 "manufacturer": "Eaton",
 "manufacturer_slug": "eaton",
 "model": "C440 electronic overload relay (via C441 Ethernet module)",
 "model_slug": "c440-overload-relay",
 "short_model": "C440",
 "aliases": [
  "C440",
  "C440 overload relay",
  "C441U",
  "C441V"
 ],
 "equipment_type": "Motor protection relay (overload relay)",
 "applies_to": "Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.",
 "summary": "The C440 is Eaton's electronic overload relay. With a C441 Ethernet module it reports motor state, phase currents, thermal memory and latched faults over Modbus TCP (and the module's RS-485 port), and accepts remote trip and reset. This map covers the adapter I/O registers, the overload data (300-315), trip/reset control (332) and scaling and identity registers (396-399).",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V)",
  "doc_number": "MN04200002E",
  "revision_date": "2012-08",
  "url": "https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf",
  "pages": "pp. 54-55 (section 7.3, Table 97)",
  "unofficial": true
 },
 "notes": [
  "Source is a distributor copy (precision-elec.com) of Eaton manual MN04200002E dated August 2012. Eaton lists a later edition (January 2016) at eaton.com, which could not be downloaded from this machine; check it for changes.",
  "The tables print 1-based Modbus register numbers: the production/consumption-list note says field inputs register 1 is register address 0 (address = register number - 1).",
  "All registers listed are single 16-bit words. Multi-word items (32-bit adapter serial number at 7, firmware/hardware revision at 9/11, IP addresses 144-154, MAC address 156) have no stated word order or layout and are left out. Signedness is not stated; values are typed unsigned.",
  "The C440 is used with the stand-alone C441U/C441V module, whose serial port is the link to the C440 and is not available as a monitoring port, so this map is reached over Modbus TCP. Functions 01/02/03/04/05/06/15/16/23 and 43/14 are supported. Coil numbers in the manual are bit views of the same registers and are not listed here.",
  "Registers 1000-4000 are a user-configurable production/consumption list (custom register block); not expanded here.",
  "Current registers (301-304, 310, 311, 396, 397) are divided by the multiplier in register 398; e.g. 398 = 10 means 0.1 A units. They are left unscaled here.",
  "Line frequency 313 is printed in deciHz (0.1 Hz).",
  "Left out: 400 serial number and 428/430 firmware revision/checksum (32-bit, word order not stated) and 402 hardware revision (packed bytes).",
  "The C440 table does not list the serial-port setup registers 159-163 that the C441 and S611 tables have."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Field inputs",
   "description": "Adapter input points.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input 1",
    "1": "Input 2",
    "2": "Input 3",
    "3": "Input 4"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Control voltage",
   "description": "Adapter supply voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "DIP switch value",
   "description": "Present DIP switch state.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "101",
   "name": "Field relay outputs",
   "description": "Adapter output relays.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Output 1",
    "1": "Output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "110",
   "name": "Modbus TCP com timeout",
   "description": "0 = disabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "111",
   "name": "Field relay fault action",
   "description": "Per relay: 0 = apply fault value, 1 = no change.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "112",
   "name": "Field relay fault state",
   "description": "Per relay value on comm fault: 0 off, 1 on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "113",
   "name": "Field relay idle action",
   "description": "Per relay: 0 = apply idle value, 1 = no change.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "114",
   "name": "Field relay idle state",
   "description": "Per relay value on comm idle: 0 off, 1 on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "143",
   "name": "IP allocation method",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "DHCP",
    "1": "Upper 3 octets from NV, last octet from DIP switches",
    "2": "Full address from NV memory",
    "3": "Restore 192.168.1.254"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "201",
   "name": "Intercom status",
   "description": "Link between adapter and host device.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Connected fully, no errors",
    "1": "Message fault occurred",
    "2": "Devices married, target identified",
    "3": "Basic connection established"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 250,
   "documented": "251",
   "name": "Motor ctrl idle loss act disable",
   "description": "1 = keep motor state on comm idle; 0 = apply idle value (252).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 251,
   "documented": "252",
   "name": "Motor ctrl com idle action value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (no change)",
    "1": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "253",
   "name": "Motor ctrl com loss act disable",
   "description": "1 = keep motor state on comm loss; 0 = apply loss value (254).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 253,
   "documented": "254",
   "name": "Motor ctrl com loss action value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (no change)",
    "1": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 299,
   "documented": "300",
