 "manufacturer": "Danfoss",
 "manufacturer_slug": "danfoss",
 "model": "VLT Compressor Drive CDS 803 (Modbus RTU)",
 "model_slug": "cds-803",
 "short_model": "CDS 803",
 "aliases": [
  "CDS803",
  "CDS-803",
  "VLT Compressor Drive CDS 803"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).",
 "summary": "Danfoss's drive for variable-speed refrigeration and air-conditioning compressors. Its RS-485 port runs Modbus RTU: the FC-profile control and status words are coils 1-16 and 33-48, and every parameter is a holding register at ten times its parameter number. This map covers the control/status coils, compressor readouts, fault and warning words, and the communication and timeout parameters.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": null,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "parameter-derived",
  "note": "The design guide states coil 1 is sent as 0000 and holding register 40001 as 0000. A parameter's register is 10 x its parameter number (3-03 -> 3030), sent minus 1: the guide's example reads 3-03 at start address 0x0BD5 (3029). Coils are 1-based too (coil 65 is sent as 64)."
 },
 "default_word_order": "ABCD",
 "firmware": "Design guide software 1.20; programming guide software 2.0",
 "source": {
  "title": "VLT Compressor Drive CDS 803 Design Guide (chapter 7 RS485 Installation and Set-up)",
  "doc_number": "MG18N202",
  "revision_date": "2015-12",
  "url": "https://files.danfoss.com/download/Drives/MG18N202.pdf",
  "pages": "Design Guide pp. 58-64 (coil and register addressing, coil table 7.15, CTW table 7.16, STW table 7.17, register table, parameter handling and read example 3-03 = 0016E360h pp. 63-64), FC profile pp. 64-67. Programming Guide MG18P202 (06/2019) parameter lists pp. 76-86 (conversion index and data type), 8-0*/8-3* descriptions pp. 37-39."
 },
 "notes": [
  "Parameter data (conversion index, data type) come from VLT Compressor Drive CDS 803 Programming Guide MG18P202, https://files.danfoss.com/download/Drives/MG18P202.pdf. Scale = 10^conversion index; the hour counters carry index 74 (factor 3600, i.e. hours expressed in seconds), so one count is one hour.",
  "32-bit values are high word first: the design guide reads 3-03 at registers 3030/3031 and gets 0016 E360 hex = 1500000 (1500.000 with conversion index -3).",
  "8-bit parameters (Uint8) are read and written as one 16-bit register. 16-34 Heatsink Temp (Int8) is left out because the sign extension in the 16-bit register is not stated.",
  "Coils 17-32 (speed reference) and 49-64 (output frequency / feedback) carry 16-bit words bit by bit; they are not listed. REF/MAV use 4000 hex = 100 % of the reference range (two's complement for negative).",
  "Alarm, warning and extended status words (16-90..16-94) are listed as raw UINT32; bit meanings are in the programming guide.",
  "The two guides cover different software versions (1.20 and 2.0); check 15-43 Software Version on site."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "1",
   "name": "CTW bit 0: Preset reference LSB",
   "description": "0/1 = reference select bit 0",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "2",
   "name": "CTW bit 1: Preset reference MSB",
   "description": "0/1 = reference select bit 1",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "3",
   "name": "CTW bit 2: DC brake",
   "description": "0 = DC brake, 1 = no DC brake",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "4",
   "name": "CTW bit 3: Coast stop",
   "description": "0 = coast stop, 1 = no coast stop",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "5",
   "name": "CTW bit 4: Quick stop",
   "description": "0 = quick stop, 1 = no quick stop",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "6",
   "name": "CTW bit 5: Freeze frequency",
   "description": "0 = freeze output frequency, 1 = no freeze",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "7",
   "name": "CTW bit 6: Ramp stop / start",
   "description": "0 = ramp stop, 1 = start",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "8",
   "name": "CTW bit 7: Reset",
   "description": "1 = reset (rising edge)",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "9",
   "name": "CTW bit 8: Jog",
   "description": "1 = jog",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "10",
   "name": "CTW bit 9: Ramp 1 / ramp 2",
   "description": "0 = ramp 1, 1 = ramp 2",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "11",
   "name": "CTW bit 10: Data valid",
   "description": "0 = control word ignored, 1 = data valid",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "12",
   "name": "CTW bit 11: Relay 1",
   "description": "1 = relay 1 on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "13",
   "name": "CTW bit 12: Relay 2",
   "description": "1 = relay 2 on",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "14",
   "name": "CTW bit 13: Set-up LSB",
   "description": "Set-up select",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 15,
   "documented": "16",
   "name": "CTW bit 15: Reversing",
   "description": "1 = reversing",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 32,
   "documented": "33",
   "name": "STW bit 0: Control ready",
   "description": "1 = control ready",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "34",
   "name": "STW bit 1: Drive ready",
   "description": "1 = frequency converter ready",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "35",
   "name": "STW bit 2: Coast stop / safety closed",
   "description": "0 = coast stop, 1 = safety closed",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "36",
   "name": "STW bit 3: Alarm",
