 "manufacturer": "DriSteem",
 "manufacturer_slug": "dristeem",
 "model": "Vapor-logic 6 humidifier controller (Modbus RTU)",
 "model_slug": "vapor-logic-6",
 "short_model": "Vapor-logic 6",
 "aliases": [
  "Vapor-logic",
  "Vapor-logic version 6",
  "VL6",
  "DriSteem GTS",
  "DriSteem XT",
  "DriSteem STS",
  "DriSteem LTS",
  "Vaporstream"
 ],
 "equipment_type": "Air handler humidifier (steam humidifier controller)",
 "applies_to": "DriSteem humidifiers and humidification systems controlled by Vapor-logic firmware 6.X.X, per IOM form VL6-IOM-EN-REVH-0225.",
 "summary": "Vapor-logic 6 is the DriSteem controller used on its steam humidifiers (electric, GTS gas, XT electrode, STS/LTS steam-to-steam), HPS/LMH high-pressure systems and WM wetted-media units. Modbus RTU is standard on terminal P7. The map gives 16-bit input registers for humidity, dew point, demand, output and temperatures, holding registers for run mode, set points, fieldbus demand and PID, discrete inputs for safety switches, and coils for every alarm and message flag.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 99,
  "baud": 9600,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The table prints each point twice, e.g. IR-1 / 30001, HR-1 / 40001, DI-1 / 10001 and coil DV-1 / 1. These are one-based Modicon numbers: input register 30001 is wire address 0 and coil 1 is wire address 0."
 },
 "default_word_order": null,
 "firmware": "Vapor-logic 6.X.X",
 "source": {
  "title": "Vapor-logic Version 6 Installation, Operation, and Maintenance Manual",
  "doc_number": "VL6-IOM-EN-REVH-0225 (Part No. 890000-741 Rev H)",
  "revision_date": "2025-02",
  "url": "https://d2tsmyh31fn7w8.cloudfront.net/public-documents/docs/iom/vapor-logic/VL6-IOM-EN.pdf",
  "pages": "p. 35 (Table 30-1 communications setup), p. 74 (connections), pp. 75-83 (Tables 75-1 to 83-1, interoperability variables)"
 },
 "notes": [
  "The PDF sits on the CloudFront host that holds DriSteem public documents (path public-documents/docs/iom/vapor-logic); the document itself is the DriSteem IOM (Research Products Corporation copyright).",
  "Note 1 of the table says all input and holding registers are 16-bit and all discrete inputs and coils single bits; no scale factor is printed, so values are whole numbers in the units shown, except WaterUntilADS / WaterUntilService where the table gives 100 lbs (or kg) per Modbus count.",
  "Units follow the controller's I-P or SI setting (°F/°C, lbs/hr / kg/h, psi/bar). Temperatures are typed INT16 because the ranges go below zero; the manual does not state signedness.",
  "Mass values (steam demand/output, up to 100,000) are listed as single 16-bit registers in the source; readings above 65,535 cannot be represented.",
  "WaterUntilADS and WaterUntilService are input registers but the table marks them RW; input registers cannot be written over Modbus, so they are listed read-only here.",
  "RunMode (40001) and MTRunMode (40014) have separate read and write meanings; reads of RunMode can also return 5 (Test outputs) and 6 (Test run).",
  "Many points apply only to one product family, marked in brackets: GTS (gas), XT (electrode), HPS/LMH (high-pressure), WM (wetted media), XV/STS (steam-to-steam). Shared numbers carry different meanings per family.",
  "Alarm and message coils are marked RW in the source; alarm meanings are in the manual's Alarms menu tables (pp. 49-50) and messages in the Diagnostics menu table (p. 46).",
  "Serial framing (parity, data and stop bits) is not stated in the manual.",
  "Note 1 of the table gives DI1-DI7 and DV1-DV69 as the ranges, but the table itself also lists DI-8 to DI-17 and DV-70; those rows are included as printed."
