 "manufacturer": "Datakom",
 "model": "DKG-705",
 "short_model": "DKG-705",
 "aliases": [
  "DKG 705",
  "DKG705"
 ],
 "equipment_type": "Generator controller",
 "applies_to": "Datakom DKG-705 AMF, parallel-to-mains and dual genset synchronization unit with J1939, Modbus application manual V-02-07 (14.04.2008).",
 "summary": "The DKG-705 is a Datakom genset controller for automatic mains failure, mains paralleling and dual-genset synchronization. Its Modbus RTU slave runs on the RS232 port (or RS422/485 via an external converter) and exposes mains and genset voltages, currents, frequencies, engine values, alarm and relay bit fields, J1939 engine data and a register for changing the operating mode. All data is read with function 03 and written one register at a time with function 06.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": null,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Register addresses are printed in hex and go straight into the request; the manual's example 01 03 00 20 00 10 reads 16 registers starting at 20h (32 decimal)."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "DKG-705 Modbus Application Manual",
  "doc_number": "V-02-07",
  "revision_date": "2008-04-14",
  "url": "https://www.datakom.com.tr/upload/Files/705_MODBUS.pdf",
  "pages": "Register definitions, pp. 5-13"
 },
 "notes": [
  "Word order: the manual states that for data longer than 16 bits the least significant register comes first, so the 32-bit engine-hours value is CDAB.",
  "Coefficients: the 'coefficient' column is the factor the value was multiplied by before storing (e.g. x10 oil pressure in bars), so scale here is 1/coefficient.",
  "Registers marked '8bit' carry their value in the low byte only; the high byte must be ignored.",
  "Left out: genset and mains active, reactive and apparent power and power factor. Active and reactive power use a sign-magnitude format (high 8 bits sign, low 24 bits value), PF is a signed byte, and the manual gives no power unit.",
  "Left out: the clock registers (BCD), charge input ratio and GOV/AVR output percentages (fractional encodings), synchroscope angle (sign-magnitude), J1939 temperatures (offset), the parameter block from 1000h and most J1939 warning slots.",
  "The source names phase sets R/S/T and U/V/W but does not say which is mains and which is genset."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0000",
   "name": "Phase R voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0001",
   "name": "Phase S voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0002",
   "name": "Phase T voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0003",
   "name": "Phase U voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0004",
   "name": "Phase V voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0005",
   "name": "Phase W voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0006",
   "name": "Phase U current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0007",
   "name": "Phase V current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0008",
   "name": "Phase W current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "0009",
   "name": "Phase R current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "000A",
   "name": "Phase S current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "000B",
   "name": "Phase T current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 12,
   "documented": "000C",
   "name": "Phase RS voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "000D",
   "name": "Phase ST voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "000E",
   "name": "Phase TR voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "000F",
   "name": "Phase UV voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "0010",
   "name": "Phase VW voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "0011",
   "name": "Phase WU voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "0012",
   "name": "Mains frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "0013",
   "name": "Genset frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "0014",
   "name": "Genset phase order",
   "description": "Low byte valid.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "7": "0 = phase order correct"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 21,
   "documented": "0015",
   "name": "Mains phase order",
   "description": "Low byte valid.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "7": "0 = phase order correct"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 42,
   "documented": "002A",
   "name": "Engine speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 43,
   "documented": "002B",
   "name": "Oil pressure",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 44,
   "documented": "002C",
   "name": "Coolant temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 45,
   "documented": "002D",
   "name": "Fuel level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 46,
   "documented": "002E",
   "name": "Oil temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 47,
   "documented": "002F",
   "name": "Battery voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 49,
   "documented": "0031",
   "name": "External DC voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 50,