   "description": "1 = alarm",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 39,
   "documented": "40",
   "name": "STW bit 7: Warning",
   "description": "1 = warning",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 40,
   "documented": "41",
   "name": "STW bit 8: At reference",
   "description": "1 = at reference",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 41,
   "documented": "42",
   "name": "STW bit 9: Hand / auto mode",
   "description": "0 = hand mode, 1 = auto mode",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 42,
   "documented": "43",
   "name": "STW bit 10: In frequency range",
   "description": "1 = in frequency range",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 43,
   "documented": "44",
   "name": "STW bit 11: Running",
   "description": "0 = stopped, 1 = running",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 45,
   "documented": "46",
   "name": "STW bit 13: Voltage warning",
   "description": "1 = voltage warning",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 46,
   "documented": "47",
   "name": "STW bit 14: Current limit",
   "description": "1 = in current limit",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 47,
   "documented": "48",
   "name": "STW bit 15: Thermal warning",
   "description": "1 = thermal warning",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 64,
   "documented": "65",
   "name": "Parameter write control",
   "description": "0 = parameter writes go to RAM only, 1 = RAM and EEPROM.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RAM only",
    "1": "RAM and EEPROM"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7",
   "name": "Last fault code",
   "description": "Fault code from the parameter database.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "8",
   "name": "Last error register",
   "description": "Address of the register where the last error occurred.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "9",
   "name": "Index pointer",
   "description": "Sub-index for array parameters.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3019,
   "documented": "3020",
   "name": "3-02 Minimum Reference",
   "description": "In the reference/feedback unit.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3029,
   "documented": "3030",
   "name": "3-03 Maximum Reference",
   "description": "In the reference/feedback unit.",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3409,
   "documented": "3410",
   "name": "3-41 Ramp 1 Ramp Up Time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3419,
   "documented": "3420",
   "name": "3-42 Ramp 1 Ramp Down Time",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4119,
   "documented": "4120",
   "name": "4-12 Motor Speed Low Limit [Hz]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4139,
   "documented": "4140",
   "name": "4-14 Motor Speed High Limit [Hz]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4189,
   "documented": "4190",
   "name": "4-19 Max Output Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8009,
   "documented": "8010",
   "name": "8-01 Control Site",
   "description": "Uint8 in one register; default digital and control word.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8019,
   "documented": "8020",
   "name": "8-02 Control Source",
   "description": "Uint8 in one register; default FC port.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8029,
   "documented": "8030",
   "name": "8-03 Control Timeout Time",
   "description": "0.1-200 s, default 20 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8039,
   "documented": "8040",
   "name": "8-04 Control Timeout Function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Freeze output",
    "2": "Stop",
    "3": "Jogging",
    "4": "Max. speed",
    "5": "Stop and trip",
    "20": "N2 override release"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8299,
   "documented": "8300",
   "name": "8-30 Protocol",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "FC",
    "2": "Modbus RTU"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8309,
   "documented": "8310",
   "name": "8-31 Address",
   "description": "1-247 for Modbus; default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8319,
   "documented": "8320",
   "name": "8-32 Baud Rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "2400",
    "1": "4800",
    "2": "9600",
    "3": "19200",
    "4": "38400",
    "5": "57600",
    "6": "76800",
    "7": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8329,
   "documented": "8330",
   "name": "8-33 Parity / Stop Bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even parity, 1 stop bit",
    "1": "Odd parity, 1 stop bit",
    "2": "No parity, 1 stop bit",
    "3": "No parity, 2 stop bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8349,
   "documented": "8350",
   "name": "8-35 Minimum Response Delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14999,
   "documented": "15000",
   "name": "15-00 Operating hours",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15009,
   "documented": "15010",
   "name": "15-01 Running Hours",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15029,
   "documented": "15030",
   "name": "15-03 Power Up's",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15039,
   "documented": "15040",
   "name": "15-04 Over Temp's",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15049,
   "documented": "15050",
   "name": "15-05 Over Volt's",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15299,
   "documented": "15300",
   "name": "15-30 Alarm Log: Error Code",
   "description": "Array (index via register 9); uint8 in one register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15999,
