Energy meter · Modbus register map

Eastron SDM630MCT Modbus register map

Updated 28 October 2026

Short answer

The SDM630MCT is Eastron's three-phase, CT-connected (1 A / 5 A CT secondary) DIN-rail multifunction meter with an RS485 Modbus RTU port. Every value is a 32-bit IEEE-754 float, high register first: live readings and energy in input registers (function 04) and settings in holding registers (function 03 read, 16 write). This map covers the full input table plus the demand, wiring, RS485, CT/PT ratio, pulse and reset settings.

This page lists 109 Modbus registers for the Eastron SDM630MCT — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eastron’s own free documentation (linked below) and checked against it.

Manufacturer
Eastron
Model
SDM630MCT
Equipment type
Energy meter
Registers
109 (12 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
SDM630 MCT
Source document
Eastron SDM630MCT Smart Meter Modbus Protocol Implementation V1.7 · V1.7
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eastron SDM630MCT

Integration in brief

Use function 04 from 30001 (wire 0) in blocks of up to 60 registers; every value is a big-endian float. Settings are floats in holding registers written with function 16, one parameter per message; system type and CT/PT ratios need the password written to 40025 first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Phase 1 line to neutral voltsFLOAT32 ABCDPhase 1 voltageRead
IR 6Phase 1 currentFLOAT32 ABCDPhase 1 currentRead
IR 52Total system powerFLOAT32 ABCDTotal system powerRead
IR 62Total system power factorFLOAT32 ABCDTotal power factorRead
IR 70Frequency of supply voltagesFLOAT32 ABCDFrequencyRead
IR 72Total import kWhFLOAT32 ABCDTotal import kWhRead
IR 74Total export kWhFLOAT32 ABCDTotal export kWhRead
HR 62CT ratioFLOAT32 ABCDCT ratio checkRead/write

Enable Modbus control & writes

RS485 Modbus RTU is built in on the RS485 versions. Set address, baud rate and parity/stop bits from the front setup menu or holding registers 40021, 40029 and 40019.

