 "manufacturer": "Condair",
 "manufacturer_slug": "condair",
 "model": "RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)",
 "model_slug": "ro-e",
 "short_model": "RO-E",
 "aliases": [
  "Condair RO-E",
  "RO-E+",
  "Condair RO-E+"
 ],
 "equipment_type": "Pump (reverse osmosis water treatment unit)",
 "applies_to": "Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.",
 "summary": "The Condair RO-E is a reverse osmosis unit that makes demineralised water for humidifiers. Its Integrated Controller is a Modbus RTU slave or Modbus TCP server. This map covers fault and RO status, valve states, unit type and capacity, pressures, permeate conductivity, temperature and flow, and service counters.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 10,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller)",
  "doc_number": "2603326-G EN 2607",
  "revision_date": null,
  "url": "https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf",
  "pages": "RO-E tables pp. 29-30; settings pp. 10-17"
 },
 "notes": [
  "Input registers are read with function 04; holding registers with 03 and written with 06 or 16.",
  "Floats use 'Register Sequence': MSR first (high register first, ABCD) is the factory setting; LSR first (CDAB) is the option. The map assumes the factory setting.",
  "Factory serial settings: Modbus RTU, address 10, 19200 baud, even parity, 8 data bits, 1 stop bit. Modbus TCP uses port 502 and unit ID 255 (per the TCP technical data).",
  "Units marked metric/imperial follow the controller's Metric/Imperial setting; the listed unit is the metric one.",
  "Left out: holding registers 'Minimum / Maximum tank pressure', printed as 43501 / 43503 but with addresses 13500 / 13502, which do not match each other."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 2003,
   "documented": "32004",
   "name": "Error or Warning Code",
   "description": "0 = no error; other codes are listed in the device operation manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2500,
   "documented": "32501",
   "name": "Fault Status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No Error",
    "1": "Warning",
    "2": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2501,
   "documented": "32502",
   "name": "Y11 Inlet valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2502,
   "documented": "32503",
   "name": "Y12 Drain valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2503,
   "documented": "32504",
   "name": "Y13 Outlet valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2504,
   "documented": "32505",
   "name": "Y15 Permeate valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Drain",
    "1": "Tank"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2505,
   "documented": "32506",
   "name": "Y16 Concentrate valve",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2506,
   "documented": "32507",
   "name": "UO Type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "RO-E",
    "1": "RO-E+"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2507,
   "documented": "32508",
   "name": "RO Status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Initializing",
    "1": "Diagnostic",
    "2": "Stopped",
    "3": "Hold",
    "4": "Filling",
    "5": "Standby",
    "6": "Flushing",
    "7": "Draining"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2508,
   "documented": "32509",
   "name": "UO Capacity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "20 l/h / 5.3 gal/hr",
    "1": "40 l/h / 10.6 gal/hr",
    "2": "100 l/h / 26.4 gal/hr",
    "3": "200 l/h / 52.8 gal/hr",
    "4": "300 l/h / 79.3 gal/hr"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2510,
   "documented": "32511",
   "name": "UO Maintenance status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No Info",
    "1": "Warning",
    "2": "Warning Sys",
    "3": "Warning Commissioning",
    "4": "Warning Activation",
    "5": "Error",
    "6": "Warning Disinfection"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2513,
   "documented": "32514",
   "name": "Inlet pressure",
   "description": "Range 0 - 6 bar 0 - 87.0 psi. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2515,
   "documented": "32516",
   "name": "Tank pressure",
   "description": "Range 0 - 6 bar 0 - 87.0 psi. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2517,
   "documented": "32518",
   "name": "Membrane pressure",
   "description": "Range 0 - 20 bar 0 - 290.0 psi. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2519,
   "documented": "32520",
   "name": "Permeate conductivity",
   "description": "Range 0 - 100 µS/cm.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "uS/cm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2521,
   "documented": "32522",
   "name": "Permeate temperature",
   "description": "Range 0 - 60 °C 32 - 140 °F. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2523,
   "documented": "32524",
   "name": "Permeat flow",
   "description": "Range 0 - 400 l/h 0 - 106 gal/hr.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "l/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2525,
   "documented": "32526",
   "name": "Next maintenance",
   "description": "Range 0 - 4000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2527,
   "documented": "32528",
   "name": "Next Disinfection",
   "description": "Range 0 - 365 [Days].",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "d",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2528,
   "documented": "32529",
   "name": "Operating hours",
   "description": "Range 0 - 1200000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "watchdog": null,
  "quirks": [
   "The address column is the wire address; 32001 is address 2000.",
   "Floats are two registers, MSR first by default."
  ],
  "summary": "Read input registers 2500-2510 (UInt16 states) and 2513-2529 (floats and the disinfection counter).",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 2500,
    "why": "Fault status"
   },
   {
    "table": "input_register",
    "address": 2507,
    "why": "RO status"
   },
   {
    "table": "input_register",
    "address": 2513,
    "why": "Inlet pressure"
   },
   {
    "table": "input_register",
    "address": 2517,
    "why": "Membrane pressure"
   },
   {
    "table": "input_register",
    "address": 2519,
    "why": "Permeate conductivity"
   }
  ],
  "enable": "Network > Modbus Settings on the controller.",
  "setup": [
   "Menu > password 8808 > Network > Modbus Settings: set protocol (Modbus/RTU or Modbus/TCP), address, parity, baud rate and register sequence; the controller restarts after a protocol change.",
   "For Modbus TCP set the IP parameters under Network > IP Settings (factory setting DHCP)."
  ],
  "gotchas": [
   "2527 (next disinfection) is UInt16 between two floats; read it on its own or mind the block layout."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/condair/ro-e",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}