 "manufacturer": "Teledyne Detcon",
 "manufacturer_slug": "detcon",
 "model": "Model CX-IR infrared combustible gas sensor (Modbus RTU)",
 "model_slug": "cx-ir",
 "short_model": "CX-IR",
 "aliases": [
  "CX-IR",
  "Detcon CX-IR"
 ],
 "equipment_type": "Sensor (fixed gas detector)",
 "applies_to": "Teledyne Detcon CX-IR wired infrared gas sensors (RS-485 Modbus RTU and 4-20 mA), instruction manual Document #4428 Rev. 1.9.",
 "summary": "The CX-IR is an infrared combustible gas sensor from Teledyne Detcon with a 4-20 mA output and a Modbus RTU RS-485 port. The holding registers give the range, gas reading in %LEL, span level, sensor life, fault bits and calibration control, plus optional smart-battery registers in the 48199-48206 block. This map covers the documented registers except temperature and voltage.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "0-based",
  "note": "Registers are printed with a leading 4 starting at 40000 (device type), so 40002 is wire address 2 and 48204 is wire address 8204."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "CX-IR Instruction Manual",
  "doc_number": "Document #4428, Rev. 1.9",
  "revision_date": "2022-03-14",
  "url": "https://www.teledynegasandflamedetection.com/en-us/products/docs/areagas-cx-smart-ir-usermanual-english.pdf",
  "pages": "pp. 23-25 (sections 4.1-4.2.2, Table 2 register map)"
 },
 "notes": [
  "Left out: 40010 sensor temperature (°C, no data type or sign given) and 48205 battery/input voltage (unit volts but no scale given). Reserved registers 40008-40009 and 40012-40013 are skipped.",
  "The gas reading is listed in %LEL. A range divisor register exists (40014) but the manual does not say how it applies, so no scale is set.",
  "Calibration enable/status codes are not listed in the CX-IR manual.",
  "Supported functions: 03, 06 and 16. Writes to read-only registers are acknowledged but ignored.",
  "Battery registers only work with a Detcon smart battery pack; check bit 4 of 48204 first. Battery status refreshes about every 60 s."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "40000",
   "name": "Device type",
   "description": "Reads 42 for a CX-IR.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "42": "CX-IR"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "40001",
   "name": "Range",
   "description": "Detectable range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%LEL",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "40002",
   "name": "Gas reading",
   "description": "Current gas reading.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%LEL",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "40003",
   "name": "Calibration level",
   "description": "AutoSpan gas level.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%LEL",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "40004",
   "name": "Sensor life",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "40005",
   "name": "Sensor faults",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Global fault",
    "1": "AutoSpan fault",
    "2": "Temperature fault",
    "5": "Memory fault",
    "6": "Processor fault",
    "7": "Sensor fault",
    "9": "Clearing fault",
    "11": "Range fault",
    "12": "Zero fault",
    "14": "Calibration mode"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "40006",
   "name": "Sensor model",
   "description": "Reads 3 (IR).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "40007",
   "name": "Days since calibration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "days",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "40011",
   "name": "Gas factor",
   "description": "See the gas factor menu in the manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "40014",
   "name": "Range divisor",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "40015",
   "name": "Calibration enable/status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "40016-40021",
   "name": "Gas type/units string",
   "description": "ASCII text set at the factory.",
   "data_type": "STRING",
   "length": 6,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8199,
   "documented": "48199",
   "name": "Battery life",
   "description": "Smart battery life remaining, 0-100.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8200,
   "documented": "48200",
   "name": "Battery life in minutes",
   "description": "Caps at 65535 (about 45.5 days).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8204,
   "documented": "48204",
   "name": "Status",
   "description": "Battery detect and battery fault flags.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "4": "Battery detected",
    "5": "Battery fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8206,
   "documented": "48206",
   "name": "Battery read error count",
   "description": "Write 0 to clear.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set a unique Modbus ID (hex) in the magnet menu, wire RS-485 at 9600 8N1 and poll holding registers 0-7 with function 03.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2,
    "why": "Gas reading %LEL"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Fault bits"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Range"
   },
   {
    "table": "holding_register",
    "address": 4,
    "why": "Sensor life"
   },
   {
    "table": "holding_register",
    "address": 8204,
    "why": "Battery status"
   }
  ],
  "enable": "The manual describes no separate enable step; set the ID with Set Modbus ID (01-FF hex, default 01).",
  "watchdog": null,
  "quirks": [
   "40000 = wire address 0; the battery block sits at 8199-8206.",
   "Bump tests do not change the Modbus gas reading."
  ],
  "setup": [
   "9600 baud, 8 data bits, no parity, 1 stop bit."
  ],
  "gotchas": [
   "Bit 14 of 40005 is set while in calibration mode."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/detcon/cx-ir",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}