 "manufacturer": "Continental Control Systems",
 "manufacturer_slug": "continental-control-systems",
 "model": "WattNode Modbus (WNC) energy meter",
 "model_slug": "wattnode-modbus-wnc",
 "short_model": "WattNode Modbus",
 "aliases": [
  "WNC-3Y-208-MB",
  "WNC-3Y-400-MB",
  "WNC-3Y-480-MB",
  "WNC-3Y-600-MB",
  "WNC-3D-240-MB",
  "WNC-3D-400-MB",
  "WNC-3D-480-MB",
  "RWNC-3Y-208-MB",
  "RWNC-3Y-400-MB",
  "RWNC-3Y-480-MB",
  "RWNC-3Y-600-MB",
  "RWNC-3D-240-MB",
  "RWNC-3D-400-MB",
  "RWNC-3D-480-MB",
  "WattNode Revenue Modbus"
 ],
 "equipment_type": "Energy meter",
 "applies_to": "WattNode Modbus WNC and revenue RWNC models, firmware 18-24, per manual WNC-MB-1.18c (2015-11-03).",
 "summary": "The WattNode Modbus is a compact three-phase energy meter with external CTs and an RS-485 Modbus RTU port. Most values come both as 32-bit floats and as scaled integers; 32-bit values are sent low word first. This map covers energy (net, positive, negative, reactive, apparent), power, voltage, current, PF, frequency, demand, CT and demand configuration, communication overrides and diagnostics.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual documents registers one-based and says they are sent zero-based: EnergySum is documented at 1001 and appears on the bus as 1000 (0x03E8). Wire address = documented number - 1."
 },
 "default_word_order": "CDAB",
 "firmware": "18-24",
 "source": {
  "title": "WattNode Modbus Installation and Operation Manual",
  "doc_number": "WNC-MB-1.18c",
  "revision_date": "2015-11-03",
  "url": "https://ctlsys.com/m/WNC-MB-Ref-Manual.pdf",
  "pages": "Addressing and 32-bit order pp. 32-33; register lists pp. 34-39; baud DIP p. 20; model codes p. 52"
 },
 "notes": [
  "Word order: the manual says the first (lower) register of a float or 32-bit integer holds the least significant 16 bits (little-endian, 'byte order 1032' on Tridium), so 32-bit values are CDAB.",
  "Holding and input registers are interchangeable (functions 03 and 04 return the same data).",
  "Left out: ConfigPasscode (1601-1602, signedness not stated); integer power, current and demand registers (1209-1212, 1343-1360), which use the configurable PowerIntScale/CurrentIntScale factors; integer per-phase energies; gain/phase adjustment, creep and I/O mode settings; option information and custom register map registers.",
  "Read both halves of a 32-bit value in one request; the meter only guarantees a consistent pair within a single read.",
  "The Model register lists codes only for WNC models; revenue RWNC codes are not given.",
  "SerialNumber, UptimeSecs and TotalSecs are described as 32-bit long integers, which the manual defines as signed, so they are INT32."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "1001, 1002",
   "name": "EnergySum",
   "description": "Net (bidirectional) energy. Kept through power loss; can be reset or preset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1002,
   "documented": "1003, 1004",
   "name": "EnergyPosSum",
   "description": "Positive energy. Kept through power loss; can be reset or preset.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1004,
   "documented": "1005, 1006",
   "name": "EnergySumNR",
   "description": "Net energy, non-resettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1006,
   "documented": "1007, 1008",
   "name": "EnergyPosSumNR",
   "description": "Positive energy, non-resettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1008,
   "documented": "1009, 1010",
   "name": "PowerSum",
   "description": "Real power, sum of active phases.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1010,
   "documented": "1011, 1012",
   "name": "PowerA",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1012,
   "documented": "1013, 1014",
   "name": "PowerB",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1014,
   "documented": "1015, 1016",
   "name": "PowerC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1016,
   "documented": "1017, 1018",
   "name": "VoltAvgLN",
   "description": "Average line-to-neutral voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1018,
   "documented": "1019, 1020",
   "name": "VoltA",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1020,
   "documented": "1021, 1022",
   "name": "VoltB",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1022,
   "documented": "1023, 1024",
   "name": "VoltC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1024,
   "documented": "1025, 1026",
   "name": "VoltAvgLL",
   "description": "Average line-to-line voltage.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1026,
   "documented": "1027, 1028",
   "name": "VoltAB",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1028,
   "documented": "1029, 1030",
   "name": "VoltBC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1030,
   "documented": "1031, 1032",
   "name": "VoltAC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1032,
   "documented": "1033, 1034",
   "name": "Freq",
