 "manufacturer": "CO2Meter",
 "manufacturer_slug": "co2meter",
 "model": "CM500 CO2 sensor / controller (RS-485 Modbus RTU)",
 "model_slug": "cm500",
 "short_model": "CM500",
 "aliases": [
  "CM500",
  "CO2Meter CM500"
 ],
 "equipment_type": "Sensor (CO2 / gas)",
 "applies_to": "CO2Meter.com CM500 with the RS-485 Modbus RTU interface, per the vendor's 'RS485 Communications Modbus Protocol' sheet (no document number).",
 "summary": "The CM500 is a CO2 sensor and controller with an RS-485 port that speaks Modbus RTU using FC03 reads and FC06 writes. Readings are single 16-bit registers. The shared register sheet also lists other gas, particulate and RTC registers that only answer on units fitted with those sensors.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 104,
  "baud": 19200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex addresses sent unchanged in the request; the examples read CO2 with start address 0x0014 (table row 14H)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "CM500 RS-485 Modbus RTU protocol (RS485 Communications Modbus Protocol)",
  "doc_number": null,
  "revision_date": null,
  "url": "https://cdn.shopify.com/s/files/1/0019/5952/files/CO2Meter-CM500-RS-485-Modbus-RTU-protocol.pdf",
  "pages": "pp. 1-4",
  "unofficial": true
 },
 "notes": [
  "The sheet is served from a Shopify file CDN (cdn.shopify.com) used by CO2Meter's store, not from a CO2Meter-branded host, so it is marked unofficial.",
  "Note 1 on page 2 says the CO2 start address is 0x0B, but the register table and both example frames use 0x14; 0x14 is used here.",
  "Default slave address is printed as 0x068 (104). The examples use 0xFA, which the sheet reserves for broadcast.",
  "Left out: O2, ambient temperature, barometer, RH, dew point and battery voltage (12H, 19H-1DH). The sheet only shows display formats such as 'xx.xx%', not the register scaling.",
  "Writable RTC registers (78H-7BH) are left out because their layout is not described."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "00H",
   "name": "Slave address",
   "description": "1-249; 250 (0xFA) is reserved for broadcast. Stored in EEPROM.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "01H",
   "name": "Baud rate",
   "description": "Takes effect after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "38400",
    "1": "19200 (default)",
    "2": "9600",
    "3": "4800"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "02H",
   "name": "UART parity / framing",
   "description": "Takes effect after a power cycle.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "N82",
    "1": "N81 (default)",
    "2": "E81",
    "3": "O81"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "13H",
   "name": "NH3",
   "description": "Whole ppm (only on units with this sensor).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "14H",
   "name": "CO2",
   "description": "Whole ppm; the manual's example reads 0x0318 = 792 ppm.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "15H",
   "name": "CO",
   "description": "Whole ppm (only on units with this sensor).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "16H",
   "name": "VOC",
   "description": "Whole ppb (only on units with this sensor).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ppb",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "17H",
   "name": "PM2.5",
   "description": "Only on units with this sensor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µg/m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 24,
   "documented": "18H",
   "name": "PM10",
   "description": "Only on units with this sensor.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µg/m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 30,
   "documented": "1EH",
   "name": "RTC year",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 31,
   "documented": "1FH",
   "name": "RTC month-day",
   "description": "Packing not described.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 32,
   "documented": "20H",
   "name": "RTC hour-minute",
   "description": "Packing not described.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 33,
   "documented": "21H",
   "name": "RTC seconds",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll 19200 8N1 at address 104 (0x68) with FC03 and read register 0x14 for CO2 in ppm. Change address, baud or parity with FC06 and power-cycle the sensor.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 20,
    "why": "CO2 ppm"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Slave address"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Baud rate code"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Parity code"
   }
  ],
  "enable": "Modbus RTU is the RS-485 interface's protocol; no enable step is described.",
  "watchdog": null,
  "quirks": [
   "Only FC03 and FC06 are supported.",
   "Baud and parity changes need a power cycle."
  ],
  "setup": [
   "Defaults: 19200 baud, 8 data bits, no parity, 1 stop bit."
  ],
  "gotchas": [
   "Address 250 (0xFA) is broadcast; do not assign it to a sensor."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/co2meter/cm500",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}