 "manufacturer": "DFRobot",
 "manufacturer_slug": "dfrobot",
 "model": "SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)",
 "model_slug": "sen0662",
 "short_model": "SEN0662",
 "aliases": [
  "SEN0662",
  "Gravity BMV080",
  "BMV080 PM2.5 sensor",
  "DFRobot BMV080"
 ],
 "equipment_type": "Sensor (particulate matter)",
 "applies_to": "DFRobot SEN0662 Gravity BMV080 module with its DIP switch set to UART, firmware V1.0.0 / register map version 4, per the DFRobot wiki register page.",
 "summary": "The SEN0662 is a maker-grade particulate sensor board built on the Bosch BMV080. With its DIP switch on the UART side it acts as a Modbus RTU slave. Input registers give PM1.0, PM2.5 and PM10 as big-endian floats plus status; holding registers set the address, serial format and measurement mode and start or stop measurement.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 87,
  "baud": 9600,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "hex 0-based",
  "note": "Registers are listed as hex protocol addresses from 0x0000 and sent unchanged; the wiki's example reads PM1.0 with start address 0x0006 on function 04."
 },
 "default_word_order": "ABCD",
 "firmware": "V1.0.0 (0x1000), register map version 0x0004",
 "source": {
  "title": "Gravity: BMV080 PM2.5 Air Quality Sensor - Modbus Register Definitions (SEN0662 wiki)",
  "doc_number": null,
  "revision_date": null,
  "url": "https://wiki.dfrobot.com/sen0662/docs/25056",
  "pages": "Register table at the top; function and exception codes; read example (57 04 00 06 00 06)"
 },
 "notes": [
  "Word order: the wiki says registers are big-endian and the high word comes first, and its example response 40 E0 00 00 decodes to 7.0 ug/m3, so floats are ABCD.",
  "The default slave address is 0x57 (decimal 87). The board's I2C address pins do not affect it.",
  "The sensor does not measure after power-up: write 1 to holding register 0x0003 after every power cycle before reading PM values.",
  "The Integration Time float has no unit printed in the table; it is listed without a unit.",
  "The wiki also documents a broadcast read of holding register 0x0000 (address scan) that only works with a single device on the bus; it is a vendor extension, not standard Modbus."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "0x0000",
   "name": "Product ID (PIDR)",
   "description": "Reads 0x0296 for this module.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "0x0001",
   "name": "Vendor ID (VIDR)",
   "description": "Reads 0x3343 (DFRobot).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "0x0002",
   "name": "Firmware Version",
   "description": "0x1000 = V1.0.0.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "0x0003",
   "name": "Register Map Version",
   "description": "Default 0x0004.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "0x0004",
   "name": "Operating Status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Booting",
    "1": "Ready, waiting for measurement",
    "2": "Continuous measurement running",
    "3": "Duty-cycle measurement running",
    "4": "Stopped",
    "5": "Error"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "0x0005",
   "name": "Last Status Code",
   "description": "Result of the last BMV080 SDK call; 0 = success.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "0x0006",
   "name": "PM1.0",
   "description": "Mass concentration, IEEE 754 float, high word first.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "µg/m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "0x0008",
   "name": "PM2.5",
   "description": "Mass concentration, IEEE 754 float, high word first.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "µg/m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "0x000A",
   "name": "PM10",
   "description": "Mass concentration, IEEE 754 float, high word first.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "µg/m³",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "0x000C",
   "name": "Operating Duration",
   "description": "Float, high word first.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "0x000E",
   "name": "Status Flags",
   "description": "Status bits; bits 10-15 reserved.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Sensor blockage",
    "1": "PM2.5 out of range",
    "2": "New PM data ready (cleared once data, flags and counter are read)",
    "3": "Sensor initialisation complete",
    "4": "Measurement in progress",
    "5": "Parameter change pending",
    "6": "Parameters validated",
    "7": "Parameters being applied",
    "8": "Reserved (always 0 with float map)",
    "9": "A float input was NaN/Inf and was written as 0"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 15,
   "documented": "0x000F",
   "name": "Sample Counter",
   "description": "Increments per sample; wraps after 65535.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "0x0010",
   "name": "SDK Major Version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 17,
   "documented": "0x0011",
   "name": "SDK Minor Version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "0x0012",
   "name": "SDK Patch Version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 19,
   "documented": "0x0013",
   "name": "Sensor Unique ID",
   "description": "12 ASCII characters across 6 registers, high byte first.",
   "data_type": "STRING",
   "length": 6,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0x0000",
   "name": "RTU Slave Address",
   "description": "1-247, default 0x57; stored in non-volatile memory.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "0x0001",
   "name": "Baud Rate",
   "description": "Stored; applies after reboot.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "2400",
    "2": "4800",
    "3": "9600",
    "4": "14400",
    "5": "19200",
    "6": "38400",
    "7": "57600",
    "8": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0x0002",
   "name": "Parity & Stop Bit Configuration",
   "description": "High byte parity: 0 none, 1 even, 2 odd. Low byte stop bits: 1=1, 2=1.5, 3=2.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "0x0003",
   "name": "Operation Command",
   "description": "Reads back 0. Not stored.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "W",
   "values": {
    "1": "Start measurement",
    "2": "Stop measurement",
    "3": "Restore default configuration"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0x0004",
   "name": "Measurement Mode",
   "description": "Send a start command after changing.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Continuous",
    "1": "Duty cycle"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0x0005",
   "name": "Measurement Algorithm",
   "description": "Duty-cycle mode forces Fast Response.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Fast Response",
    "2": "Balanced",
    "3": "High Precision"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "0x0006",
   "name": "Blockage Detection Switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "0x0007",
   "name": "Vibration Filter Switch",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "0x0008",
   "name": "Integration Time",
   "description": "Float, high word first; default 10.0.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "0x000A",
   "name": "Duty-Cycle Period",
   "description": "Integration time plus sleep time; default 30.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "At 9600 8N1, address 0x57: write 0x0001 to holding register 0x0003 to start measuring, then read six input registers from 0x0006 with function 04 for PM1.0, PM2.5 and PM10 as big-endian floats in ug/m3.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 3,
    "why": "Start measurement command"
   },
   {
    "table": "input_register",
    "address": 6,
    "why": "PM1.0"
   },
   {
    "table": "input_register",
    "address": 8,
    "why": "PM2.5"
   },
   {
    "table": "input_register",
    "address": 10,
    "why": "PM10"
   },
   {
    "table": "input_register",
    "address": 14,
    "why": "Status flags"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "Operating status"
   }
  ],
  "enable": "Set the module's DIP switch to the UART side; Modbus RTU is then active at the stored address and baud rate.",
  "watchdog": null,
  "quirks": [
   "Measurement must be started after every power cycle.",
   "Baud and parity changes take effect after a reboot.",
   "Changing the algorithm restarts measurement; blockage and vibration settings are re-applied when changed. After changing the measurement mode, send a start command."
  ],
  "setup": [
   "Defaults: 9600 baud, 8 data bits, no parity, 1 stop bit, address 0x57.",
   "The wiki wiring example connects the board R/T pins to a UART adapter (RainbowLink V2)."
  ],
  "gotchas": [
   "If a PM value reads 0 or NaN, check bit 9 of status flags (0x000E).",
   "Full-scale PM range is 1000 ug/m3; bit 1 of status flags flags PM2.5 out of range."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/dfrobot/sen0662",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}