 ],
 "registers": [
  {
   "table": "coil",
   "address": 0,
   "documented": "DV-1 / 1",
   "name": "ProgOutput1StatusNO-1",
   "description": "Programmable dry contact 1 state (0 open, 1 closed).",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 1,
   "documented": "DV-2 / 2",
   "name": "ProgOutput2StatusNO-2",
   "description": "Programmable dry contact 2 state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 2,
   "documented": "DV-3 / 3",
   "name": "ActiveManualClearAlarmsExist",
   "description": "Set when an alarm needing manual clear exists.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 3,
   "documented": "DV-4 / 4",
   "name": "ClearAllActiveAlarms",
   "description": "Write 1 to clear all active faults.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 4,
   "documented": "DV-5 / 5",
   "name": "TankTempSensorFailed / WaterTempSensorFailed (HPS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 5,
   "documented": "DV-6 / 6",
   "name": "TankOvertemp-UnitRebootRequired",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 6,
   "documented": "DV-7 / 7",
   "name": "SignalAtRHInputOutOfRange",
   "description": "Alarm: RH, dew point or demand signal out of range.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 7,
   "documented": "DV-8 / 8",
   "name": "DuctRHSignalOutOfRange",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 8,
   "documented": "DV-9 / 9",
   "name": "AuxTempSenseOutOfRange",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 9,
   "documented": "DV-10 / 10",
   "name": "WaterProbeMiswired",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 10,
   "documented": "DV-11 / 11",
   "name": "FaultyWaterProbe / VFDFault (HPS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 11,
   "documented": "DV-12 / 12",
   "name": "ExcessiveFillTime",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 12,
   "documented": "DV-13 / 13",
   "name": "ExcessiveRefillTime",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 13,
   "documented": "DV-14 / 14",
   "name": "TankNotDraining / CheckHumidifierFloats (LMH)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 14,
   "documented": "DV-15 / 15",
   "name": "ExcessiveBoilTime-UnitRebootRequired",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 15,
   "documented": "DV-16 / 16",
   "name": "NoSDUAirflow",
   "description": "Alarm: no airflow at the dispersion unit.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 16,
   "documented": "DV-17 / 17",
   "name": "NoPowerVentAirflow (GTS) / XVHeaderFlooded (STS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 17,
   "documented": "DV-18 / 18",
   "name": "NoCombustionAirflow (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 18,
   "documented": "DV-19 / 19",
   "name": "BlockedFlue (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 19,
   "documented": "DV-20 / 20",
   "name": "Burner1Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 20,
   "documented": "DV-21 / 21",
   "name": "Burner2Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 21,
   "documented": "DV-22 / 22",
   "name": "Burner3Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 22,
   "documented": "DV-23 / 23",
   "name": "Burner4Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 23,
   "documented": "DV-24 / 24",
   "name": "IgnitionModule1Fault (GTS) / Stage1EfficiencyBelow50Percent (WM)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 24,
   "documented": "DV-25 / 25",
   "name": "IgnitionModule2Fault (GTS) / Stage2EfficiencyBelow50Percent (WM)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 25,
   "documented": "DV-26 / 26",
   "name": "IgnitionModule3Fault (GTS) / Stage3EfficiencyBelow50Percent (WM)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 26,
   "documented": "DV-27 / 27",
   "name": "IgnitionModule4Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 27,
   "documented": "DV-28 / 28",
   "name": "Blower1Fault (GTS) / TempSensorStage1Fault (WM)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 28,
   "documented": "DV-29 / 29",
   "name": "Blower2Fault (GTS) / TempSensorStage2Fault (WM)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 29,
   "documented": "DV-30 / 30",
   "name": "Blower3Fault (GTS) / TempSensorStage3Fault (WM)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 30,
   "documented": "DV-31 / 31",
   "name": "Blower4Fault (GTS) / TempSensorFault (WM)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 31,
   "documented": "DV-32 / 32",
   "name": "GasValve1Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 32,
   "documented": "DV-33 / 33",
   "name": "GasValve2Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 33,
   "documented": "DV-34 / 34",
   "name": "GasValve3Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 34,
   "documented": "DV-35 / 35",
   "name": "GasValve4Fault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 35,
   "documented": "DV-36 / 36",
