 "manufacturer": "Daikin",
 "manufacturer_slug": "daikin",
 "model": "EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)",
 "model_slug": "ekrhh-homehub",
 "short_model": "Daikin EKRHH HomeHub",
 "aliases": [
  "EKRHH",
  "Daikin HomeHub",
  "4P744838-1E",
  "Daikin Altherma 3 Modbus",
  "Altherma Smart Grid Modbus"
 ],
 "equipment_type": "Heat pump (air-to-water) Modbus interface",
 "applies_to": "Daikin HomeHub EKRHH in use case 3 (Modbus for Daikin Altherma air-to-water heat pumps) and use case 4 (Modbus smart-grid control of air-to-air heat pumps), installer reference guide 4P744838-1E (2026.01).",
 "summary": "The Daikin HomeHub (EKRHH) connects to a Daikin Altherma system and offers a Modbus TCP (port 502, or 802 with TLS) or Modbus RTU slave. Holding registers set leaving-water and room setpoints, operation mode, on/off, quiet mode, hot-water reheat and booster, weather-dependent mode and the smart-grid mode with power limits; input registers return error state and code, pump/compressor/heater/defrost states, water, outdoor and refrigerant temperatures, flow, power use and setpoint limits. For air-to-air units only the smart-grid mode and demand-control power limit are offered.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "1-based",
  "note": "The guide lists register offsets 1-based and says PDU addressing is 0-based: register 1 is requested at PDU address 0. Every wire address here is the printed offset minus one."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "Installer reference guide - Daikin HomeHub EKRHH",
  "doc_number": "4P744838-1E",
  "revision_date": "2026-01",
  "url": "https://www.daikin.eu/content/dam/document-library/Installer-reference-guide/heat/accessories/ekrhh/EKRHH_Installer%20reference%20guide_4PEN744838-1E_English.pdf",
  "pages": "pp. 39-44 use case 3 (protocol, data types, holding and input registers, special values); pp. 45-47 smart grid buffering; pp. 48-51 use case 4"
 },
 "notes": [
  "Data types are Daikin's: Temp16 and Pow16 are signed 16-bit values divided by 100 (°C and kW); Int16 is a signed 16-bit value with no scaling; Text16 is two ASCII characters. The holding-register setpoints are printed as Int16, so they are whole degrees.",
  "Holding offsets 59 and 61 (thermostat inputs): with external room thermostat control ([C-07]=1) they are only valid when thermostat type [C-05]=0 (SW contact), otherwise they read 0 (off). Not available on Daikin Altherma 3 R / 3 M units with Micon ID 20002203.",
  "Offsets 1001 and 1002 belong to use case 4 (air-to-air heat pumps) and are the only registers supported there. The type of 1001 is not printed; it is listed as INT16 with the same codes as offset 56.",
  "Special return values: 32767 = register unsupported, 32766 = register unavailable in this configuration, 32765 = value not loaded yet (also returned while the HomeHub synchronises).",
  "Writes to setpoint registers outside the configured range are clamped to the nearest limit; out-of-range writes to other registers are ignored."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 20,
   "documented": "21",
   "name": "Unit abnormality",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No error",
    "1": "Fault",
    "2": "Warning"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 21,
   "documented": "22",
   "name": "Unit abnormality code",
   "description": "Two ASCII characters, high byte first (e.g. 0x5538 = 'U8').",
   "data_type": "STRING",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "23",
   "name": "Unit abnormality sub code",
   "description": "0-99 on a unit error; 32766 if no error.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 29,
   "documented": "30",
   "name": "Circulation pump running",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "31",
   "name": "Compressor run",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 31,
   "documented": "32",
   "name": "Booster heater run",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "33",
   "name": "Disinfection operation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "35",
   "name": "Defrost",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 35,
   "documented": "36",
   "name": "Hot Start",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "37",
   "name": "3-way valve",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Space heating",
    "1": "DHW"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 37,
   "documented": "38",
   "name": "Operation mode",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "1": "Heating",
    "2": "Cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 39,
   "documented": "40",
   "name": "Leaving water temperature PHE",
   "description": "After the plate heat exchanger.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "41",
   "name": "Leaving water temperature BUH",
   "description": "After the backup heater.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 41,
   "documented": "42",
   "name": "Return water temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "43",
   "name": "Domestic Hot Water temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 43,
   "documented": "44",
   "name": "Outside air temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 44,
   "documented": "45",
   "name": "Liquid refrigerant temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 48,
   "documented": "49",
   "name": "Flow rate",
   "description": "Litres per minute x 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "L/min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 49,
   "documented": "50",
   "name": "Remote controller room temperature Main",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 50,
   "documented": "51",
   "name": "Heat pump power consumption",
   "description": "Pow16: kW x 100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 51,
   "documented": "52",
   "name": "DHW normal operation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle/buffering",
    "1": "Operating"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 52,
   "documented": "53",
   "name": "Space heating/cooling normal operation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Idle/buffering",
    "1": "Operating"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 53,
   "documented": "54",
   "name": "Leaving water Main Heating setpoint Lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 54,
   "documented": "55",
   "name": "Leaving water Main Heating setpoint Upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 55,
   "documented": "56",
   "name": "Leaving water Main Cooling setpoint Lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 56,
   "documented": "57",
   "name": "Leaving water Main Cooling setpoint Upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 57,
   "documented": "58",
   "name": "Leaving water Add Heating setpoint Lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 58,
   "documented": "59",
   "name": "Leaving water Add Heating setpoint Upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 59,
   "documented": "60",
   "name": "Leaving water Add Cooling setpoint Lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 60,
   "documented": "61",
   "name": "Leaving water Add Cooling setpoint Upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 75,
   "documented": "76",
   "name": "Domestic Hot Water Upper temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 76,
