 "manufacturer": "Condair",
 "manufacturer_slug": "condair",
 "model": "RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)",
 "model_slug": "rs-ii",
 "short_model": "RS II",
 "aliases": [
  "Condair RS",
  "Condair RS II",
  "RS"
 ],
 "equipment_type": "Air handler humidifier (resistive steam)",
 "applies_to": "Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.",
 "summary": "The Condair RS is a resistive-heating steam humidifier with one or two cylinders. Its Integrated Controller is a Modbus RTU slave on RS-485 or a Modbus TCP server. This map covers per-cylinder status, safety chain, heating, valves and levels, capacities, demand, operating hours and service counters, plus two-channel setpoint and control registers.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 10,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller)",
  "doc_number": "2603326-G EN 2607",
  "revision_date": null,
  "url": "https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf",
  "pages": "RS tables pp. 25-28; settings pp. 10-17"
 },
 "notes": [
  "Input registers are read with function 04; holding registers with 03 and written with 06 or 16.",
  "Floats use 'Register Sequence': MSR first (high register first, ABCD) is the factory setting; LSR first (CDAB) is the option. The map assumes the factory setting.",
  "Factory serial settings: Modbus RTU, address 10, 19200 baud, even parity, 8 data bits, 1 stop bit. Modbus TCP uses port 502 and unit ID 255 (per the TCP technical data).",
  "Units marked metric/imperial follow the controller's Metric/Imperial setting; the listed unit is the metric one."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 2000,
   "documented": "32001",
   "name": "Device Status Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Initializing",
    "1": "Diagnostic",
    "2": "Stopped",
    "3": "Break",
    "4": "Level Test",
    "5": "Standby",
    "6": "Humidifying",
    "7": "Filling",
    "8": "Idle",
    "9": "Draining",
    "10": "Remote Off",
    "11": "Keep Warm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2001,
   "documented": "32002",
   "name": "Device Status Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Initializing",
    "1": "Diagnostic",
    "2": "Stopped",
    "3": "Break",
    "4": "Level Test",
    "5": "Standby",
    "6": "Humidifying",
    "7": "Filling",
    "8": "Idle",
    "9": "Draining",
    "10": "Remote Off",
    "11": "Keep Warm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2002,
   "documented": "32003",
   "name": "Maintenance and Error Status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Service Info",
    "1": "Warning",
    "2": "RO Service",
    "3": "Extended Maintenance",
    "4": "Small Maintenance",
    "5": "Activation Code",
    "6": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2003,
   "documented": "32004",
   "name": "ErrorWarning Code",
   "description": "0 = no error; other codes are listed in the device operation manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2004,
   "documented": "32005",
   "name": "Overheat Switch Cyl. A",
   "description": "Range 0 = Open 1 = Closed (=ok).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2005,
   "documented": "32006",
   "name": "Overheat Switch Cyl. B",
   "description": "Range 0 = Open 1 = Closed (=ok).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2006,
   "documented": "32007",
   "name": "External Safety Loop Cyl. A",
   "description": "Range 0 = Open 1 = Closed (=ok).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2007,
   "documented": "32008",
   "name": "External Safety Loop Cyl. B",
   "description": "Range 0 = Open 1 = Closed (=ok).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2008,
   "documented": "32009",
   "name": "Security Floater Cyl. A",
   "description": "Range 0 = Open 1 = Closed (=ok).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2009,
   "documented": "32010",
   "name": "Security Floater Cyl. B",
   "description": "Range 0 = Open 1 = Closed (=ok).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2010,
   "documented": "32011",
   "name": "Heating Voltage Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2011,
   "documented": "32012",
   "name": "Heating Voltage Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2012,
   "documented": "32013",
   "name": "Blower Pack Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On (ready)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2013,
   "documented": "32014",
   "name": "Blower Pack Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On (ready)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2014,
   "documented": "32015",
   "name": "Main Contactor Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2015,
   "documented": "32016",
   "name": "Main Contactor Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2016,
   "documented": "32017",
   "name": "Relay Pump Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2017,
   "documented": "32018",
   "name": "Relay Pump Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2018,
   "documented": "32019",
   "name": "Inlet Valve 1 Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2019,
   "documented": "32020",
   "name": "Inlet Valve 1 Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2020,
   "documented": "32021",
   "name": "Inlet Valve 2 Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2021,
   "documented": "32022",
   "name": "Inlet Valve 2 Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2022,
   "documented": "32023",
   "name": "Drain Cooling Valve Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2023,
   "documented": "32024",
   "name": "Drain Cooling Valve Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2024,
   "documented": "32025",
   "name": "Complete Drain Valve Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2025,
   "documented": "32026",
   "name": "Complete Drain Valve Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2026,
   "documented": "32027",
   "name": "Leakage Sensor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off (leak)",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2027,
   "documented": "32028",
   "name": "Furnace fan (UL) / external pipe flush (CE)",
   "description": "UL units: remote furnace/fan 0 off, 1 on. CE units: pipe flush 0 closed, 1 open.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2028,
   "documented": "32029",
   "name": "Level Cyl. A",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "no level",
    "1": "low",
    "2": "low-mid",
    "3": "mid",
    "4": "mid-high",
