- Home
- Modbus register maps
- Danfoss
Manufacturer
Danfoss Modbus register maps
Updated 24 October 2026
3 Danfoss models, 174 registers in all, each re-typed from Danfoss’s own free documentation and checked against it.
- Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102
Danfoss: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| VLT AQUA Drive FC 202 (Modbus RTU) | RTU | Not stated | 8E1 | ABCD | parameter-derived | 61 |
| VLT AutomationDrive FC 301/302 (Modbus RTU) | RTU | 1 | 8E1 | ABCD | parameter-derived | 62 |
| VLT HVAC Drive FC 102 (Modbus RTU) | RTU | Not stated | 8E1 | ABCD | parameter-derived | 51 |