   "documented": "0032",
   "name": "Shutdown alarm bits 1",
   "description": "1 = active.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "external input_0 shutdown alarm",
    "1": "external input_1 shutdown alarm",
    "2": "external input_2 shutdown alarm",
    "3": "external input_3 shutdown alarm",
    "4": "external input_4 shutdown alarm",
    "5": "external input_5 shutdown alarm",
    "6": "external input_6 shutdown alarm",
    "7": "external input_7 shutdown alarm",
    "9": "genset under frequency shutdown alarm",
    "10": "genset over frequency shutdown alarm",
    "11": "high battery voltage shutdown alarm",
    "12": "low fuel level (measured) shutdown alarm",
    "13": "high oil temperature (measured) shutdown alarm",
    "14": "high coolant temp. (measured) shutdown alarm",
    "15": "low oil pressure (measured) shutdown alarm"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 51,
   "documented": "0033",
   "name": "Shutdown alarm bits 2",
   "description": "1 = active.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "fail to stop shutdown alarm",
    "1": "fail to start shutdown alarm",
    "2": "genset low voltage fail shutdown alarm",
    "3": "genset high voltage fail shutdown alarm",
    "4": "slave unavailable shutdown alarm",
    "5": "genset phase sequence fail shutdown alarm",
    "6": "genset low rpm shutdown alarm",
    "7": "genset high rpm shutdown alarm",
    "11": "J1939 ECU communication fail shutdown alarm",
    "14": "communication lost shutdown alarm"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 52,
   "documented": "0034",
   "name": "Loaddump alarm bits",
   "description": "1 = active.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "external input_0 loaddump alarm",
    "1": "external input_1 loaddump alarm",
    "2": "external input_2 loaddump alarm",
    "3": "external input_3 loaddump alarm",
    "4": "external input_4 loaddump alarm",
    "5": "external input_5 loaddump alarm",
    "6": "external input_6 loaddump alarm",
    "7": "external input_7 loaddump alarm",
    "13": "genset reverse power loaddump alarm",
    "14": "genset excess power loaddump alarm",
    "15": "alternator overcurrent loaddump alarm"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 53,
   "documented": "0035",
   "name": "Warning bits 1",
   "description": "1 = active.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "11": "J1939 ECU warning",
    "12": "genset on load warning",
    "13": "mains on load warning",
    "14": "service request warning"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 54,
   "documented": "0036",
   "name": "Warning bits 2",
   "description": "1 = active.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "external input_0 warning",
    "1": "external input_1 warning",
    "2": "external input_2 warning",
    "3": "external input_3 warning",
    "4": "external input_4 warning",
    "5": "external input_5 warning",
    "6": "external input_6 warning",
    "7": "external input_7 warning",
    "8": "synchronization fail warning",
    "9": "genset under frequency warning",
    "10": "genset over frequency warning",
    "11": "high battery voltage warning",
    "12": "low fuel level (measured) warning",
    "13": "high oil temperature (measured) warning",
    "14": "high coolant temperature (measured) warning",
    "15": "low oil pressure (measured) warning"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 55,
   "documented": "0037",
   "name": "Warning bits 3",
   "description": "1 = active.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "mains phase sequence fail warning",
    "2": "charge fail warning",
    "3": "low battery voltage warning",
    "4": "AVR control fail warning",
    "5": "GOV control fail warning",
    "6": "genset low rpm warning",
    "7": "genset high rpm warning",
    "8": "mains failure at parallel warning",
    "9": "mains recerse power at parallel warning",
    "10": "mains frequency fail at parallel warning",
    "11": "no mains frequency at parallel warning",
    "12": "ROCOF (df/dt) failure at parallel warning",
    "13": "vectorshift (df/dt) failure at parallel warning",
    "14": "communication lost warning"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 57,
   "documented": "0039",
   "name": "On-board relay output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "relay_1 status (terminal_36)",
    "2": "relay_2 status ( terminal_33), start relay",
    "3": "relay_3 status (terminal_37)",
    "4": "relay_4 status (terminal_1), genset contactor",
    "5": "relay_5 status (terminal_10), mains contactor",
    "6": "relay_6 status (terminal_32), fuel relay",
    "7": "relay_7 status (terminal_35)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 58,
   "documented": "003A",
   "name": "Relay extension module status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "module_1, relay_1 status",
    "1": "module_1, relay_2 status",
    "2": "module_1, relay_3 status",
    "3": "module_1, relay_4 status",
    "4": "module_1, relay_5 status",
    "5": "module_1, relay_6 status",
    "6": "module_1, relay_7 status",
    "7": "module_1, relay_8 status",
    "8": "module_2, relay_1 status",