   "name": "Motor control state",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Stopped",
    "1": "Running",
    "2": "Tripped",
    "3": "Tripped",
    "4": "Resetting"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "301",
   "name": "Phase A RMS current",
   "description": "Scaled by register 398.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 301,
   "documented": "302",
   "name": "Phase B RMS current",
   "description": "Scaled by register 398.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "303",
   "name": "Phase C RMS current",
   "description": "Scaled by register 398.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 303,
   "documented": "304",
   "name": "Average current",
   "description": "Scaled by register 398.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "305",
   "name": "Thermal memory",
   "description": "100% = trip.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 305,
   "documented": "306",
   "name": "Latched faults",
   "description": "Cleared by network reset or when current flows.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Overload fault",
    "1": "Phase imbalance",
    "2": "Phase loss fault",
    "3": "Ground fault",
    "4": "Network trip command",
    "5": "NV memory failure"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "307",
   "name": "Current as percent of FLA",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 307,
   "documented": "308",
   "name": "Phase imbalance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "309",
   "name": "Ground fault percent",
   "description": "GF% = ground current / (0.5 x FLA).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 309,
   "documented": "310",
   "name": "Ground current",
   "description": "Scaled by register 398.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "311",
   "name": "FLA setting",
   "description": "From the potentiometer; scaled by 398.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 311,
   "documented": "312",
   "name": "Overload class",
   "description": "Device dependent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 312,
   "documented": "313",
   "name": "Line frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 313,
   "documented": "314",
   "name": "Feature states",
   "description": "Bits 0-1 trip class: 00=10, 01=15, 10=20, 11=30.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "2": "Phase loss/imbalance enabled",
    "3": "Ground fault enabled",
    "4": "Auto reset enabled",
    "5": "Remote reset active",
    "6": "DIP switch position 0",
    "7": "DIP switch position 1",
    "8": "DIP switch position 2",
    "9": "DIP switch position 3"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "315",
   "name": "Device temperature",
   "description": "Accuracy about 10%.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 331,
   "documented": "332",
   "name": "Trip/reset control",
   "description": "Auto-clearing command bits.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Cause a trip (overrides reset)",
    "1": "Cause a reset"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 395,
   "documented": "396",
   "name": "Min FLA",
   "description": "Lowest FLA setting; scaled by 398.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 396,
   "documented": "397",
   "name": "Max FLA",
   "description": "Highest FLA setting; scaled by 398.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 397,
   "documented": "398",
   "name": "Current scale value",
   "description": "Multiplier for currents: 10 means values are in 0.1 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 398,
   "documented": "399",
   "name": "Product code",
   "description": "Odd number = ground-fault capable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 428,
   "documented": "429",
   "name": "Firmware build",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 398 once for the current multiplier, then poll 300 (state), 301-304 (currents), 305 (thermal memory) and 306 (latched faults). Write 332 bit 1 to reset or bit 0 to trip.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 299,
    "why": "Motor state"
   },
   {
    "table": "holding_register",
    "address": 303,
    "why": "Average current (scale by 398)"
   },
   {
    "table": "holding_register",
    "address": 397,
    "why": "Current scale value"
   },
   {
    "table": "holding_register",
    "address": 304,
    "why": "Thermal memory"
   },
   {
    "table": "holding_register",
    "address": 305,
    "why": "Latched fault bits"
   },
   {
    "table": "holding_register",
    "address": 331,
    "why": "Remote trip / reset"
   }
  ],
  "enable": "Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.",
  "watchdog": "Register 110 sets the Modbus TCP com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.",
  "quirks": [
   "Register numbers are 1-based; subtract 1 on the wire.",
   "Coil numbers in the manual are bit views of registers (coil = 16 x (register - 1) + bit + 1), not separate data."
  ],
  "setup": [
   "IP address mode is set by the DIP switch on the module: 0 = restore 192.168.1.254, 1-253 = last octet with the rest from NV memory, 254 = NV memory (factory 192.168.1.254), 255 = DHCP.",
   "The C440 table has no serial-port registers: the C441U/C441V serial port is the link to the C440, so use Modbus TCP."
  ],
  "gotchas": [
   "Several values change scale with hardware or a scale register; check the notes before trusting raw numbers."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/eaton/c440-overload-relay",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}