 "manufacturer": "Dwyer",
 "manufacturer_slug": "dwyer",
 "model": "Series RHPX communicating humidity/temperature transmitter",
 "model_slug": "rhpx",
 "short_model": "RHPX",
 "aliases": [
  "RHPX",
  "Dwyer RHPX BACnet/Modbus",
  "607xxx"
 ],
 "equipment_type": "Sensor (humidity / temperature transmitter)",
 "applies_to": "Dwyer Series RHPX humidity and temperature transmitters with the BACnet MS/TP / Modbus RTU communication board, set to Modbus with DIP switch 9 (bulletin AQ-RHPX-C).",
 "summary": "The Dwyer RHPX is a duct or wall humidity and temperature transmitter that talks BACnet MS/TP or Modbus RTU on RS-485, chosen by DIP switch. Measurements are 32-bit floats in input registers: relative humidity, dew point, enthalpy and absolute humidity in two unit sets, and temperature. Offsets and display units are holding registers. This map covers every published register.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 127,
  "baud": null,
  "parity": null,
  "data_bits": 8,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Tables list register numbers starting at 0001 and state that the register address is one less than the register number, so 0001-0002 (relative humidity) is read at address 0. Float registers 1-2000 are big-endian; the same values can be read with other byte orders by adding 2000 (byte swap), 4000 (word swap) or 6000 (little-endian)."
 },
 "default_word_order": "ABCD",
 "firmware": null,
 "source": {
  "title": "Series RHPX Humidity/Temperature Communicating Transmitter - Specifications, Installation and Operating Instructions",
  "doc_number": "Bulletin AQ-RHPX-C",
  "revision_date": "2024-03",
  "url": "https://assets.dwyeromega.com/manuals-do/AQ_RHPX_C.pdf",
  "pages": "p. 4 (DIP switches, baud rates, function codes, input and holding register tables, error flags), p. 5 (multi-address byte-order table)"
 },
 "notes": [
  "Byte order: addresses 1-2000 use big-endian order (ABCD for floats). Adding 2000 gives byte-swapped (BADC), 4000 word-swapped (CDAB) and 6000 little-endian (DCBA) copies; the info registers (8001+) exist only big-endian.",
  "Strings are read as a stream: first character in the high byte of the first register; unused bytes are zero.",
  "Holding register 0007-0023 Device name (String(32), default 'RHPX') is left out: the printed range spans 17 registers while a 32-character string needs 16.",
  "Supported functions: 03 (read holding), 04 (read input), 06 and 16.",
  "Default address 127 comes from the default DIP setting (switches 1-7 on). Baud, parity and stop bits are detected automatically ('Intelligent Serial Configuration'); supported: 9600-115200 baud, even/odd/none, 1 or 2 stop bits."
 ],
 "registers": [
  {
   "table": "input_register",
   "address": 0,
   "documented": "0001-0002",
   "name": "Relative humidity",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 2,
   "documented": "0003-0004",
   "name": "Dew point (°F)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 4,
   "documented": "0005-0006",
   "name": "Dew point (°C)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 6,
   "documented": "0007-0008",
   "name": "Enthalpy (BTU/lb)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "BTU/lb",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8,
   "documented": "0009-0010",
   "name": "Enthalpy (kJ/kg)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "kJ/kg",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 10,
   "documented": "0011-0012",
   "name": "Absolute humidity (g/m3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "g/m3",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 12,
   "documented": "0013-0014",
   "name": "Absolute humidity (lb/million ft3)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "lb/MMCF",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 14,
   "documented": "0015-0016",
   "name": "Temperature (°F)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°F",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 16,
   "documented": "0017-0018",
   "name": "Temperature (°C)",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 18,
   "documented": "0019-0020",
   "name": "Error flags",
   "description": "Bit-coded errors (bits 0-7 used).",
   "data_type": "UINT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Invalid address",
    "1": "Sensor range exceeded",
    "2": "Sensor error",
    "3": "No sensor",
    "4": "User settings invalid",
    "5": "Factory settings invalid",
    "6": "External memory failure",
    "7": "Internal memory failure"
   },
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8000,
   "documented": "8001-8016",
   "name": "Model number",
   "description": "ASCII, 32 characters, e.g. 'RHPX-XXX'.",
   "data_type": "STRING",
   "length": 16,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8016,
   "documented": "8017-8020",
   "name": "Serial number",
   "description": "ASCII, 8 characters.",
   "data_type": "STRING",
   "length": 4,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8020,
   "documented": "8021-8028",
   "name": "Firmware version",
   "description": "ASCII, 16 characters.",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "input_register",
   "address": 8028,
   "documented": "8029-8032",
   "name": "Date code",
   "description": "ASCII, 8 characters.",
   "data_type": "STRING",
   "length": 4,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 0,
   "documented": "0001-0002",
   "name": "Humidity offset",
   "description": "-3.5 to +3.5 %RH.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "%RH",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "0003-0004",
   "name": "Temperature offset",
   "description": "-5.0 to +5.0 °F.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "ABCD",
   "scale": 1,
   "units": "°F",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "0005",
   "name": "Humidity display unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Dew point (°F)",
    "1": "Dew point (°C)",
    "2": "Relative humidity (%RH)",
    "3": "Enthalpy (BTU/lb)",
    "4": "Enthalpy (lb/million ft3)",
    "5": "Absolute humidity (kJ/kg)",
    "6": "Absolute humidity (g/m3)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "0006",
   "name": "Temperature display unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°F",
    "1": "°C"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Set the address with DIP switches 1-8 and switch 9 to Modbus, power up and let the transmitter auto-detect the line settings from the master's traffic, then read input registers 0-17 as big-endian floats.",
  "minimum_registers": [
   {
    "table": "input_register",
    "address": 0,
    "why": "Relative humidity"
   },
   {
    "table": "input_register",
    "address": 16,
    "why": "Temperature °C"
   },
   {
    "table": "input_register",
    "address": 14,
    "why": "Temperature °F"
   },
   {
    "table": "input_register",
    "address": 4,
    "why": "Dew point °C"
   },
   {
    "table": "input_register",
    "address": 18,
    "why": "Error flags"
   }
  ],
  "enable": "DIP switch 9 ON selects Modbus (OFF = BACnet); switches 1-8 set the address bits (128...1), switch 10 enables the 120 ohm terminator. Modbus addresses must be 1-247.",
  "watchdog": null,
  "quirks": [
   "Register address = register number - 1.",
   "Pick the byte order by address range (+2000/+4000/+6000) instead of configuring the master.",
   "The red LED blinks until the transmitter has locked onto the bus settings; if the bus settings change, power-cycle it."
  ],
  "setup": [
   "Terminate the RS-485 line at both ends with 120 ohm (switch 10 on an end device).",
   "If the transmitter is set up offline, send read requests to it so it can detect the baud rate."
  ],
  "gotchas": [
   "The factory DIP setting is address 127; change it before putting several units on one bus."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/dwyer/rhpx",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}