 "manufacturer": "Danfoss",
 "manufacturer_slug": "danfoss",
 "model": "VLT Micro Drive FC 51 (Modbus RTU)",
 "model_slug": "fc-51",
 "short_model": "FC 51",
 "aliases": [
  "FC 51",
  "FC51",
  "VLT Micro Drive",
  "VLT Micro Drive FC 51"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.",
 "summary": "Danfoss's smallest VLT drive with Modbus RTU on the RS-485 terminals. Control and status run through coils (control word bits at coils 1-16, status bits at coils 33-48), and every parameter is a holding register at 10 x its parameter number. This map covers the control and status coils, the Modbus and timeout settings, counters and the 16-xx readouts.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "parameter-derived",
  "note": "The design guide says Modbus addresses are referenced to 0: coil 1 is coil 0 on the wire and holding register 40001 is register 0. A parameter's register number is 10 x its parameter number (16-13 -> 16130; 3-12 is read in holding register 3120) and the request carries that number minus 1 (16-13 at address 16129). Coil n is address n - 1."
 },
 "default_word_order": null,
 "firmware": "3.1x",
 "source": {
  "title": "Design Guide VLT Micro Drive FC 51",
  "doc_number": "MG02K402",
  "revision_date": "2016-01",
  "url": "https://assets.danfoss.com/documents/273509/AJ361178983102en-000401.pdf",
  "pages": "8.8 Modbus RTU pp. 72-77: 8.8.8 coil register addressing and tables 8.15-8.17 (coils, control word, status word), table 8.18 address/registers, 8.8.10 function codes, 8.9 parameter handling, storage (coil 65) and IND"
 },
 "notes": [
  "Parameter data (type, conversion index, defaults, option lists) come from the VLT Micro Drive FC 51 Programming Guide MG02C702 (12/2014, software 3.1x), https://assets.danfoss.com/documents/273489/AU361182403098en-000901.pdf, section 5.2 parameter lists. Conversion index -1 = x0.1, -2 = x0.01, -3 = x0.001, 0 = x1.",
  "Left out: all 32-bit parameters (3-02, 3-03, 3-41, 3-42, 15-00 to 15-03, 16-01, 16-52, 16-90, 16-92, 16-94). The FC 51 guides only say they take 2 registers; the design guide's generic examples are inconsistent (3-14 at 3410, and a 3-03 read whose bytes 00 16 E3 60 are described as 000088B8 = 35 Hz), and Danfoss's general Modbus RTU instructions MG92B102 are written for software 6.4x and do not name the FC 51, so the word order is not settled for this drive.",
  "The design guide's 32-bit example names 3-14 at registers 3410/3411; by the x10 rule 3-14 is register 3140, and the programming guide types 3-14 as Int16. Treat that example as a typo.",
  "Uint8 parameters are read and written as one 16-bit register.",
  "Section 8.11 lists CTW/REF at holding registers 50000/50010 and STW/MAV at 50200/50210 (and, from software 2.32, 2810/2811 and 2910/2911), but the same section says to set 8-30 = [0] FC, so their use with Modbus is unclear and they are not listed. Coils 1-16 carry the control word, 17-32 the bus reference (16-bit, 0x0-0xFFFF = -200 %..~200 %), 33-48 the status word and 49-64 output frequency (open loop) or feedback (closed loop); the reference and actual-value coil groups are not listed bit by bit.",
  "Coil 15 (control word bit 14) is unused in the FC profile table and is not listed; status coils 37-39 and 45 are 'not used'.",
  "Alarm and warning words (16-90/16-92) are 32-bit and left out for the word-order reason above; use status coil 36 (alarm) and 40 (warning) instead.",
  "Left out: 16-05 and 16-15 (normalised percentages), 16-50/16-51 external and pulse references, text parameters (15-4x), the fault log arrays (15-30, need IND) and Smart Logic groups."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "1",
   "name": "CTW bit 0: preset reference LSB",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "2",
   "name": "CTW bit 1: preset reference MSB",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "3",
   "name": "CTW bit 2: DC brake",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "DC brake",
    "1": "No DC brake"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "4",
   "name": "CTW bit 3: coast stop",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Coast stop",
    "1": "No coast stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "5",
   "name": "CTW bit 4: quick stop",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Quick stop",
    "1": "No quick stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "6",
   "name": "CTW bit 5: freeze frequency",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Freeze frequency",
    "1": "No freeze frequency"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "7",
   "name": "CTW bit 6: ramp stop / start",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ramp stop",
    "1": "Start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "8",
   "name": "CTW bit 7: reset",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No reset",
    "1": "Reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "9",
   "name": "CTW bit 8: jog",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No jog",
    "1": "Jog"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "10",
   "name": "CTW bit 9: ramp select",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ramp 1",
    "1": "Ramp 2"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "11",
   "name": "CTW bit 10: data valid",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Data not valid",
    "1": "Data valid"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "12",
   "name": "CTW bit 11: relay 1",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Relay 1 off",
