cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "+1",
    "-1": "-1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "18-19",
   "name": "L1 kvar sign",
   "description": "+1 or -1; gives the quadrant together with PF/cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "+1",
    "-1": "-1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "1C-1D",
   "name": "L2 Current",
   "description": "Max at 21C-21D, min at 31C-31D.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "20-21",
   "name": "L2 Inductive Reactive Power",
   "description": "Max at 220-221, min at 320-321.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "22-23",
   "name": "L2 Capacitive Reactive Power",
   "description": "Max at 222-223, min at 322-323.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "26-27",
   "name": "L2 Apparent Power",
   "description": "Max at 226-227, min at 326-327.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "28-29",
   "name": "L2 Reactive Power Consumed",
   "description": "Max at 228-229, min at 328-329.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "2A-2B",
   "name": "L2 Reactive Power Generated",
   "description": "Max at 22A-22B, min at 32A-32B.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "30-31",
   "name": "L2 kW sign",
   "description": "+1 or -1; gives the quadrant together with PF/cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "+1",
    "-1": "-1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "32-33",
   "name": "L2 kvar sign",
   "description": "+1 or -1; gives the quadrant together with PF/cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "+1",
    "-1": "-1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "36-37",
   "name": "L3 Current",
   "description": "Max at 236-237, min at 336-337.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "3A-3B",
   "name": "L3 Inductive Reactive Power",
   "description": "Max at 23A-23B, min at 33A-33B.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "3C-3D",
   "name": "L3 Capacitive Reactive Power",
   "description": "Max at 23C-23D, min at 33C-33D.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "40-41",
   "name": "L3 Apparent Power",
   "description": "Max at 240-241, min at 340-341.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "42-43",
   "name": "L3 Reactive Power Consumed",
   "description": "Max at 242-243, min at 342-343.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 68,
   "documented": "44-45",
   "name": "L3 Reactive Power Generated",
   "description": "Max at 244-245, min at 344-345.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 74,
   "documented": "4A-4B",
   "name": "L3 kW sign",
   "description": "+1 or -1; gives the quadrant together with PF/cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "+1",
    "-1": "-1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "4C-4D",
   "name": "L3 kvar sign",
   "description": "+1 or -1; gives the quadrant together with PF/cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "+1",
    "-1": "-1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 80,
   "documented": "50-51",
   "name": "Three-phase current",
   "description": "Max at 250-251, min at 350-351.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 84,
   "documented": "54-55",
   "name": "Three-phase inductive power",
   "description": "Max at 254-255, min at 354-355.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 86,
   "documented": "56-57",
   "name": "Three-phase capacitive power",
   "description": "Max at 256-257, min at 356-357.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 90,
   "documented": "5A-5B",
   "name": "Three-phase apparent power",
   "description": "Max at 25A-25B, min at 35A-35B.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 100,
   "documented": "64-65",
   "name": "Three-phase kW sign",
   "description": "+1 or -1; gives the quadrant together with PF/cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "+1",
    "-1": "-1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 102,
   "documented": "66-67",
   "name": "Three-phase kvar sign",
   "description": "+1 or -1; gives the quadrant together with PF/cos phi.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "+1",
    "-1": "-1"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 104,
   "documented": "68-69",
   "name": "Frequency",
   "description": "Max at 268-269, min at 368-369.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 112,
   "documented": "70-71",
   "name": "Neutral Current",
   "description": "Max at 270-271, min at 370-371.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 114,
   "documented": "72-73",
   "name": "Leakage Current",
   "description": "Max at 272-273, min at 372-373.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 136,
   "documented": "88-89",
   "name": "Active energy consumed kWh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 138,
   "documented": "8A-8B",
   "name": "Active energy consumed Wh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 140,
   "documented": "8C-8D",
   "name": "Inductive energy consumed kvarLh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 142,
   "documented": "8E-8F",
   "name": "Inductive energy consumed varLh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 144,
   "documented": "90-91",
   "name": "Capacitive energy consumed kvarCh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 146,
   "documented": "92-93",
   "name": "Capacitive energy consumed varCh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 148,
   "documented": "94-95",
   "name": "Apparent energy consumed kVAh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 150,
   "documented": "96-97",
   "name": "Apparent energy consumed VAh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 152,
   "documented": "98-99",
   "name": "Active energy generated kWh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 154,
   "documented": "9A-9B",
   "name": "Active energy generated Wh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 156,
   "documented": "9C-9D",
   "name": "Inductive energy generated kvarLh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 158,
   "documented": "9E-9F",
   "name": "Inductive energy generated varLh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 160,
   "documented": "A0-A1",
   "name": "Capacitive energy generated kvarCh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kvarh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 162,
   "documented": "A2-A3",
   "name": "Capacitive energy generated varCh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 164,
   "documented": "A4-A5",
   "name": "Apparent energy generated kVAh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kVAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 166,
   "documented": "A6-A7",
   "name": "Apparent energy generated VAh",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VAh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read with function 04 in register pairs (high word first). Use the kW and kvar sign registers to tell consumed from generated and inductive from capacitive operation.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 80,
    "why": "Three-phase current (mA)"
   },
   {
    "table": "input_register",
    "address": 90,
    "why": "Three-phase apparent power"
   },
   {
    "table": "input_register",
    "address": 100,
    "why": "Three-phase kW sign"
   },
   {
    "table": "input_register",
    "address": 102,
    "why": "Three-phase kvar sign"
   },
   {
    "table": "input_register",
    "address": 104,
    "why": "Frequency (Hz/10)"
   },
   {
    "table": "input_register",
    "address": 136,
    "why": "Active energy consumed kWh"
   }
  ],
  "enable": "Modbus RTU is available on the RS-485 port; peripheral number and serial settings are set in the setup menu.",
  "watchdog": null,
  "quirks": [
   "Frames of more than 80 bytes are not accepted (sent or received); size reads so the reply stays within 80 bytes.",
   "Energy is split into a whole-unit register (kWh) and a remainder register (Wh)."
  ],
  "setup": [
   "Defaults: peripheral number 1, 19200 baud, no parity, 8 data bits, 1 stop bit; 9600 or 19200 can be chosen in the setup menu."
  ],
  "gotchas": [
   "Do not apply the CVM-series x10 voltage scaling blindly; this manual's voltage scaling is inconsistent, so verify voltages against the display."
  ]
 },
 "manufacturer_slug": "circutor",
 "model_slug": "computer-smart-iii",
 "page": "https://easymodbus.com/modbus-register-maps/circutor/computer-smart-iii",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}