   "name": "LowWaterOrOvertemp (GTS) / OvertempCutoutUnitRebootRequired (Electric, LMH)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 36,
   "documented": "DV-37 / 37",
   "name": "ExcessiveFoaming2 (XT) / LowInletPressure (HPS, LMH) / ReplaceIgnitorsNow (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 37,
   "documented": "DV-38 / 38",
   "name": "ReplaceIgnitorsSoon (GTS) / ReplaceContactors (Electric, LMH) / ReplaceUVLamp (WM)",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 38,
   "documented": "DV-39 / 39",
   "name": "ServiceUnit",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 39,
   "documented": "DV-40 / 40",
   "name": "DrainPending",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 40,
   "documented": "DV-41 / 41",
   "name": "NoAirflow",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 41,
   "documented": "DV-42 / 42",
   "name": "InterlockOpen",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 42,
   "documented": "DV-43 / 43",
   "name": "FreezeDrain",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 43,
   "documented": "DV-44 / 44",
   "name": "EndOfSeasonDrainActive",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 44,
   "documented": "DV-45 / 45",
   "name": "TempCompOn",
   "description": "Message: temperature compensation on.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 45,
   "documented": "DV-46 / 46",
   "name": "CleanProbes",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 46,
   "documented": "DV-47 / 47",
   "name": "DuctHLTrip",
   "description": "Message: duct high limit tripped.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 47,
   "documented": "DV-48 / 48",
   "name": "DuctHLSpan",
   "description": "Message: within duct high limit span.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 48,
   "documented": "DV-49 / 49",
   "name": "InsufficientWaterFlow",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 49,
   "documented": "DV-50 / 50",
   "name": "BoilingTempCalibrated",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 50,
   "documented": "DV-51 / 51",
   "name": "CurrentSensorOutOfRange (XT)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 51,
   "documented": "DV-52 / 52",
   "name": "CurrentSensorOutOfRange (XT) / ROSensorOutOfRange (HPS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 52,
   "documented": "DV-53 / 53",
   "name": "Overcurrent (XT) / HighInletPressure (HPS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 53,
   "documented": "DV-54 / 54",
   "name": "SupplyWaterFailure (XT) / LowInletWaterTemp (HPS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 54,
   "documented": "DV-55 / 55",
   "name": "ExcessiveFoaming (XT) / HighPumpPressure (HPS) / FoamingFault (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 55,
   "documented": "DV-56 / 56",
   "name": "CheckCylinderEndOfLife (XT) / LowInletWaterTempMessage (HPS)",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 56,
   "documented": "DV-57 / 57",
   "name": "Overcurrent2 (XT) / HighInletWaterTemp (HPS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 57,
   "documented": "DV-58 / 58",
   "name": "SupplyWater2Failure (XT) / LowPumpPressure (HPS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 58,
   "documented": "DV-59 / 59",
   "name": "CheckCylinder2EndOfLife (XT)",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 59,
   "documented": "DV-60 / 60",
   "name": "MainEnableOpen",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 60,
   "documented": "DV-61 / 61",
   "name": "LowInletPressure (LMH)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 61,
   "documented": "DV-62 / 62",
   "name": "HighOutletPressure (LMH)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 62,
   "documented": "DV-63 / 63",
   "name": "InletSensorOutOfRange (HPS) / StorageSensorOutOfRange (LMH) / FlueSensorOutOfRange (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 63,
   "documented": "DV-64 / 64",
   "name": "ExcessiveTDSAlarm (LMH)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 64,
   "documented": "Dv-65 / 65",
   "name": "ExcessiveTDSDuringFill (LMH)",
   "description": "Message flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 65,
   "documented": "DV-66 / 66",
   "name": "PumpStationCannotRun (HPS)",
   "description": "Alarm: HPS redundant system cannot run.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 66,
   "documented": "DV-67 / 67",
   "name": "XVClearingCondensate (XV)",
   "description": "XV is trying to clear condensate from the header.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 67,
   "documented": "DV-68 / 68",
   "name": "XVCondensateClearingFailure (XV)",
   "description": "Alarm: XV failed to clear header condensate.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 68,
   "documented": "DV-69 / 69",
   "name": "XV2PositionValveFailure (XV)",
   "description": "Alarm: end switch did not close while valve powered.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "coil",
   "address": 69,
   "documented": "DV-70 / 70",
