 "manufacturer": "Circutor",
 "model": "CVM-C5",
 "short_model": "CVM-C5",
 "aliases": [
  "CVM-C5-ITF-485",
  "CVM-C5-MC-485",
  "CVM-C5-mV-485"
 ],
 "equipment_type": "Power meter",
 "applies_to": "Circutor CVM-C5 panel power analyzer, RS-485 Modbus RTU versions (ITF-485, MC-485, mV-485), manual M026B01-03.",
 "summary": "The CVM-C5 is a compact panel power analyzer from Circutor with an RS-485 Modbus RTU port. Every measured value is a 32-bit integer in two registers with fixed scaling (V x10, mA, Hz x10, % x10), read with function 03 or 04, each with instantaneous, maximum and minimum copies. This map covers voltages, currents, reactive and apparent power, frequency, THD, demand and the two-tariff energy counters plus the tariff selector.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "All Modbus addresses in the manual are hexadecimal wire addresses. The manual's example reads L1-L2 voltage at initial register 2A and receives 0000 084D = 212.5 V, which matches the table entry 2A-2B with V x10 scaling."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "CVM-C5 Instruction Manual",
  "doc_number": "M026B01-03",
  "revision_date": null,
  "url": "https://docs.circutor.com/docs/M026B01-03.pdf",
  "pages": "Section 4.7, PDF pp. 43-46 (tables 17-18)"
 },
 "notes": [
  "Word order: the manual's example response gives register 1 = 0000 and register 2 = 084D for 212.5 V, so 32-bit values are high word first (ABCD). The manual states all parameters are 32 bits long.",
  "Left out: active power, signed reactive power, power factor and cos phi (per phase and three-phase), because the manual does not state whether those Modbus values are signed.",
  "Left out: the 'Maximum demand' register at 44-45, whose unit is printed as W/VA/mA, so its unit depends on the selected demand variable.",
  "Left out: apparent energy (consumed and generated) because the units column prints kVAh for one and VAh for the other; CO2, cost and hours per tariff.",
  "Energy counters are per tariff only (T1 and T2); there is no total register.",
  "Frequency is scaled x10 on this model (not x100 as on the CVM-C10)."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "00-01",
   "name": "L1 phase-neutral voltage",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "02-03",
   "name": "L1 current",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "0A-0B",
   "name": "L2 phase-neutral voltage",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "0C-0D",
   "name": "L2 current",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 20,
   "documented": "14-15",
   "name": "L3 phase-neutral voltage",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "16-17",
   "name": "L3 current",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "20-21",
   "name": "Three-phase inductive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "22-23",
   "name": "Three-phase capacitive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "28-29",
   "name": "Frequency",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "2A-2B",
   "name": "L1-L2 voltage",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "2C-2D",
   "name": "L2-L3 voltage",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 46,
   "documented": "2E-2F",
   "name": "L3-L1 voltage",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "30-31",
   "name": "THD voltage L1",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "32-33",
   "name": "THD voltage L2",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 52,
   "documented": "34-35",
   "name": "THD voltage L3",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "36-37",
   "name": "THD current L1",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 56,
   "documented": "38-39",
   "name": "THD current L2",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "3A-3B",
   "name": "THD current L3",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "3C-3D",
   "name": "Active energy tariff 1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 62,
   "documented": "3E-3F",
   "name": "Inductive reactive energy tariff 1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 64,
   "documented": "40-41",
   "name": "Capacitive reactive energy tariff 1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 66,
   "documented": "42-43",
   "name": "Three-phase apparent power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 70,
   "documented": "46-47",
   "name": "Three-phase current (average)",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 82,
   "documented": "52-53",
   "name": "Maximum demand I2",
   "description": "Present maximum-demand value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 84,
   "documented": "54-55",
   "name": "Maximum demand I3",
   "description": "Present maximum-demand value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 86,
   "documented": "56-57",
   "name": "Phase-phase voltage (average)",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 88,
   "documented": "58-59",
   "name": "Phase-neutral voltage (average)",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 96,
   "documented": "60-61",
   "name": "Generated active energy tariff 1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 98,
   "documented": "62-63",
   "name": "Generated inductive reactive energy tariff 1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 100,
   "documented": "64-65",
   "name": "Generated capacitive reactive energy tariff 1",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 108,
   "documented": "6C-6D",
   "name": "Active energy tariff 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 110,