    "1": "Relay 1 on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "13",
   "name": "CTW bit 12: relay 2",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Relay 2 off",
    "1": "Relay 2 on"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "14",
   "name": "CTW bit 13: set-up select LSB",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 15,
   "documented": "16",
   "name": "CTW bit 15: reversing",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No reversing",
    "1": "Reversing"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 32,
   "documented": "33",
   "name": "STW bit 0: control ready",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Control not ready",
    "1": "Control ready"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "34",
   "name": "STW bit 1: drive ready",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not ready",
    "1": "Ready"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "35",
   "name": "STW bit 2: coast stop / safety closed",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Coast stop",
    "1": "Safety closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "36",
   "name": "STW bit 3: alarm",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No alarm",
    "1": "Alarm"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 39,
   "documented": "40",
   "name": "STW bit 7: warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No warning",
    "1": "Warning"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 40,
   "documented": "41",
   "name": "STW bit 8: at reference",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not at reference",
    "1": "At reference"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 41,
   "documented": "42",
   "name": "STW bit 9: hand/auto",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Hand mode",
    "1": "Auto mode"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 42,
   "documented": "43",
   "name": "STW bit 10: frequency range",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Out of frequency range",
    "1": "In frequency range"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 43,
   "documented": "44",
   "name": "STW bit 11: running",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stopped",
    "1": "Running"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 45,
   "documented": "46",
   "name": "STW bit 13: voltage warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No voltage warning",
    "1": "Voltage warning"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 46,
   "documented": "47",
   "name": "STW bit 14: current limit",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not in current limit",
    "1": "Current limit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 47,
   "documented": "48",
   "name": "STW bit 15: thermal warning",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No thermal warning",
    "1": "Thermal warning"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 64,
   "documented": "65",
   "name": "Parameter write control",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Writes go to RAM only",
    "1": "Writes go to RAM and EEPROM"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "7",
   "name": "Last fault code",
   "description": "Fault code from the parameter database.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "9",
   "name": "Index pointer (IND)",
   "description": "Array index used for array parameters such as 3-10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4119,
   "documented": "4120 (par. 4-12)",
   "name": "4-12 Motor Speed Low Limit [Hz]",
   "description": "Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4139,
   "documented": "4140 (par. 4-14)",
   "name": "4-14 Motor Speed High Limit [Hz]",
   "description": "Write only when stopped.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8009,
   "documented": "8010 (par. 8-01)",
   "name": "8-01 Control Site",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Digital and control word",
    "1": "Digital only",
    "2": "Control word only"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8019,
   "documented": "8020 (par. 8-02)",
   "name": "8-02 Control Word Source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "None",
    "1": "FC RS485"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8029,
   "documented": "8030 (par. 8-03)",
   "name": "8-03 Control Word Timeout Time",
   "description": "0.1-6500 s, factory 1.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8039,
   "documented": "8040 (par. 8-04)",
   "name": "8-04 Control Word Timeout Function",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Freeze output",
    "2": "Stop",
    "3": "Jogging",
    "4": "Max. speed",
    "5": "Stop and trip"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8299,
   "documented": "8300 (par. 8-30)",
   "name": "8-30 Protocol",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "FC",
    "2": "Modbus"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8309,
   "documented": "8310 (par. 8-31)",
   "name": "8-31 Address",
   "description": "1-247, factory 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8319,
   "documented": "8320 (par. 8-32)",
   "name": "8-32 FC Port Baud Rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "2400",
    "1": "4800",
    "2": "9600 (default with FC protocol)",
    "3": "19200 (default with Modbus)",
    "4": "38400"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8329,
   "documented": "8330 (par. 8-33)",