   "description": "Line frequency.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1100,
   "documented": "1101, 1102",
   "name": "EnergyA",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1102,
   "documented": "1103, 1104",
   "name": "EnergyB",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1104,
   "documented": "1105, 1106",
   "name": "EnergyC",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1106,
   "documented": "1107, 1108",
   "name": "EnergyPosA",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1108,
   "documented": "1109, 1110",
   "name": "EnergyPosB",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1110,
   "documented": "1111, 1112",
   "name": "EnergyPosC",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1112,
   "documented": "1113, 1114",
   "name": "EnergyNegSum",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1114,
   "documented": "1115, 1116",
   "name": "EnergyNegSumNR",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1116,
   "documented": "1117, 1118",
   "name": "EnergyNegA",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1118,
   "documented": "1119, 1120",
   "name": "EnergyNegB",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1120,
   "documented": "1121, 1122",
   "name": "EnergyNegC",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1122,
   "documented": "1123, 1124",
   "name": "EnergyReacSum",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kVARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1124,
   "documented": "1125, 1126",
   "name": "EnergyReacA",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kVARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1126,
   "documented": "1127, 1128",
   "name": "EnergyReacB",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kVARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1128,
   "documented": "1129, 1130",
   "name": "EnergyReacC",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kVARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1130,
   "documented": "1131, 1132",
   "name": "EnergyAppSum",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kVAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1132,
   "documented": "1133, 1134",
   "name": "EnergyAppA",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kVAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1134,
   "documented": "1135, 1136",
   "name": "EnergyAppB",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kVAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1136,
   "documented": "1137, 1138",
   "name": "EnergyAppC",
   "description": "Resettable/presettable.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "kVAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1138,
   "documented": "1139, 1140",
   "name": "PowerFactorAvg",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1140,
   "documented": "1141, 1142",
   "name": "PowerFactorA",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1142,
   "documented": "1143, 1144",
   "name": "PowerFactorB",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1144,
   "documented": "1145, 1146",
   "name": "PowerFactorC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1146,
   "documented": "1147, 1148",
   "name": "PowerReacSum",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1148,
   "documented": "1149, 1150",
   "name": "PowerReacA",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1150,
   "documented": "1151, 1152",
   "name": "PowerReacB",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1152,
   "documented": "1153, 1154",
   "name": "PowerReacC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "VAR",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1154,
   "documented": "1155, 1156",
   "name": "PowerAppSum",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1156,
   "documented": "1157, 1158",
   "name": "PowerAppA",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1158,
   "documented": "1159, 1160",
   "name": "PowerAppB",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1160,
   "documented": "1161, 1162",
   "name": "PowerAppC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "VA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1162,
   "documented": "1163, 1164",
   "name": "CurrentA",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1164,
   "documented": "1165, 1166",
   "name": "CurrentB",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1166,
   "documented": "1167, 1168",
   "name": "CurrentC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1168,
   "documented": "1169, 1170",
   "name": "Demand",
   "description": "Real power demand over the demand period.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1170,
   "documented": "1171, 1172",
   "name": "DemandMin",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1172,
   "documented": "1173, 1174",
   "name": "DemandMax",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1174,
   "documented": "1175, 1176",
   "name": "DemandApp",
