 "manufacturer": "Condair",
 "manufacturer_slug": "condair",
 "model": "ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)",
 "model_slug": "me-ii",
 "short_model": "ME II",
 "aliases": [
  "Condair ME",
  "Condair ME II",
  "ME"
 ],
 "equipment_type": "Air handler humidifier (evaporative)",
 "applies_to": "Condair ME with the Integrated Controller, per addendum 2603326-G.",
 "summary": "The Condair ME is an evaporative humidifier and adiabatic cooler for air handling units. Its Integrated Controller is a Modbus RTU slave on RS-485 or a Modbus TCP server. This map covers mode and status, pump faults and speeds, tank and valve states, humidity, air and water temperatures, stage capacities, service counters and the writable humidity and temperature control registers.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 10,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller)",
  "doc_number": "2603326-G EN 2607",
  "revision_date": null,
  "url": "https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf",
  "pages": "ME tables pp. 21-24; settings pp. 10-17"
 },
 "notes": [
  "Input registers are read with function 04; holding registers with 03 and written with 06 or 16.",
  "Floats use 'Register Sequence': MSR first (high register first, ABCD) is the factory setting; LSR first (CDAB) is the option. The map assumes the factory setting.",
  "Factory serial settings: Modbus RTU, address 10, 19200 baud, even parity, 8 data bits, 1 stop bit. Modbus TCP uses port 502 and unit ID 255 (per the TCP technical data).",
  "Units marked metric/imperial follow the controller's Metric/Imperial setting; the listed unit is the metric one."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 2000,
   "documented": "32001",
   "name": "System Mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Humidifying",
    "1": "Cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2001,
   "documented": "32002",
   "name": "Device Status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Initializing",
    "1": "Diagnostic",
    "2": "Stopped",
    "3": "Humidifying",
    "4": "Cooling",
    "5": "Holding",
    "6": "Draining",
    "7": "Refreshing",
    "8": "Filling",
    "9": "Standby",
    "10": "Diluting",
    "11": "Assisted Draining",
    "12": "Bleeding",
    "13": "Softstart",
    "14": "Switched Off",
    "15": "Remote Off",
    "16": "Purging",
    "17": "Drain Check"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2002,
   "documented": "32003",
   "name": "Maintenance and Error Status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No Info",
    "1": "Warning",
    "2": "Maintenance",
    "3": "WET Tank empty",
    "4": "Replace PureFlo Cartridge",
    "5": "Replace UV Lamp",
    "6": "Matrix Wash Over",
    "7": "Out of Comissioning",
    "8": "Activation Code",
    "9": "Error",
    "10": "Disinfection Tank empty"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2003,
   "documented": "32004",
   "name": "Error or Warning Code",
   "description": "0 = no error; other codes are listed in the device operation manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2004,
   "documented": "32005",
   "name": "Safety Loop",
   "description": "Range 0 = Open 1 = Closed (=ok).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2005,
   "documented": "32006",
   "name": "Number of Running Stages",
   "description": "Range 0 – 7 stages.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2006,
   "documented": "32007",
   "name": "Fault Pump 1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2007,
   "documented": "32008",
   "name": "Fault Pump 2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2008,
   "documented": "32009",
   "name": "Fault Pump 3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2009,
   "documented": "32010",
   "name": "Fault Pump 4",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2010,
   "documented": "32011",
   "name": "Fault Pump 5",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2011,
   "documented": "32012",
   "name": "Fault Pump 6",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2012,
   "documented": "32013",
   "name": "Fault Pump 7",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2013,
   "documented": "32014",
   "name": "Fault Water Inlet",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2014,
   "documented": "32015",
   "name": "Fault Water Temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2015,
   "documented": "32016",
   "name": "Fault Water Outlet",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2016,
   "documented": "32017",
   "name": "Fault Level Sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2017,
   "documented": "32018",
   "name": "Fault Water Conductivity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Fault",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2018,
   "documented": "32019",
   "name": "Speed Pump 1",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2019,
   "documented": "32020",
   "name": "Speed Pump 2",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2020,
   "documented": "32021",
   "name": "Speed Pump 3",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2021,
   "documented": "32022",
   "name": "Speed Pump 4",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2022,
   "documented": "32023",
   "name": "Speed Pump 5",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2023,
   "documented": "32024",
   "name": "Speed Pump 6",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2024,
   "documented": "32025",
   "name": "Speed Pump 7",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2025,
   "documented": "32026",
   "name": "Water Level Tank",
   "description": "Range 0 - 7.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2026,
   "documented": "32027",
   "name": "WET Tank Level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Empty",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2027,
   "documented": "32028",
   "name": "Disinfection Tank Level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Empty",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2028,
   "documented": "32029",
   "name": "Leakage Sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Leak",
    "1": "Ok"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2029,