Byte order & addressing

Network setup

Watch out for

Eastron SDM630MCT Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

109 of 109 shown
Eastron SDM630MCT Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Phase 1 line to neutral voltsNot available on 3-phase 3-wire.FLOAT32ABCDVRead
IR2doc 30003Phase 2 line to neutral voltsNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDVRead
IR4doc 30005Phase 3 line to neutral voltsNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDVRead
IR6doc 30007Phase 1 currentFLOAT32ABCDARead
IR8doc 30009Phase 2 currentNot available on single-phase.FLOAT32ABCDARead
IR10doc 30011Phase 3 currentNot available on single-phase.FLOAT32ABCDARead
IR12doc 30013Phase 1 active powerNot available on 3-phase 3-wire.FLOAT32ABCDWRead
IR14doc 30015Phase 2 active powerNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDWRead
IR16doc 30017Phase 3 active powerNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDWRead
IR18doc 30019Phase 1 apparent powerNot available on 3-phase 3-wire.FLOAT32ABCDVARead
IR20doc 30021Phase 2 apparent powerNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDVARead
IR22doc 30023Phase 3 apparent powerNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDVARead
IR24doc 30025Phase 1 reactive powerNot available on 3-phase 3-wire.FLOAT32ABCDVArRead
IR26doc 30027Phase 2 reactive powerNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDVArRead
IR28doc 30029Phase 3 reactive powerNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDVArRead
IR30doc 30031Phase 1 power factorSign shows current direction: negative = reverse. Not available on 3-phase 3-wire.FLOAT32ABCDRead
IR32doc 30033Phase 2 power factorNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDRead
IR34doc 30035Phase 3 power factorNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDRead
IR36doc 30037Phase 1 phase angleNot available on 3-phase 3-wire.FLOAT32ABCDDegreesRead
IR38doc 30039Phase 2 phase angleNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDDegreesRead
IR40doc 30041Phase 3 phase angleNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDDegreesRead
IR42doc 30043Average line to neutral voltsNot available on 3-phase 3-wire or single-phase.FLOAT32ABCDVRead
IR46doc 30047Average line currentFLOAT32ABCDARead
IR48doc 30049Sum of line currentsFLOAT32ABCDARead
IR52doc 30053Total system powerFLOAT32ABCDWRead
IR56doc 30057Total system volt ampsFLOAT32ABCDVARead
IR60doc 30061Total system VArFLOAT32ABCDVArRead
IR62doc 30063Total system power factorSign shows current direction: negative = reverse.FLOAT32ABCDRead
IR66doc 30067Total system phase angleFLOAT32ABCDDegreesRead
IR70doc 30071Frequency of supply voltagesFLOAT32ABCDHzRead
IR72doc 30073Total import kWhFLOAT32ABCDkWhRead
IR74doc 30075Total export kWhFLOAT32ABCDkWhRead
IR76doc 30077Total import kVArhFLOAT32ABCDkVArhRead
IR78doc 30079Total export kVArhFLOAT32ABCDkVArhRead
IR80doc 30081Total VAhFLOAT32ABCDkVAhRead
IR82doc 30083AhFLOAT32ABCDAhRead
IR84doc 30085Total system power demandFLOAT32ABCDWRead
IR86doc 30087Maximum total system power demandFLOAT32ABCDWRead
IR100doc 30101Total system VA demandFLOAT32ABCDVARead
IR102doc 30103Maximum total system VA demandFLOAT32ABCDVARead
IR104doc 30105Neutral current demandOnly on 3-phase 4-wire.FLOAT32ABCDARead
IR106doc 30107Maximum neutral current demandOnly on 3-phase 4-wire.FLOAT32ABCDARead
IR108doc 30109Total system reactive power demandNot available on 3-phase 3-wire.FLOAT32ABCDVArRead
IR110doc 30111Maximum total system reactive power demandNot available on 3-phase 3-wire.FLOAT32ABCDVArRead
IR200doc 30201Line 1 to line 2 voltsNot available on single-phase 2-wire.FLOAT32ABCDVRead
IR202doc 30203Line 2 to line 3 voltsNot available on single-phase 2-wire.FLOAT32ABCDVRead
IR204doc 30205Line 3 to line 1 voltsNot available on single-phase 2-wire.FLOAT32ABCDVRead
IR206doc 30207Average line to line voltsNot available on single-phase 2-wire.FLOAT32ABCDVRead
IR224doc 30225Neutral currentOnly on 3-phase 4-wire.FLOAT32ABCDARead
IR234doc 30235Phase 1 L/N volts THDNot available on 3-phase 3-wire.FLOAT32ABCD%Read
IR236doc 30237Phase 2 L/N volts THDNot available on 3-phase 3-wire or single-phase.FLOAT32ABCD%Read
IR238doc 30239Phase 3 L/N volts THDNot available on 3-phase 3-wire or single-phase.FLOAT32ABCD%Read
IR240doc 30241Phase 1 current THDFLOAT32ABCD%Read
IR242doc 30243Phase 2 current THDNot available on single-phase.FLOAT32ABCD%Read
IR244doc 30245Phase 3 current THDNot available on single-phase.FLOAT32ABCD%Read
IR248doc 30249Average line to neutral volts THDNot available on 3-phase 3-wire.FLOAT32ABCD%Read
IR250doc 30251Average line current THDFLOAT32ABCD%Read
IR258doc 30259Phase 1 current demandFLOAT32ABCDARead
IR260doc 30261Phase 2 current demandNot available on single-phase.FLOAT32ABCDARead
IR262doc 30263Phase 3 current demandNot available on single-phase.FLOAT32ABCDARead
IR264doc 30265Maximum phase 1 current demandFLOAT32ABCDARead
IR266doc 30267Maximum phase 2 current demandNot available on single-phase.FLOAT32ABCDARead
IR268doc 30269Maximum phase 3 current demandNot available on single-phase.FLOAT32ABCDARead
IR334doc 30335Line 1 to line 2 volts THDNot available on single-phase 2-wire.FLOAT32ABCD%Read
IR336doc 30337Line 2 to line 3 volts THDNot available on single-phase 2-wire.FLOAT32ABCD%Read
IR338doc 30339Line 3 to line 1 volts THDNot available on single-phase 2-wire.FLOAT32ABCD%Read
IR340doc 30341Average line to line volts THDNot available on single-phase 2-wire.FLOAT32ABCD%Read
IR342doc 30343Total kWhImport plus export.FLOAT32ABCDkWhRead
IR344doc 30345Total kVArhImport plus export.FLOAT32ABCDkVArhRead
IR346doc 30347L1 import kWhFLOAT32ABCDkWhRead
IR348doc 30349L2 import kWhNot available on single-phase.FLOAT32ABCDkWhRead
IR350doc 30351L3 import kWhNot available on single-phase.FLOAT32ABCDkWhRead
IR352doc 30353L1 export kWhFLOAT32ABCDkWhRead
IR354doc 30355L2 export kWhNot available on single-phase.FLOAT32ABCDkWhRead
IR356doc 30357L3 export kWhNot available on single-phase.FLOAT32ABCDkWhRead
IR358doc 30359L1 total kWhFLOAT32ABCDkWhRead
IR360doc 30361L2 total kWhNot available on single-phase.FLOAT32ABCDkWhRead
IR362doc 30363L3 total kWhNot available on single-phase.FLOAT32ABCDkWhRead
IR364doc 30365L1 import kVArhFLOAT32ABCDkVArhRead
IR366doc 30367L2 import kVArhNot available on single-phase.FLOAT32ABCDkVArhRead
IR368doc 30369L3 import kVArhNot available on single-phase.FLOAT32ABCDkVArhRead
IR370doc 30371L1 export kVArhFLOAT32ABCDkVArhRead
IR372doc 30373L2 export kVArhNot available on single-phase.FLOAT32ABCDkVArhRead
IR374doc 30375L3 export kVArhNot available on single-phase.FLOAT32ABCDkVArhRead
IR376doc 30377L1 total kVArhFLOAT32ABCDkVArhRead
IR378doc 30379L2 total kVArhNot available on single-phase.FLOAT32ABCDkVArhRead
IR380doc 30381L3 total kVArhNot available on single-phase.FLOAT32ABCDkVArhRead
IR384doc 30385Resettable total active energyFLOAT32ABCDkWhRead
IR386doc 30387Resettable total reactive energyFLOAT32ABCDkVArhRead
IR388doc 30389Resettable import active energyFLOAT32ABCDkWhRead
IR390doc 30391Resettable export active energyFLOAT32ABCDkWhRead
IR392doc 30393Resettable import reactive energyFLOAT32ABCDkVArhRead
IR394doc 30395Resettable export reactive energyFLOAT32ABCDkVArhRead
HR0doc 40001Demand timeMinutes into the first demand period; demand values are valid once it reaches the period.FLOAT32ABCDminRead
HR2doc 40003Demand period0, 5, 8, 10, 15, 20, 30 or 60 min (default 60); 0 shows live values.FLOAT32ABCDminRead/write
HR10doc 40011System typeNeeds the password (40025) first.FLOAT32ABCDRead/write1 = 1P2W; 2 = 3P3W; 3 = 3P4W
HR12doc 40013Pulse output 1 width60, 100 or 200 ms; default 200.FLOAT32ABCDmsRead/write
HR14doc 40015Password lockFLOAT32ABCDRead0 = Locked; 1 = Unlocked
HR18doc 40019Parity / stop bitsDefault 0.FLOAT32ABCDRead/write0 = 1 stop bit, no parity; 1 = 1 stop bit, even parity; 2 = 1 stop bit, odd parity; 3 = 2 stop bits, no parity
HR20doc 40021Modbus address1-247, default 1.FLOAT32ABCDRead/write
HR22doc 40023Pulse 1 divisorFLOAT32ABCDRead/write1 = 0.01 kWh/imp; 2 = 0.1 kWh/imp; 3 = 1 kWh/imp; 4 = 10 kWh/imp; 5 = 100 kWh/imp; 6 = 1000 kWh/imp
HR24doc 40025PasswordWrite the password to unlock protected settings (default 1000 per the table; see notes).FLOAT32ABCDRead/write
HR28doc 40029Baud rateDefault 2 (9600).FLOAT32ABCDRead/write0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400
HR62doc 40063CT ratioPrimary / secondary current, 1-2000. Needs the password; non-MID meters only.FLOAT32ABCDRead/write
HR64doc 40065PT ratioPrimary / secondary voltage, 1-2000. Needs the password; non-MID meters only.FLOAT32ABCDRead/write
HR86doc 40087Pulse 1 energy typeDefault 39.FLOAT32ABCDRead/write37 = Total kWh; 39 = Total kVArh
HR61456doc 461457ResetWrite 0000 to reset maximum demand or 0003 to reset the resettable energy.UINT16Write
HR64514doc 464515Meter codeReads 0x0079 on this model.UINT16Read
HR64515doc 464516Software versionHex-coded firmware version.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eastron SDM630MCT