   "documented": "6E-6F",
   "name": "Inductive reactive energy tariff 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 112,
   "documented": "70-71",
   "name": "Capacitive reactive energy tariff 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 116,
   "documented": "74-75",
   "name": "Generated active energy tariff 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "Wh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 118,
   "documented": "76-77",
   "name": "Generated inductive reactive energy tariff 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 120,
   "documented": "78-79",
   "name": "Generated capacitive reactive energy tariff 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "varh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 132,
   "documented": "84-85",
   "name": "L1 phase-neutral voltage (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 134,
   "documented": "86-87",
   "name": "L1 current (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 142,
   "documented": "8E-8F",
   "name": "L2 phase-neutral voltage (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 144,
   "documented": "90-91",
   "name": "L2 current (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 152,
   "documented": "98-99",
   "name": "L3 phase-neutral voltage (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 154,
   "documented": "9A-9B",
   "name": "L3 current (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 164,
   "documented": "A4-A5",
   "name": "Three-phase inductive power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 166,
   "documented": "A6-A7",
   "name": "Three-phase capacitive power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 172,
   "documented": "AC-AD",
   "name": "Frequency (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 174,
   "documented": "AE-AF",
   "name": "L1-L2 voltage (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 176,
   "documented": "B0-B1",
   "name": "L2-L3 voltage (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 178,
   "documented": "B2-B3",
   "name": "L3-L1 voltage (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 180,
   "documented": "B4-B5",
   "name": "THD voltage L1 (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 182,
   "documented": "B6-B7",
   "name": "THD voltage L2 (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 184,
   "documented": "B8-B9",
   "name": "THD voltage L3 (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 186,
   "documented": "BA-BB",
   "name": "THD current L1 (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 188,
   "documented": "BC-BD",
   "name": "THD current L2 (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 190,
   "documented": "BE-BF",
   "name": "THD current L3 (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 198,
   "documented": "C6-C7",
   "name": "Three-phase apparent power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 202,
   "documented": "CA-CB",
   "name": "Three-phase current (average) (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 218,
   "documented": "DA-DB",
   "name": "Phase-phase voltage (average) (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 220,
   "documented": "DC-DD",
   "name": "Phase-neutral voltage (average) (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 256,
   "documented": "100-101",
   "name": "L1 phase-neutral voltage (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 258,
   "documented": "102-103",
   "name": "L1 current (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 266,
   "documented": "10A-10B",
   "name": "L2 phase-neutral voltage (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 268,
   "documented": "10C-10D",
   "name": "L2 current (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 276,
   "documented": "114-115",
   "name": "L3 phase-neutral voltage (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 278,
   "documented": "116-117",
   "name": "L3 current (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 288,
   "documented": "120-121",
   "name": "Three-phase inductive power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 290,
   "documented": "122-123",
   "name": "Three-phase capacitive power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 296,
   "documented": "128-129",
   "name": "Frequency (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 298,
   "documented": "12A-12B",
   "name": "L1-L2 voltage (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 300,
   "documented": "12C-12D",
   "name": "L2-L3 voltage (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 302,
   "documented": "12E-12F",
   "name": "L3-L1 voltage (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 304,
   "documented": "130-131",
   "name": "THD voltage L1 (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 306,
   "documented": "132-133",
   "name": "THD voltage L2 (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 308,
   "documented": "134-135",
   "name": "THD voltage L3 (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 310,
   "documented": "136-137",
   "name": "THD current L1 (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 312,
   "documented": "138-139",
   "name": "THD current L2 (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 314,
   "documented": "13A-13B",
   "name": "THD current L3 (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 322,
   "documented": "142-143",
   "name": "Three-phase apparent power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 326,