   "documented": "77",
   "name": "Domestic Hot Water Lower temperature",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 83,
   "documented": "84",
   "name": "Room Heating setpoint Lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 84,
   "documented": "85",
   "name": "Room Heating setpoint Upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 85,
   "documented": "86",
   "name": "Room Cooling setpoint Lower limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 86,
   "documented": "87",
   "name": "Room Cooling setpoint Upper limit",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Leaving water Main Heating setpoint",
   "description": "Range set by field settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Leaving water Main Cooling setpoint",
   "description": "Range set by field settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "3",
   "name": "Operation mode",
   "description": "Reads 32766 on heating-only units.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto",
    "1": "Heating",
    "2": "Cooling"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "4",
   "name": "Space heating/cooling ON/OFF",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "6",
   "name": "Room thermostat control Heating setpoint Main",
   "description": "12-30 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7",
   "name": "Room thermostat control Cooling setpoint Main",
   "description": "15-35 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "9",
   "name": "Quiet mode operation",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "10",
   "name": "DHW reheat setpoint",
   "description": "30-60 °C; applied only with tank on, reheat-only mode and fixed setpoint.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "12",
   "name": "DHW reheat ON/OFF",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "13",
   "name": "DHW booster mode ON/OFF (Powerful)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "53",
   "name": "Weather dependent mode Main",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Fixed",
    "1": "Weather dependent",
    "2": "Fixed + scheduled",
    "3": "Weather dependent + scheduled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "54",
   "name": "Weather dependent mode Main LWT Heating setpoint offset",
   "description": "-10 to 10 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "55",
   "name": "Weather dependent mode Main LWT Cooling setpoint offset",
   "description": "-10 to 10 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "56",
   "name": "Smart Grid operation mode",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Free running",
    "1": "Forced off",
    "2": "Recommended on",
    "3": "Forced on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 56,
   "documented": "57",
   "name": "Power limit during Recommended on / buffering",
   "description": "Pow16: kW x 100, 0-20 kW.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "58",
   "name": "General power limit",
   "description": "Pow16: kW x 100, 0-20 kW.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "59",
   "name": "Thermostat Main Input A",
   "description": "Valid only with [C-05]=0 when [C-07]=1; not on Micon ID 20002203 units.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "61",
   "name": "Thermostat Add Input A",
   "description": "Valid only with [C-05]=0 when [C-07]=1; not on Micon ID 20002203 units.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "On"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 62,
   "documented": "63",
   "name": "Leaving water Add Heating setpoint",
   "description": "Range set by field settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "64",
   "name": "Leaving water Add Cooling setpoint",
   "description": "Range set by field settings.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "65",
   "name": "Weather dependent mode Add",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Fixed",
    "1": "Weather dependent",
    "2": "Fixed + scheduled",
    "3": "Weather dependent + scheduled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 65,
   "documented": "66",
   "name": "Weather dependent mode Add LWT Heating setpoint offset",
   "description": "-10 to 10 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 66,
   "documented": "67",
   "name": "Weather dependent mode Add LWT Cooling setpoint offset",
   "description": "-10 to 10 °C.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1000,
   "documented": "1001",
   "name": "Smart Grid operation mode (air-to-air use case)",
   "description": "Use case 4 only; type not printed, same codes as offset 56.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Free running",
    "1": "Forced off",
    "2": "Recommended on",
    "3": "Forced on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1001,
   "documented": "1002",
   "name": "Power limit for Demand Control (air-to-air use case)",
   "description": "Use case 4 only. Pow16: kW x 100, 0-20 kW.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Enable Modbus in the ONECTA app, then read input registers 21-53 for state and temperatures and write holding registers 1-13 and 53-58 for setpoints, modes and smart-grid control. Refresh written values periodically because the HomeHub only forwards changes.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 3,
    "why": "Space heating/cooling on/off"
   },
   {
    "table": "holding_register",
    "address": 2,
    "why": "Operation mode"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Leaving water heating setpoint"
   },
   {
    "table": "holding_register",
    "address": 55,
    "why": "Smart grid mode"
   },
   {
    "table": "holding_register",
    "address": 57,
    "why": "General power limit"
   },
   {
    "table": "input_register",
    "address": 20,
    "why": "Unit abnormality"
   },
   {
    "table": "input_register",
    "address": 21,
    "why": "Error code"
   },
   {
    "table": "input_register",
    "address": 30,
    "why": "Compressor running"
   },
   {
    "table": "input_register",
    "address": 43,
    "why": "Outside air temperature"
   },
   {
    "table": "input_register",
    "address": 50,
    "why": "Power consumption"
   }
  ],
  "enable": "Modbus (RTU or TCP/IP) is configured in the ONECTA app settings for the HomeHub (installer reference guide section 13.1.1).",
  "watchdog": null,
  "quirks": [
   "Modbus writes are change based: the HomeHub only updates the unit when it sees a change, so values lost during an outage are not resent. Refresh the state from the client periodically.",
   "After the compressor starts, power-limit writes can be overruled for 15 minutes with max(4.5 kW, register value).",
   "The error code (input 22) is two ASCII characters packed high byte first."
  ],
  "setup": [
   "RTU: 3-wire RS-485 on the HomeHub's X8A connector, 9600 baud, no parity, 8 data bits, 1 stop bit, slave address 1-247.",
   "TCP: port 502 without encryption or 802 with TLS, at the HomeHub's IP address."
  ],
  "gotchas": [
   "Room buffering during smart-grid requests needs unit control method [C-07]=2 (room thermostat control); tank buffering needs field settings [E-05]=1 and [E-06]=1.",
   "The DHW reheat setpoint only takes effect when the tank is enabled, heat pump mode is reheat only and the setpoint mode is fixed."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/daikin/ekrhh-homehub",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}