   "name": "PumpSensorOutOfRange (HPS) / InletSensorOutOfRange (LMH) / DrainSensorOutOfRange (GTS)",
   "description": "Alarm flag.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 0,
   "documented": "DI-1 / 10001",
   "name": "AirflowProvingSwitch",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 1,
   "documented": "DI-2 / 10002",
   "name": "DuctHLSwitch",
   "description": "Duct high limit switch.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 2,
   "documented": "DI-3 / 10003",
   "name": "SafetyInterlock",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 3,
   "documented": "DI-4 / 10004",
   "name": "CombustionAirDamper (GTS) / Stage1Active (HPS)",
   "description": "GTS: 0 damper closed, 1 open. HPS: stage 1 active.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 4,
   "documented": "DI-5 / 10005",
   "name": "FluePressureSwitch (GTS) / Stage2Active (HPS) / InletPressureSwitch (LMH)",
   "description": "GTS and LMH: 0 open, 1 closed. HPS: 0 closed, 1 open.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 5,
   "documented": "DI-6 / 10006",
   "name": "PowerVentSwitch (GTS) / Stage3Active (HPS) / XVHeaderEmptyOrExternalDemand (STS)",
   "description": "GTS 0 off 1 on; HPS 0 closed 1 open; STS 0 not ready 1 ready.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 6,
   "documented": "DI-7 / 10007",
   "name": "LowWaterSensorOrOvertempLoop (GTS)",
   "description": "",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No water",
    "1": "Water"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 7,
   "documented": "DI-8 / 10008",
   "name": "FillValve",
   "description": "Fill valve state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Closed",
    "1": "Open"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 8,
   "documented": "DI-9 / 10009",
   "name": "DrainValve",
   "description": "Drain valve state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not draining",
    "1": "Draining"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 9,
   "documented": "DI-10 / 10010",
   "name": "MTActiveFaultInSystem",
   "description": "Multi-tank only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 10,
   "documented": "DI-11 / 10011",
   "name": "MTActiveMessageInSystem",
   "description": "Multi-tank only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No",
    "1": "Yes"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 11,
   "documented": "DI-12 / 10012",
   "name": "HighWaterSensor (XT)",
   "description": "XT systems only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No water",
    "1": "Water"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 12,
   "documented": "DI-13 / 10013",
   "name": "HighWaterSensor2 (XT)",
   "description": "Right cylinder, two-cylinder XT only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No water",
    "1": "Water"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 13,
   "documented": "DI-14 / 10014",
   "name": "HPASVFDDriveFault (HPS)",
   "description": "HPS systems only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "No fault",
    "1": "Fault"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 14,
   "documented": "DI-15 / 10015",
   "name": "XV 2 position shutoff valve",
   "description": "XV shutoff valve power state.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Valve not powered",
    "1": "Valve powered"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 15,
   "documented": "DI-16 / 10016",
   "name": "XV2PositionValveEndSwitch (XV)",
   "description": "XV with Vapor-logic only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Open",
    "1": "Closed"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "discrete_input",
   "address": 16,
   "documented": "DI-17 / 10017",
   "name": "XVFloatSwitch (XV)",
   "description": "XV with Vapor-logic only.",
   "data_type": "BIT",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Empty, OK to run",
    "1": "Full"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 0,
   "documented": "IR-1 / 30001",
   "name": "SpaceRH",
   "description": "Space relative humidity.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 1,
   "documented": "IR-2 / 30002",
   "name": "SpaceDewPoint",
   "description": "Space dew point; °F or °C per unit setting.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "IR-3 / 30003",
   "name": "DuctRH",
   "description": "Duct relative humidity.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 3,
   "documented": "IR-4 / 30004",
   "name": "SteamDemandMass",
   "description": "Steam demand, lbs/hr or kg/h per unit setting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "lbs/hr / kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "IR-5 / 30005",
   "name": "SteamDemandPercent",
   "description": "Steam demand as % of total capacity.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 5,
   "documented": "IR-6 / 30006",
   "name": "AuxTemp",
   "description": "Auxiliary temperature sensor.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "IR-7 / 30007",
