 "manufacturer": "Cuby",
 "manufacturer_slug": "cuby",
 "model": "Cuby smart AC controller (Modbus RTU)",
 "model_slug": "smart-ac-controller",
 "short_model": "Cuby",
 "aliases": [
  "Cuby Smart",
  "Cuby AC controller",
  "Cuby minisplit controller"
 ],
 "equipment_type": "VRF / split AC gateway (IR-to-Modbus controller)",
 "applies_to": "Cuby smart IR controllers for mini-split air conditioners with the Modbus RTU firmware described in the 2025 'MODBUS REGISTERS' sheet (fixed address 1).",
 "summary": "Cuby makes a small controller that drives mini-split air conditioners over infrared and exposes them on Modbus RTU. The registers set power, mode, fan speed, setpoint, vanes and turbo, and report indoor temperature, humidity, occupancy and contact-open time from Cuby sensors. All values are single 16-bit registers.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "The sheet prints both the protocol address (0-based, e.g. 4 for the setpoint) and the PLC address (1-based, 5). The protocol address goes on the wire. The sheet does not name function codes; the registers are listed here as holding registers because the writable rows can only be holding registers and all rows share one address list."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "MODBUS REGISTERS",
  "doc_number": null,
  "revision_date": "2025",
  "url": "https://pages.cuby.mx/hubfs/Fichas%20t%C3%A9cnicas/Modbus-registers.pdf",
  "pages": "pp. 1-2"
 },
 "notes": [
  "Hosted on Cuby's own HubSpot file storage (pages.cuby.mx).",
  "The unit address is fixed at 1 and the serial setting is 9600 8N1 in this firmware; the sheet says later firmware will make them configurable.",
  "Indoor temperature, humidity, occupancy and open time read -32768 until a value is available; signed 16-bit is assumed for those rows because of that initial value.",
  "Address 5 and other gaps are not listed in the source."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0 (PLC 1)",
   "name": "AC ON/OFF",
   "description": "Power state of the air conditioner.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "1 (PLC 2)",
   "name": "AC MODE",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Heat",
    "2": "Dry",
    "3": "Fan only",
    "4": "Cool"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "2 (PLC 3)",
   "name": "FAN SPEED",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Low",
    "2": "Med",
    "3": "High"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "3 (PLC 4)",
   "name": "IR PROTOCOL",
   "description": "IR protocol 0-254; other values keep the configured protocol.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "4 (PLC 5)",
   "name": "AC Temperature Setpoint",
   "description": "Setpoint 16-31 °C, sent as °C x 10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "6 (PLC 7)",
   "name": "Command Type",
   "description": "Needed only for special commands; use 0 (power) otherwise.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Power",
    "1": "Temperature",
    "2": "Mode",
    "3": "Fan speed",
    "4": "Display",
    "5": "Vertical vane",
    "6": "Horizontal vane",
    "7": "Turbo",
    "8": "Units"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "7 (PLC 8)",
   "name": "Display",
   "description": "On some units any write toggles the display.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "8 (PLC 9)",
   "name": "Turbo",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "9 (PLC 10)",
   "name": "Vertical Vane",
   "description": "Vertical swing; positions 2-6 are model dependent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Auto",
    "2": "Top",
    "3": "Top-Center",
    "4": "Center",
    "5": "Bottom-Center",
    "6": "Bottom"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "10 (PLC 11)",
   "name": "Horizontal Vane",
   "description": "Horizontal swing; positions 2-7 are model dependent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Auto",
    "2": "Left",
    "3": "Left-Center",
    "4": "Center",
    "5": "Right-Center",
    "6": "Right",
    "7": "Sides"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "11 (PLC 12)",
   "name": "Temperature Units",
   "description": "Display units on air conditioners that support it.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Celsius",
    "1": "Fahrenheit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "12 (PLC 13)",
   "name": "Command Source",
   "description": "Code 0-31 for who sent the last command (IR remote, app, Modbus, etc.).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "13 (PLC 14)",
   "name": "Indoor Temperature",
   "description": "-50 to 125 °C as °C x 10; -32768 until first reading.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "15 (PLC 16)",
   "name": "Indoor Relative Humidity",
   "description": "0-100 % as % x 10; -32768 until first reading.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "19 (PLC 20)",
   "name": "Occupancy Status",
   "description": "-32768 until first reading.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Vacant",
    "1": "Occupied"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "22 (PLC 23)",
   "name": "Open Time",
   "description": "Seconds any contact sensor has been open (0-32000); resets when all close.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 40,
   "documented": "40 (PLC 41)",
   "name": "Force IR Command",
   "description": "Write 1 to send the IR command now; always reads 0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 48,
   "documented": "48 (PLC 49)",
   "name": "FW Version",
   "description": "Firmware version.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Connect RS485 at 9600 8N1 to unit 1. Write power (0), mode (1), fan (2) and setpoint x10 (4); read indoor temperature (13) and humidity (15).",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Power on/off"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Operating mode"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Setpoint (x10)"
   },
   {
    "table": "holding_register",
    "address": 13,
    "why": "Indoor temperature (x10)"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Fan speed"
   }
  ],
  "enable": "No enable step is described; Modbus RTU is active at fixed address 1.",
  "watchdog": null,
  "quirks": [
   "Setpoint and temperatures are x10 (225 = 22.5 °C).",
   "Special commands (display, turbo, swing, units) may need Command Type (6) set first.",
   "Display is a toggle on some air conditioners."
  ],
  "setup": [
   "Fixed address 1, 9600 baud, 8 data bits, no parity, 1 stop bit."
  ],
  "gotchas": [
   "Command Source (12) shows who sent the last command (IR remote, app, Modbus, rules, HTTP API, BACnet and others).",
   "If reads of the read-only rows fail with function 03, the sheet does not name function codes; try function 04."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/cuby/smart-ac-controller",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}