   "documented": "32030",
   "name": "Inlet Valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2030,
   "documented": "32031",
   "name": "Drain Valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2031,
   "documented": "32032",
   "name": "Drain Pump",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2037,
   "documented": "32038",
   "name": "Actual Humidity or Demand",
   "description": "Range 0 - 100 %.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2039,
   "documented": "32040",
   "name": "Actual Air Temperature",
   "description": "Range °C or °F. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2041,
   "documented": "32042",
   "name": "Incoming Air Temperature",
   "description": "Range °C or °F. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2043,
   "documented": "32044",
   "name": "Actual Water Temperature",
   "description": "Range °C or °F. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2045,
   "documented": "32046",
   "name": "Water Conductivity",
   "description": "Range 0 - x uS/cm.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "uS/cm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2047,
   "documented": "32048",
   "name": "UV Current",
   "description": "Range 0 - 4.0 A.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2049,
   "documented": "32050",
   "name": "Water Capacity Stage 1",
   "description": "Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2051,
   "documented": "32052",
   "name": "Water Capacity Stage 2",
   "description": "Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2053,
   "documented": "32054",
   "name": "Water Capacity Stage 3",
   "description": "Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2055,
   "documented": "32056",
   "name": "Water Capacity Stage 4",
   "description": "Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2057,
   "documented": "32058",
   "name": "Water Capacity Stage 5",
   "description": "Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2059,
   "documented": "32060",
   "name": "Water Capacity Stage 6",
   "description": "Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2061,
   "documented": "32062",
   "name": "Water Capacity Stage 7",
   "description": "Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2063,
   "documented": "32064",
   "name": "Operating Hours",
   "description": "Range 0 - 1200000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2065,
   "documented": "32066",
   "name": "Next Maintenance",
   "description": "Range 0 - 10000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2067,
   "documented": "32068",
   "name": "Next UV Lamp Exchange",
   "description": "Range 0 - 450 d.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "d",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2069,
   "documented": "32070",
   "name": "Next PureFlo Exchange",
   "description": "Range 0 - 365 d.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "d",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3000,
   "documented": "43001",
   "name": "Setpoint Humidity Control",
   "description": "Range 0 - 95 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3001,
   "documented": "43002",
   "name": "P-Band Humidity Control",
   "description": "Range 6 - 65 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3002,
   "documented": "43003",
   "name": "I-Time Humidity Control",
   "description": "Range 1 - 60 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3003,
   "documented": "43004",
   "name": "Actual Humidity or Demand via Modbus",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3004,
   "documented": "43005",
   "name": "I-Time Temperature Control",
   "description": "Range 1 - 60 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3010,
   "documented": "43011",
   "name": "Setpoint Temperature Control",
   "description": "Range 0 - 40 °C 32 - 104 °F. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3012,
   "documented": "43013",
   "name": "P-Band Temperature Control",
   "description": "Range 1 - 50 °C 1.8 - 89.9 °F. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3014,
   "documented": "43015",
   "name": "Actual Temperature via Modbus",
   "description": "Range -25 - 100 °C -12.9 - 211.9 °F. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5001,
   "documented": "45002",
   "name": "Remote Draining",
   "description": "Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5002,
   "documented": "45003",
   "name": "Remote Matrix Wash Over",
   "description": "Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5003,
   "documented": "45004",
   "name": "Remote Error/Warning Reset",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "watchdog": "When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.",
  "quirks": [
   "The address column is the wire address; 32001 is address 2000.",
   "Floats are two registers, MSR first by default."
  ],
  "summary": "Read input registers 2000-2031 (UInt16) and 2037-2070 (floats). Write the demand or humidity value to holding 3003 and, in cooling mode, the temperature to 3014 (float).",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 2000,
    "why": "System mode"
   },
   {
    "table": "input_register",
    "address": 2001,
    "why": "Device status"
   },
   {
    "table": "input_register",
    "address": 2002,
    "why": "Maintenance and error status"
   },
   {
    "table": "input_register",
    "address": 2005,
    "why": "Running stages"
   },
   {
    "table": "input_register",
    "address": 2037,
    "why": "Actual humidity or demand"
   },
   {
    "table": "holding_register",
    "address": 3003,
    "why": "Demand/humidity via Modbus"
   }
  ],
  "enable": "Controls > Signal Settings: set Source = Modbus and choose the control mode.",
  "setup": [
   "Menu > password 8808 > Network > Modbus Settings: set protocol (Modbus/RTU or Modbus/TCP), address, parity, baud rate and register sequence; the controller restarts after a protocol change.",
   "For Modbus TCP set the IP parameters under Network > IP Settings (factory setting DHCP)."
  ],
  "gotchas": [
   "Temperature setpoint registers (3010-3015) are floats; the humidity ones are UInt16."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/condair/me-ii",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}