   "description": "Apparent power demand (unit printed as W).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1176,
   "documented": "1177, 1178",
   "name": "DemandA",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1178,
   "documented": "1179, 1180",
   "name": "DemandB",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1180,
   "documented": "1181, 1182",
   "name": "DemandC",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "W",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1200,
   "documented": "1201, 1202",
   "name": "EnergySum (integer)",
   "description": "Constant 0.1 kWh resolution.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1202,
   "documented": "1203, 1204",
   "name": "EnergyPosSum (integer)",
   "description": "Constant 0.1 kWh resolution.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1204,
   "documented": "1205, 1206",
   "name": "EnergySumNR (integer)",
   "description": "Constant 0.1 kWh resolution.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1206,
   "documented": "1207, 1208",
   "name": "EnergyPosSumNR (integer)",
   "description": "Constant 0.1 kWh resolution.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1212,
   "documented": "1213",
   "name": "VoltAvgLN (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1213,
   "documented": "1214",
   "name": "VoltA (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1214,
   "documented": "1215",
   "name": "VoltB (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1215,
   "documented": "1216",
   "name": "VoltC (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1216,
   "documented": "1217",
   "name": "VoltAvgLL (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1217,
   "documented": "1218",
   "name": "VoltAB (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1218,
   "documented": "1219",
   "name": "VoltBC (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1219,
   "documented": "1220",
   "name": "VoltAC (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1220,
   "documented": "1221",
   "name": "Freq (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1312,
   "documented": "1313, 1314",
   "name": "EnergyNegSum (integer)",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1314,
   "documented": "1315, 1316",
   "name": "EnergyNegSumNR (integer)",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1322,
   "documented": "1323, 1324",
   "name": "EnergyReacSum (integer)",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kVARh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1330,
   "documented": "1331, 1332",
   "name": "EnergyAppSum (integer)",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.1,
   "units": "kVAh",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1338,
   "documented": "1339",
   "name": "PowerFactorAvg (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1339,
   "documented": "1340",
   "name": "PowerFactorA (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1340,
   "documented": "1341",
   "name": "PowerFactorB (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1341,
   "documented": "1342",
   "name": "PowerFactorC (integer)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1360,
   "documented": "1361",
   "name": "IoPinState",
   "description": "I/O pin digital input or output state (I/O option).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1361,
   "documented": "1362",
   "name": "PulseCount",
   "description": "I/O pin pulse count (I/O option).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1602,
   "documented": "1603",
   "name": "CtAmps",
   "description": "Sets all three CT ratings at once; default 5.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1603,
   "documented": "1604",
   "name": "CtAmpsA",
   "description": "Phase A CT rated current, 0-6000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1604,
   "documented": "1605",
   "name": "CtAmpsB",
   "description": "0-6000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1605,
   "documented": "1606",
   "name": "CtAmpsC",
   "description": "0-6000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1606,
   "documented": "1607",
   "name": "CtDirections",
   "description": "Invert CT orientations, 0-7.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1607,
   "documented": "1608",
   "name": "Averaging",
   "description": "Measurement averaging 0-3; default 1 (fast).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1608,
   "documented": "1609",
   "name": "PowerIntScale",
   "description": "Scale for integer power registers, 0 = auto (default).",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "W",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1609,
   "documented": "1610",
   "name": "DemPerMins",
   "description": "Demand period 1-720, default 15.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1610,
   "documented": "1611",
   "name": "DemSubints",
   "description": "Demand subintervals 1-10.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1618,