   "name": "8-33 FC Port Parity",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even parity, 1 stop bit",
    "1": "Odd parity, 1 stop bit",
    "2": "No parity, 1 stop bit",
    "3": "No parity, 2 stop bits"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8349,
   "documented": "8350 (par. 8-35)",
   "name": "8-35 Minimum Response Delay",
   "description": "0.001-0.5 s, factory 0.010 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15039,
   "documented": "15040 (par. 15-04)",
   "name": "15-04 Over Temp's",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15049,
   "documented": "15050 (par. 15-05)",
   "name": "15-05 Over Volt's",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15999,
   "documented": "16000 (par. 16-00)",
   "name": "16-00 Control Word",
   "description": "Last control word received, hex.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16019,
   "documented": "16020 (par. 16-02)",
   "name": "16-02 Reference %",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16029,
   "documented": "16030 (par. 16-03)",
   "name": "16-03 Status Word",
   "description": "Status word, hex; bits as coils 33-48.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16099,
   "documented": "16100 (par. 16-10)",
   "name": "16-10 Power [kW]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16119,
   "documented": "16120 (par. 16-12)",
   "name": "16-12 Motor Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16129,
   "documented": "16130 (par. 16-13)",
   "name": "16-13 Frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16139,
   "documented": "16140 (par. 16-14)",
   "name": "16-14 Motor Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16179,
   "documented": "16180 (par. 16-18)",
   "name": "16-18 Motor Thermal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16299,
   "documented": "16300 (par. 16-30)",
   "name": "16-30 DC Link Voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16339,
   "documented": "16340 (par. 16-34)",
   "name": "16-34 Heatsink Temp.",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16349,
   "documented": "16350 (par. 16-35)",
   "name": "16-35 Inverter Thermal",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16359,
   "documented": "16360 (par. 16-36)",
   "name": "16-36 Inv. Nom. Current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16599,
   "documented": "16600 (par. 16-60)",
   "name": "16-60 Digital input 18,19,27,33",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16619,
   "documented": "16620 (par. 16-62)",
   "name": "16-62 Analog Input 53 (V)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16629,
   "documented": "16630 (par. 16-63)",
   "name": "16-63 Analog Input 53 (mA)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16639,
   "documented": "16640 (par. 16-64)",
   "name": "16-64 Analog Input 60",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16649,
   "documented": "16650 (par. 16-65)",
   "name": "16-65 Analog Output 42 [mA]",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "mA",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set 8-30 = Modbus, 8-31 address, 8-32/8-33 baud and parity, keep 8-02 = FC RS485, then drive the unit with coils 1-16 (write coils 3, 4, 5, 7 and 11 = 1 to run) and the reference on coils 17-32. Read coils 33-48 for status and holding registers 16130/16140 for frequency and current.",
  "minimum_registers": [
   {
    "table": "coil",
    "address": 6,
    "why": "Start (1) / ramp stop (0)"
   },
   {
    "table": "coil",
    "address": 10,
    "why": "Data valid - must be 1"
   },
   {
    "table": "coil",
    "address": 43,
    "why": "Running status"
   },
   {
    "table": "coil",
    "address": 35,
    "why": "Alarm status"
   },
   {
    "table": "coil",
    "address": 39,
    "why": "Warning status"
   },
   {
    "table": "holding_register",
    "address": 16129,
    "why": "16-13 Frequency, 0.1 Hz"
   },
   {
    "table": "holding_register",
    "address": 16139,
    "why": "16-14 Motor current, 0.01 A"
   },
   {
    "table": "holding_register",
    "address": 8299,
    "why": "8-30 Protocol"
   }
  ],
  "enable": "Set 8-30 Protocol = [2] Modbus RTU (takes effect only after the drive is powered off and on), 8-31 Address (1-247, factory 1), 8-32 baud (19200 is the default once Modbus is chosen) and 8-33 parity (factory even, 1 stop bit). 8-02 must stay [1] FC RS485 and 8-01 Control Site decides whether terminals, the control word or both act; 8-50 to 8-56 (factory Logic OR) set how bus and terminal commands combine.",
  "watchdog": "8-03 Control Word Timeout Time (0.1-6500 s, factory 1.0 s) with 8-04 Control Word Timeout Function: Off (factory), Freeze output, Stop, Jogging, Max. speed, or Stop and trip.",
  "quirks": [
   "Parameter register = 10 x parameter number, wire address = that minus 1 (16-13 -> 16129).",
   "Control word bits are active-low for stops: coils 3-5 must be 1 (no DC brake, no coast, no quick stop) and coil 7 = 1 starts.",
   "Coil 11 (data valid) must be 1 or the control word is ignored."
  ],
  "setup": [
   "Coil 65 = 1 makes parameter writes go to EEPROM as well as RAM; leave it 0 for cyclic writes.",
   "Array parameters need holding register 9 (IND) set to the index first."
  ],
  "gotchas": [
   "With factory 8-04 = Off the drive keeps running if the master stops polling.",
   "Holding registers 50000-50210 (and 2810-2911) are described in the design guide alongside an instruction to set 8-30 = FC; use the coils for Modbus control."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/danfoss/fc-51",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}