What Modbus registers does the Eastron SDM630MCT have?

This map lists 109 registers: 93 input registers, 16 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eastron SDM630MCT Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed Modicon style (30001 / 40001, and six-digit 46xxxx for high addresses) next to the hex start address actually sent. Wire address = printed number minus 30001 or 40001 (or 400001): 30001 is 0x0000, 30007 is 0x0006 (the document's own example), 461457 is 0xF010.

What byte order does the Eastron SDM630MCT use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Eastron SDM630MCT?

Start with IR 0 Phase 1 line to neutral volts (Phase 1 voltage); IR 6 Phase 1 current (Phase 1 current); IR 52 Total system power (Total system power); IR 62 Total system power factor (Total power factor); IR 70 Frequency of supply voltages (Frequency); IR 72 Total import kWh (Total import kWh); IR 74 Total export kWh (Total export kWh); HR 62 CT ratio (CT ratio check).

How do I enable Modbus control of the Eastron SDM630MCT?

RS485 Modbus RTU is built in on the RS485 versions. Set address, baud rate and parity/stop bits from the front setup menu or holding registers 40021, 40029 and 40019.

Where is the official Eastron SDM630MCT Modbus documentation?

The source is Eastron SDM630MCT Smart Meter Modbus Protocol Implementation V1.7 (V1.7), published free by Eastron at https://www.eastroneurope.com/images/uploads/products/protocol/SDM630MCT_MODBUS_Protocol_V1.7.pdf.

More Eastron Modbus register maps

Source: Eastron SDM630MCT Smart Meter Modbus Protocol Implementation V1.7 · V1.7. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.