   "documented": "1619",
   "name": "PhaseOffset",
   "description": "Nominal angle between voltage phases; default 120.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "deg",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1619,
   "documented": "1620",
   "name": "ZeroEnergy",
   "description": "Write 1 to zero all resettable energy registers.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1620,
   "documented": "1621",
   "name": "ZeroDemand",
   "description": "Write 1 to zero all demand values.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1621,
   "documented": "1622",
   "name": "CurrentIntScale",
   "description": "Scale factor for integer currents, default 20000.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1650,
   "documented": "1651",
   "name": "ApplyComConfig",
   "description": "Write 1234 to apply 1652-1656; reads 1 if changes are pending.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1651,
   "documented": "1652",
   "name": "Address (Modbus address override)",
   "description": "Modbus address; non-zero overrides the DIP switches.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1652,
   "documented": "1653",
   "name": "BaudRate",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "DIP switch assigned",
    "1": "1200",
    "2": "2400",
    "3": "4800",
    "4": "9600",
    "5": "19200",
    "6": "38400"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1653,
   "documented": "1654",
   "name": "ParityMode",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "N81 - no parity, 1 stop bit",
    "1": "E81 - even parity, 1 stop bit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1654,
   "documented": "1655",
   "name": "ModbusMode",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RTU",
    "1": "TCP-RTU"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1655,
   "documented": "1656",
   "name": "ReplyDelay",
   "description": "Minimum reply delay 5-180 ms, default 5.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1700,
   "documented": "1701, 1702",
   "name": "SerialNumber",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1702,
   "documented": "1703, 1704",
   "name": "UptimeSecs",
   "description": "Seconds since last power on.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1704,
   "documented": "1705, 1706",
   "name": "TotalSecs",
   "description": "Total seconds of operation.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1706,
   "documented": "1707",
   "name": "Model",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "201": "WNC-3Y-208-MB",
    "202": "WNC-3Y-400-MB",
    "203": "WNC-3Y-480-MB",
    "204": "WNC-3Y-600-MB",
    "205": "WNC-3D-240-MB",
    "206": "WNC-3D-400-MB",
    "207": "WNC-3D-480-MB"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1707,
   "documented": "1708",
   "name": "Version",
   "description": "Firmware version.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1709,
   "documented": "1710",
   "name": "ErrorStatus",
   "description": "Recent error/event code; see the manual's error list.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1710,
   "documented": "1711",
   "name": "PowerFailCount",
   "description": "Power cycles, up to 32767.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the address and baud on the DIP switches, set CtAmps (1603), then read floats from 1001-1034 (documented numbers; wire 1000-1033) in one request, decoding each pair low word first.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 1000,
    "why": "EnergySum (kWh)"
   },
   {
    "table": "holding_register",
    "address": 1008,
    "why": "PowerSum (W)"
   },
   {
    "table": "holding_register",
    "address": 1016,
    "why": "Average L-N voltage"
   },
   {
    "table": "holding_register",
    "address": 1162,
    "why": "Current phase A"
   },
   {
    "table": "holding_register",
    "address": 1138,
    "why": "Average power factor"
   },
   {
    "table": "holding_register",
    "address": 1032,
    "why": "Frequency"
   },
   {
    "table": "holding_register",
    "address": 1602,
    "why": "CtAmps (must match the CTs)"
   }
  ],
  "enable": "Modbus RTU on RS-485 is always on. Address and baud come from the DIP switches unless overridden at 1652-1656 (write 1234 to 1651 to apply).",
  "watchdog": null,
  "quirks": [
   "32-bit values are low word first (CDAB).",
   "Documented numbers are one-based; subtract 1 on the wire.",
   "Float energy loses resolution above 100,000 kWh; the integer energy registers keep 0.1 kWh."
  ],
  "setup": [
   "Default 9600 baud (DIP switch 8 down), N81.",
   "Set CtAmps (1603) to the CT rating before reading power."
  ],
  "gotchas": [
   "A configuration passcode (1601) blocks writes if one was set.",
   "Writing a 32-bit register with two single writes must happen within 30 s with nothing else in between."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/continental-control-systems/wattnode-modbus-wnc",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}