   "name": "TankTemperature / WaterTemperature (HPS)",
   "description": "Evaporating-chamber water temperature; inlet water temperature on HPS.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 7,
   "documented": "IR-8 / 30008",
   "name": "SteamOutputMass",
   "description": "Estimated steam output, lbs/hr or kg/h.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "lbs/hr / kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "IR-9 / 30009",
   "name": "SteamOutputPercent",
   "description": "Estimated steam output as % of capacity.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 9,
   "documented": "IR-10 / 30010",
   "name": "WaterUntilADS",
   "description": "Water left before next auto drain sequence; one count = 100 lbs or 100 kg.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 100,
   "units": "lbs / kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "IR-11 / 30011",
   "name": "WaterUntilService",
   "description": "Water left before next service cycle; one count = 100 lbs or 100 kg.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 100,
   "units": "lbs / kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 22,
   "documented": "IR-23 / 30023",
   "name": "MTSteamDemandMass",
   "description": "Multi-tank system steam demand.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "lbs/hr / kg/h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 24,
   "documented": "IR-25 / 30025",
   "name": "MTSteamDemandPercent",
   "description": "Multi-tank system steam demand.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 25,
   "documented": "IR-26 / 30026",
   "name": "XTBottle1Current (XT)",
   "description": "XT operating current, left cylinder.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 26,
   "documented": "IR-27 / 30027",
   "name": "XTBottle2Current (XT)",
   "description": "XT operating current, right cylinder.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 27,
   "documented": "IR-28 / 30028",
   "name": "InPressure (HPS)",
   "description": "Supply water pressure.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "psi / bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 28,
   "documented": "IR-29 / 30029",
   "name": "OutPressure (HPS)",
   "description": "Output pressure.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "psi / bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 29,
   "documented": "IR-30 / 30030",
   "name": "CurrentTankCOC (WM)",
   "description": "Current tank cycles of concentration.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 30,
   "documented": "IR-31 / 30031",
   "name": "SupplyWaterConductivity (WM)",
   "description": "Supply water conductivity.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "µS",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 31,
   "documented": "IR-32 / 30032",
   "name": "Stage1Temperature (WM)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 32,
   "documented": "IR-33 / 30033",
   "name": "Stage2Temperature (WM)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 33,
   "documented": "IR-34 / 30034",
   "name": "Stage3Temperature (WM) / FlueTemperature (GTS)",
   "description": "WM stage 3 temperature; GTS flue box temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 34,
   "documented": "IR-35 / 30035",
   "name": "SupplyAirTemperature (WM) / DrainTemperature (GTS)",
   "description": "WM supply air; GTS drain block water temperature.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 35,
   "documented": "IR-36 / 30036",
   "name": "Stage1MediaEffectiveness (WM)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 36,
   "documented": "IR-37 / 30037",
   "name": "Stage2MediaEffectiveness (WM)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 37,
   "documented": "IR-38 / 30038",
   "name": "Stage3MediaEffectiveness (WM)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 38,
   "documented": "IR-39 / 30039",
   "name": "OutputTemperature (WM)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 39,
   "documented": "IR-40 / 30040",
   "name": "WetbulbTemperature (WM)",
   "description": "",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 40,
   "documented": "IR-41 / 30041",
   "name": "StoragePressure (LMH)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "psi / bar",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 41,
   "documented": "IR-42 / 30042",
   "name": "PumpRuntimeHours (HPS, LMH)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 42,
   "documented": "IR-43 / 30043",
   "name": "TDS (LMH)",
   "description": "Total dissolved solids reading.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 43,
   "documented": "IR-44 / 30044",
   "name": "HPASActivePumpStationNumber (HPS)",
   "description": "Active pump station, 0-4.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "HR-1 / 40001",
   "name": "RunMode",
   "description": "Unit mode. Write 1-4; reads can also return 5 or 6.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Auto",