   "documented": "146-147",
   "name": "Three-phase current (average) (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 342,
   "documented": "156-157",
   "name": "Phase-phase voltage (average) (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 344,
   "documented": "158-159",
   "name": "Phase-neutral voltage (average) (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 380,
   "documented": "17C-17D",
   "name": "L1 inductive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 382,
   "documented": "17E-17F",
   "name": "L2 inductive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 384,
   "documented": "180-181",
   "name": "L3 inductive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 386,
   "documented": "182-183",
   "name": "L1 capacitive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 388,
   "documented": "184-185",
   "name": "L2 capacitive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 390,
   "documented": "186-187",
   "name": "L3 capacitive reactive power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 392,
   "documented": "188-189",
   "name": "L1 apparent power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 394,
   "documented": "18A-18B",
   "name": "L2 apparent power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 396,
   "documented": "18C-18D",
   "name": "L3 apparent power",
   "description": "Instantaneous value.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 398,
   "documented": "18E-18F",
   "name": "L1 inductive reactive power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 400,
   "documented": "190-191",
   "name": "L2 inductive reactive power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 402,
   "documented": "192-193",
   "name": "L3 inductive reactive power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 404,
   "documented": "194-195",
   "name": "L1 capacitive reactive power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 406,
   "documented": "196-197",
   "name": "L2 capacitive reactive power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 408,
   "documented": "198-199",
   "name": "L3 capacitive reactive power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 410,
   "documented": "19A-19B",
   "name": "L1 apparent power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 412,
   "documented": "19C-19D",
   "name": "L2 apparent power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 414,
   "documented": "19E-19F",
   "name": "L3 apparent power (max)",
   "description": "Maximum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 416,
   "documented": "1A0-1A1",
   "name": "L1 inductive reactive power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 418,
   "documented": "1A2-1A3",
   "name": "L2 inductive reactive power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 420,
   "documented": "1A4-1A5",
   "name": "L3 inductive reactive power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 422,
   "documented": "1A6-1A7",
   "name": "L1 capacitive reactive power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 424,
   "documented": "1A8-1A9",
   "name": "L2 capacitive reactive power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 426,
   "documented": "1AA-1AB",
   "name": "L3 capacitive reactive power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "var",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 428,
   "documented": "1AC-1AD",
   "name": "L1 apparent power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 430,
   "documented": "1AE-1AF",
   "name": "L2 apparent power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 432,
   "documented": "1B0-1B1",
   "name": "L3 apparent power (min)",
   "description": "Minimum recorded since last reset.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5000,
   "documented": "1388",
   "name": "Active tariff",
   "description": "Write with function 10, read with function 04.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Tariff T1",
    "1": "Tariff T2"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read with function 04 from 0x00 in two-register steps (maximum 20 variables / 40 registers per frame). Values are 32-bit integers, high word first.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "L1 phase-neutral voltage (V x10)"
   },
   {
    "table": "input_register",
    "address": 2,
    "why": "L1 current (mA)"
   },
   {
    "table": "input_register",
    "address": 66,
    "why": "Three-phase apparent power"
   },
   {
    "table": "input_register",
    "address": 40,
    "why": "Frequency (Hz x10)"
   },
   {
    "table": "input_register",
    "address": 60,
    "why": "Active energy tariff 1"
   },
   {
    "table": "input_register",
    "address": 108,
    "why": "Active energy tariff 2"
   }
  ],
  "enable": "Modbus RTU is the only protocol. Set peripheral number, speed, parity and stop bits in the setup menu (sections 4.6.18-4.6.23).",
  "watchdog": null,
  "quirks": [
   "The active tariff is selected by writing 0 or 1 to register 0x1388 with function 10.",
   "Each measurement has maximum and minimum copies at separate addresses."
  ],
  "setup": [
   "Default: peripheral number 1, 9600 baud, no parity, 8 data bits, 1 stop bit.",
   "Speeds 1200-19200 baud; data bits fixed at 8."
  ],
  "gotchas": [
   "Limit each read to 20 variables (40 registers)."
  ]
 },
 "manufacturer_slug": "circutor",
 "model_slug": "cvm-c5",
 "page": "https://easymodbus.com/modbus-register-maps/circutor/cvm-c5",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}