 "manufacturer": "E+E Elektronik",
 "manufacturer_slug": "e-e-elektronik",
 "model": "EE160 humidity and temperature sensor for building automation (RS-485 Modbus RTU)",
 "model_slug": "ee160",
 "short_model": "EE160",
 "aliases": [
  "EE160",
  "EE160-HT6",
  "E+E EE160",
  "EE 160"
 ],
 "equipment_type": "Sensor (humidity / temperature transmitter)",
 "applies_to": "EE160 RH/T room/duct sensor with RS-485 interface in Modbus RTU mode, per user manual BA_EE160 v2.7 (04-2026).",
 "summary": "The EE160 is an HVAC humidity and temperature sensor with an RS-485 Modbus RTU port. It gives temperature and relative humidity as 32-bit floats and as 16-bit integers scaled by 100, plus serial number, firmware version and sensor name.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 245,
  "baud": 9600,
  "parity": "Even",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual prints a decimal register number starting at 1 and a hex register address starting at 0. Send the hex address: temperature is register 26, address 0x19, and the manual's example request reads 0x0019."
 },
 "default_word_order": "CDAB",
 "firmware": null,
 "source": {
  "title": "User Manual EE160 Humidity and Temperature Sensor for Building Automation",
  "doc_number": "BA_EE160 v2.7",
  "revision_date": "2026-04",
  "url": "https://downloads.epluse.com/fileadmin/data/product/ee160/BA_EE160.pdf",
  "pages": "Modbus settings and device-setup registers pp. 16-17 (Tab. 3-4); measured data p. 17 (Tab. 5); example and float decoding pp. 17-18 (Tab. 6-7)"
 },
 "notes": [
  "Float word order: the manual's worked example reads 0x19 and gets 51 F0 41 BA, decoded as IEEE 754 0x41BA51F0 = 23.29 °C. The first register holds the low word, so floats are CDAB.",
  "Metric or US units are fixed by the order code and cannot be changed with PCS10; the unit fields show the metric case.",
  "The integer block uses scale 100 per the manual (2550 = 25.5).",
  "Left out: write-only setup registers 0x00 (Modbus address) and 0x01 (protocol settings); the manual refers to E+E note AN0103 for their coding.",
  "Measured values can be read with function 03 or 04; they are filed here as holding registers."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1 (0x00)",
   "name": "Serial number",
   "description": "ASCII text across 8 registers; read all 8.",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "9 (0x08)",
   "name": "Firmware version",
   "description": "High byte = major release, low byte = minor release.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 9,
   "documented": "10 (0x09)",
   "name": "Sensor name",
   "description": "ASCII text across 8 registers; read all 8.",
   "data_type": "STRING",
   "length": 8,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 25,
   "documented": "26 (0x19)",
   "name": "Temperature T",
   "description": "Float; °F on non-metric order versions.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "28 (0x1B)",
   "name": "Relative humidity RH",
   "description": "Float.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "301 (0x12C)",
   "name": "Temperature T (integer)",
   "description": "Value x100; °F on non-metric order versions.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 301,
   "documented": "302 (0x12D)",
   "name": "Relative humidity RH (integer)",
   "description": "Value x100.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%RH",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Default 9600 baud 8E1, address 245. Read 2 registers at 0x19 for temperature and 2 at 0x1B for humidity (floats, low word first), or 0x12C/0x12D for x100 integers.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 25,
    "why": "Temperature, float"
   },
   {
    "table": "holding_register",
    "address": 27,
    "why": "Relative humidity, float"
   },
   {
    "table": "holding_register",
    "address": 300,
    "why": "Temperature, integer x100"
   },
   {
    "table": "holding_register",
    "address": 301,
    "why": "Relative humidity, integer x100"
   }
  ],
  "enable": "Modbus RTU is the interface. Set address and serial settings with PCS10 and the USB-C configuration stick HA011070; a non-zero DIP-switch address overrides any software-set address.",
  "watchdog": null,
  "quirks": [
   "Floats are low word first (CDAB).",
   "Read both float registers in one request so both halves match.",
   "Serial number and sensor name need all 8 registers read at once."
  ],
  "setup": [
   "Factory settings: 9600 baud, 8 data bits, even parity, 1 stop bit, Modbus address 245.",
   "Selectable: 9600-115200 baud, none/odd/even parity, 1 or 2 stop bits, address 1-247.",
   "All DIP switches at 0 means the address set in PCS10 is used.",
   "A jumper terminates the bus; it is off (not terminated) from the factory."
  ],
  "gotchas": [
   "Default address is 245, not 1.",
   "°C vs °F is an order option, not a setting."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/e-e-elektronik/ee160",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}