   "documented": "16000",
   "name": "16-00 Control Word",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16009,
   "documented": "16010",
   "name": "16-01 Reference [Unit]",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16019,
   "documented": "16020",
   "name": "16-02 Reference [%]",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16029,
   "documented": "16030",
   "name": "16-03 Status Word",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16049,
   "documented": "16050",
   "name": "16-05 Main Actual Value [%]",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16099,
   "documented": "16100",
   "name": "16-10 Power [kW]",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16119,
   "documented": "16120",
   "name": "16-12 Motor Voltage",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16129,
   "documented": "16130",
   "name": "16-13 Frequency",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16139,
   "documented": "16140",
   "name": "16-14 Motor current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16149,
   "documented": "16150",
   "name": "16-15 Frequency [%]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16159,
   "documented": "16160",
   "name": "16-16 Torque [Nm]",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.1,
   "units": "Nm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16179,
   "documented": "16180",
   "name": "16-18 Motor Thermal",
   "description": "Uint8 in one register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16219,
   "documented": "16220",
   "name": "16-22 Torque [%]",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16299,
   "documented": "16300",
   "name": "16-30 DC Link Voltage",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16349,
   "documented": "16350",
   "name": "16-35 Inverter Thermal",
   "description": "Uint8 in one register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16359,
   "documented": "16360",
   "name": "16-36 Inv. Nom. Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16369,
   "documented": "16370",
   "name": "16-37 Inv. Max. Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16499,
   "documented": "16500",
   "name": "16-50 External Reference",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16519,
   "documented": "16520",
   "name": "16-52 Feedback [Unit]",
   "description": "",
   "data_type": "INT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 0.001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16599,
   "documented": "16600",
   "name": "16-60 Digital Input",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16859,
   "documented": "16860",
   "name": "16-86 FC Port REF 1",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16899,
   "documented": "16900",
   "name": "16-90 Alarm Word",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16909,
   "documented": "16910",
   "name": "16-91 Alarm Word 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16919,
   "documented": "16920",
   "name": "16-92 Warning Word",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16929,
   "documented": "16930",
   "name": "16-93 Warning Word 2",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16939,
   "documented": "16940",
   "name": "16-94 Ext. Status Word",
   "description": "",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set 8-30 = [2] Modbus RTU plus 8-31 address, 8-32 baud and 8-33 parity, keep 8-02 = FC port, then drive the compressor with the control-word coils (coil 11 data valid, coil 7 start) and read 16-13 frequency, 16-14 current, 16-10 power and 16-90 alarm word.",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 6,
    "why": "CTW bit 6: ramp stop / start"
   },
   {
    "table": "coil",
    "address": 10,
    "why": "CTW bit 10: data valid"
   },
   {
    "table": "coil",
    "address": 43,
    "why": "STW: running"
   },
   {
    "table": "holding_register",
    "address": 16129,
    "why": "16-13 Frequency, 0.1 Hz"
   },
   {
    "table": "holding_register",
    "address": 16139,
    "why": "16-14 Motor current, 0.01 A"
   },
   {
    "table": "holding_register",
    "address": 16099,
    "why": "16-10 Power, 0.001 kW"
   },
   {
    "table": "holding_register",
    "address": 16899,
    "why": "16-90 Alarm word"
   }
  ],
  "enable": "8-30 Protocol = [2] Modbus RTU, 8-31 Address (1-247), 8-32 Baud Rate, 8-33 Parity/Stop Bits. 8-01 Control Site chooses digital inputs and/or control word; 8-02 Control Source must be FC Port; 8-50..8-56 decide how bus bits combine with digital inputs (most default to Logic OR).",
  "watchdog": "8-03 Control Timeout Time (0.1-200 s, default 20 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, N2 override release) act when the control word is not updated in time.",
  "quirks": [
   "Parameter register = parameter number x 10, request address = that minus 1.",
   "32-bit values are high word first (ABCD).",
   "CTW bit 10 (coil 11) must be 1 or the control word is ignored.",
   "Coil 65 chooses whether parameter writes also go to EEPROM."
  ],
  "setup": [
   "Defaults: address 1, even parity with 1 stop bit; the protocol default is FC, so 8-30 must be changed to Modbus RTU.",
   "The guides say the default baud rate depends on the protocol chosen in 8-30 and do not print the Modbus default, so set 8-32 explicitly (2400-115200)."
  ],
  "gotchas": [
   "Changing 8-30 Protocol may change the baud rate (8-32); re-check it after switching to Modbus."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/danfoss/cds-803",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}