    "9": "module_2, relay_2 status",
    "10": "module_2, relay_3 status",
    "11": "module_2, relay_4 status",
    "12": "module_2, relay_5 status",
    "13": "module_2, relay_6 status",
    "14": "module_2, relay_7 status",
    "15": "module_2, relay_8 status"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 59,
   "documented": "003B",
   "name": "Relay function status 1",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "choke",
    "1": "preheat",
    "2": "crank",
    "3": "alarm (timed)",
    "4": "genset contactor",
    "5": "mains contactor",
    "6": "fuel",
    "7": "stop",
    "8": "load shedding",
    "9": "alarm (not timed)",
    "10": "load contactor",
    "11": "auto ready",
    "12": "master relay",
    "13": "exerciser on",
    "14": "fuel pump"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 60,
   "documented": "003C",
   "name": "Relay function status 2",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "external DC fail",
    "1": "idle speed operation",
    "2": "gas engine gas solenoid",
    "5": "flashing relay"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 61,
   "documented": "003D",
   "name": "Operating mode",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "4": "auto mode",
    "5": "off mode",
    "6": "test mode",
    "7": "load test mode"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 63,
   "documented": "003F",
   "name": "Genset operating status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "load on mains",
    "1": "waiting before fuel (preheat)",
    "2": "waiting before/between cranks",
    "3": "cranking",
    "4": "engine heating",
    "5": "synchronization for load transfer to genset",
    "6": "genset contactor timer (synch mode)",
    "7": "genset contactor timer (non synch mode)",
    "8": "load on genset",
    "9": "synchronization for load transfer to mains",
    "10": "mains contactor timer (synch mode)",
    "11": "mains conntactor timer (non synch mode)",
    "12": "cooldown operation",
    "13": "stopping",
    "14": "soft transfer from gen to mains",
    "15": "soft transfer from mains to gen"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 64,
   "documented": "0040",
   "name": "Last pressed key / mode command",
   "description": "Write a mode bit to change operating mode over Modbus.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "4": "Auto mode",
    "5": "Off mode",
    "6": "Test mode",
    "7": "Load test mode"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 96,
   "documented": "0060",
   "name": "J1939 engine speed",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.125,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 98,
   "documented": "0062",
   "name": "J1939 oil pressure",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 99,
   "documented": "0063-0064",
   "name": "J1939 total engine hours",
   "description": "Raw value is hours x20.",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 0.05,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 103,
   "documented": "0067",
   "name": "J1939 fuel pressure",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 105,
   "documented": "0069",
   "name": "J1939 fuel rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "l/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "0070",
   "name": "J1939 warning 1 FMI",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "0071",
   "name": "J1939 warning 1 SPN",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read up to 16 holding registers per request with function 03 from 0000h (electrical values) and 002Ah (engine values, alarms, status). Change operating mode by writing a mode bit to 0040h with function 06.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 3,
    "why": "Phase U voltage"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Phase U current"
   },
   {
    "table": "holding_register",
    "address": 19,
    "why": "Genset frequency"
   },
   {
    "table": "holding_register",
    "address": 42,
    "why": "Engine speed"
   },
   {
    "table": "holding_register",
    "address": 50,
    "why": "Shutdown alarms"
   },
   {
    "table": "holding_register",
    "address": 63,
    "why": "Genset operating status"
   },
   {
    "table": "holding_register",
    "address": 64,
    "why": "Operating mode command"
   }
  ],
  "enable": "Set a controller address (1-250) in parameter P_650 to turn Modbus on; address 0 disables Modbus and returns the port to the Rainbow protocol.",
  "watchdog": null,
  "quirks": [
   "Only functions 03 and 06 are supported; write one register at a time.",
   "A read of more than 16 registers returns only the first 16.",
   "Writing a read-only register returns exception code 10 (write protection)."
  ],
  "setup": [
   "Serial format is fixed at 9600 bps, 8 data bits, no parity, 1 stop bit.",
   "The Modbus port is RS232; use an external RS422/485 converter or modem for multi-drop or remote links."
  ],
  "gotchas": [
   "The unit replies at least 4.3 ms after the request; allow for it in master timing."
  ]
 },
 "manufacturer_slug": "datakom",
 "model_slug": "dkg-705",
 "page": "https://easymodbus.com/modbus-register-maps/datakom/dkg-705",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}