    "2": "Local standby",
    "3": "System standby",
    "4": "Manual drain",
    "5": "Test outputs (read only)",
    "6": "Test run (read only)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "HR-2 / 40002",
   "name": "SpaceRHSetPoint",
   "description": "Space humidity set point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "HR-3 / 40003",
   "name": "SpaceDewPointSetPoint",
   "description": "Space dew point set point.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°F / °C",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "HR-4 / 40004",
   "name": "DuctHighLimitSetPoint",
   "description": "Duct high limit set point.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "HR-5 / 40005",
   "name": "FieldbusDemandMass",
   "description": "Steam demand sent over the fieldbus; above capacity runs at 100%.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "lbs/hr / kg/h",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "HR-6 / 40006",
   "name": "FieldbusDemandPcnt",
   "description": "Steam demand over the fieldbus as % of capacity.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "W",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "HR-7 / 40007",
   "name": "PIDBand",
   "description": "PID band.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "HR-8 / 40008",
   "name": "PIDKp",
   "description": "Proportional gain.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "HR-9 / 40009",
   "name": "PIDKi",
   "description": "Integral gain.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "HR-10 / 40010",
   "name": "PIDKd",
   "description": "Derivative gain.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 13,
   "documented": "HR-14 / 40014",
   "name": "MTRunMode",
   "description": "Multi-tank system run mode.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "System standby",
    "2": "System auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "HR-15 / 40015",
   "name": "MTSteamOutputReqMass",
   "description": "Multi-tank fieldbus steam request.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "lbs/hr / kg/h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "HR-17 / 40017",
   "name": "MTSteamOutputReqPcnt",
   "description": "Multi-tank fieldbus steam request, % of system capacity.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 17,
   "documented": "HR-18 / 40018",
   "name": "Pump1RuntimeHours (HPS, LMH)",
   "description": "Pump 1 hours since reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 18,
   "documented": "HR-19 / 40019",
   "name": "Pump2RuntimeHours (HPS)",
   "description": "Pump 2 hours since reset.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 19,
   "documented": "HR-20 / 40020",
   "name": "TargetCOC (WM)",
   "description": "Desired cycles of concentration.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 20,
   "documented": "HR-21 / 40021",
   "name": "HPASPumpSelected (HPS)",
   "description": "Selected pump, HPS systems.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Pump 1",
    "1": "Pump 2"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Enable Modbus in the Communications setup, wire RS-485 to P7, and poll input registers 0-10 for humidity, demand and output. To command the unit, set Control via Modbus and write RunMode (40001) and either a set point (40002) or fieldbus demand (40006).",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Space RH"
   },
   {
    "table": "input_register",
    "address": 8,
    "why": "Steam output %"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "Steam demand %"
   },
   {
    "table": "holding_register",
    "address": 0,
    "why": "Run mode"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Space RH set point"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Fieldbus demand %"
   },
   {
    "table": "coil",
    "address": 2,
    "why": "Manual-clear alarm exists"
   },
   {
    "table": "coil",
    "address": 3,
    "why": "Clear all alarms"
   }
  ],
  "enable": "Setup menu > Communications > Modbus: Modbus enabled = Yes, set address (default 99) and baud rate (default 9600). For demand over Modbus, Setup > Demand signal > Control via Modbus = Yes.",
  "watchdog": null,
  "quirks": [
   "Printed numbers are Modicon-style (30001, 40001, 10001, coil 1): subtract one for the wire address.",
   "Units switch between I-P and SI with the unit setting; there are no decimal places."
  ],
  "setup": [
   "Connect RS-485 to terminal P7 on the Vapor-logic board (+ to +, - to -).",
   "Set the Modbus address and baud rate in Setup > Communications, then cycle power."
  ],
  "gotchas": [
   "Several point numbers mean different things on GTS, XT, HPS, LMH and WM units; check which family you have.",
   "Numbers are not continuous (no IR 12-22 or 24, no HR 11-13 or 16); DV-65, DV-67, DI-8, DI-9 and DI-15 are on the last table page."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/dristeem/vapor-logic-6",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}