    "5": "high"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2029,
   "documented": "32030",
   "name": "Level Cyl. B",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "no level",
    "1": "low",
    "2": "low-mid",
    "3": "mid",
    "4": "mid-high",
    "5": "high"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2030,
   "documented": "32031",
   "name": "Nominal Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "200V",
    "1": "208V",
    "2": "230 V",
    "3": "240 V",
    "4": "380 V",
    "5": "400 V",
    "6": "415 V",
    "7": "440 V",
    "8": "460 V",
    "9": "480 V",
    "10": "500 V",
    "11": "550V",
    "12": "600 V"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2041,
   "documented": "32042",
   "name": "Max Hum. Capacity",
   "description": "Range 5 - 160 kg/h 10 - 360 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2043,
   "documented": "32044",
   "name": "Max Hum. Capacity Cyl. A",
   "description": "Range 5 - 40 kg/h 10 - 90 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2045,
   "documented": "32046",
   "name": "Max Hum. Capacity Cyl. B",
   "description": "Range 5 - 40 kg/h 10 - 90 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2047,
   "documented": "32048",
   "name": "Actual Hum. Capacity",
   "description": "Range 0 - 160 kg/h 0 - 360 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2049,
   "documented": "32050",
   "name": "Actual Hum. Capacity Cyl. A",
   "description": "Range 0 - 40 kg/h 0 - 90 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2051,
   "documented": "32052",
   "name": "Actual Hum. Capacity Cyl. B",
   "description": "Range 0 - 40 kg/h 0 - 90 lb/hr. Metric or imperial per controller setting.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2053,
   "documented": "32054",
   "name": "Control CH1",
   "description": "Range 0 - 100%.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2055,
   "documented": "32056",
   "name": "Control CH2",
   "description": "Range 0 - 100%.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2057,
   "documented": "32058",
   "name": "System Demand",
   "description": "Range 0 - 100%.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2059,
   "documented": "32060",
   "name": "Operating Hours",
   "description": "Range 0 - 1'200'000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2061,
   "documented": "32062",
   "name": "Operating Hours Cyl. A",
   "description": "Range 0 - 1'200'000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2063,
   "documented": "32064",
   "name": "Operating Hours Cyl. B",
   "description": "Range 0 - 1'200'000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2065,
   "documented": "32066",
   "name": "Next Small Maintenance Cyl. A",
   "description": "Range 0 - 6000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2067,
   "documented": "32068",
   "name": "Next Small Maintenance Cyl. B",
   "description": "Range 0 - 6000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2069,
   "documented": "32070",
   "name": "Next Extended Maintenance Cyl. A",
   "description": "Range 0 - 6000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2071,
   "documented": "32072",
   "name": "Next Extended Maintenance Cyl. B",
   "description": "Range 0 - 6000 h.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3000,
   "documented": "43001",
   "name": "Setpoint CH1",
   "description": "Range 5 - 95 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3001,
   "documented": "43002",
   "name": "Setpoint CH2",
   "description": "Range 5 - 95 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3002,
   "documented": "43003",
   "name": "P-Band CH1",
   "description": "Range 6 - 65 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3003,
   "documented": "43004",
   "name": "P-Band CH2",
   "description": "Range 6 - 65 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3004,
   "documented": "43005",
   "name": "I-Time CH1",
   "description": "Range 1 - 60 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3005,
   "documented": "43006",
   "name": "I-Time CH2",
   "description": "Range 1 - 60 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3006,
   "documented": "43007",
   "name": "Capacity Limitation",
   "description": "Range 20 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3007,
   "documented": "43008",
   "name": "Actual humidity or demand via Modbus CH1",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3008,
   "documented": "43009",
   "name": "Actual humidity or demand via Modbus CH2",
   "description": "Range 0 - 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5001,
   "documented": "45002",
   "name": "Remote RS Drain",
   "description": "Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5002,
   "documented": "45003",
   "name": "Remote RS Drain Cyl. A",
   "description": "Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5003,
   "documented": "45004",
   "name": "Remote RS Drain Cyl. B",
   "description": "Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "watchdog": "When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.",
  "quirks": [
   "The address column is the wire address; 32001 is address 2000.",
   "Floats are two registers, MSR first by default."
  ],
  "summary": "Read input registers 2000-2030 (UInt16) and 2041-2072 (floats). Write channel 1 demand or humidity to holding 3007 (and channel 2 to 3008 for dual control).",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 2000,
    "why": "Status cylinder A"
   },
   {
    "table": "input_register",
    "address": 2002,
    "why": "Maintenance and error status"
   },
   {
    "table": "input_register",
    "address": 2003,
    "why": "Error/warning code"
   },
   {
    "table": "input_register",
    "address": 2047,
    "why": "Actual capacity"
   },
   {
    "table": "input_register",
    "address": 2057,
    "why": "System demand"
   },
   {
    "table": "holding_register",
    "address": 3007,
    "why": "Demand/humidity via Modbus CH1"
   }
  ],
  "enable": "Controls > Signal Settings: set Source = Modbus.",
  "setup": [
   "Menu > password 8808 > Network > Modbus Settings: set protocol (Modbus/RTU or Modbus/TCP), address, parity, baud rate and register sequence; the controller restarts after a protocol change.",
   "For Modbus TCP set the IP parameters under Network > IP Settings (factory setting DHCP)."
  ],
  "gotchas": [
   "Cylinder B registers read meaningfully only on two-cylinder units."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/condair/rs-ii",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}