 "manufacturer": "Eaton",
 "manufacturer_slug": "eaton",
 "model": "C441 Motor Insight motor protection relay (via C441 Ethernet module)",
 "model_slug": "c441-motor-insight",
 "short_model": "C441 Motor Insight",
 "aliases": [
  "Motor Insight",
  "C441BA",
  "C441BB",
  "C441CA",
  "C441CB",
  "C441DA",
  "C441DB",
  "C441R",
  "C441T"
 ],
 "equipment_type": "Motor protection relay",
 "applies_to": "Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.",
 "summary": "Motor Insight is Eaton's voltage and current monitoring motor protection relay. The C441 Ethernet module serves its data over Modbus TCP and RS-485 Modbus RTU together with its own I/O and network settings. This map covers the adapter I/O and comms registers, the motor measurements and trip/warning words (300-336), the command register and the protection settings (400-446).",
 "transport": [
  "TCP",
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V)",
  "doc_number": "MN04200002E",
  "revision_date": "2012-08",
  "url": "https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf",
  "pages": "pp. 50-53 (section 7, Table 96)",
  "unofficial": true
 },
 "notes": [
  "Source is a distributor copy (precision-elec.com) of Eaton manual MN04200002E dated August 2012. Eaton lists a later edition (January 2016) at eaton.com, which could not be downloaded from this machine; check it for changes.",
  "The tables print 1-based Modbus register numbers: the production/consumption-list note says field inputs register 1 is register address 0 (address = register number - 1).",
  "All registers listed are single 16-bit words. Multi-word items (32-bit adapter serial number at 7, firmware/hardware revision at 9/11, IP addresses 144-154, MAC address 156) have no stated word order or layout and are left out. Signedness is not stated; values are typed unsigned.",
  "The same map is served over Modbus TCP and over the adapter's RS-485 Modbus RTU port; functions 01/02/03/04/05/06/15/16/23 and 43/14 are supported. Coil numbers in the manual are bit views of the same registers and are not listed here.",
  "Registers 1000-4000 are a user-configurable production/consumption list (custom register block); not expanded here.",
  "Current registers 300-303 are 0.1 A on 90 A models and on 9 A models with external CTs, and 0.01 A on 9 A models without CTs; motor power 308 is 0.1 kW with external CTs and 0.01 kW otherwise. They are left unscaled here; apply the factor that matches the hardware.",
  "Fault code 315 heads a fault queue: read as a list, faults run newest first. The table's next entry is 325.",
  "CT multiplier 403: 90 A units 1-4 conductor passes; 9 A units 1-2 passes or 3 = 150:5, 4 = 300:5, 5 = 600:5 CTs.",
  "Register 401 (Motor Control) has no description in the manual and is left out.",
  "Defaults are those printed for the C441R/C441T serial monitoring port (address 1, 19.2k, even parity, 1 stop bit, RTU); data bits and the Modbus TCP port are not stated."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Field inputs",
   "description": "Adapter input points.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input 1",
    "1": "Input 2",
    "2": "Input 3",
    "3": "Input 4"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Control voltage",
   "description": "Adapter supply voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "DIP switch value",
   "description": "Present DIP switch state.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "101",
   "name": "Field relay outputs",
   "description": "Adapter output relays.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Output 1",
    "1": "Output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "110",
   "name": "Modbus TCP com timeout",
   "description": "0 = disabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "111",
   "name": "Field relay fault action",
   "description": "Per relay: 0 = apply fault value, 1 = no change.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "112",
   "name": "Field relay fault state",
   "description": "Per relay value on comm fault: 0 off, 1 on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "113",
   "name": "Field relay idle action",
   "description": "Per relay: 0 = apply idle value, 1 = no change.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "114",
   "name": "Field relay idle state",
   "description": "Per relay value on comm idle: 0 off, 1 on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "143",
   "name": "IP allocation method",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "DHCP",
    "1": "Upper 3 octets from NV, last octet from DIP switches",
    "2": "Full address from NV memory",
    "3": "Restore 192.168.1.254"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "159",
   "name": "Modbus serial com timeout",
   "description": "0 = disabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 159,
   "documented": "160",
   "name": "Modbus TX mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RTU",
    "1": "ASCII"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "161",
   "name": "Modbus baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "19200",
    "1": "9600",
    "2": "57600",
    "3": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "162",
   "name": "Modbus address",
   "description": "Serial slave address loaded at start-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "163",
   "name": "Modbus parity and stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even, 1 stop",
    "1": "Odd, 1 stop",
    "2": "None, 2 stop",
    "3": "Even, 2 stop",
    "4": "Odd, 2 stop",
    "5": "None, 1 stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "201",
   "name": "Intercom status",
   "description": "Link between adapter and host device.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Connected fully, no errors",
    "1": "Message fault occurred",
    "2": "Devices married, target identified",
    "3": "Basic connection established"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 250,
   "documented": "251",
   "name": "Motor ctrl idle loss act disable",
   "description": "1 = keep motor state on comm idle; 0 = apply idle value (252).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 251,
   "documented": "252",
   "name": "Motor ctrl com idle action value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (no change)",
    "1": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "253",
   "name": "Motor ctrl com loss act disable",
   "description": "1 = keep motor state on comm loss; 0 = apply loss value (254).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 253,
   "documented": "254",
   "name": "Motor ctrl com loss action value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (no change)",
    "1": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 299,
   "documented": "300",
   "name": "Current I1",
   "description": "Phase A RMS; scale depends on model (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "301",
   "name": "Current I2",
   "description": "Phase B RMS; scale depends on model.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 301,
   "documented": "302",
   "name": "Current I3",
   "description": "Phase C RMS; scale depends on model.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "303",
   "name": "Current average",
   "description": "Average RMS; scale depends on model.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 303,
   "documented": "304",
   "name": "Voltage L1-L2",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "305",
   "name": "Voltage L2-L3",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 305,
   "documented": "306",
   "name": "Voltage L3-L1",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "307",
   "name": "Voltage average",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 307,
   "documented": "308",
   "name": "Motor power",
   "description": "0.1 kW with external CTs, else 0.01 kW (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "309",
   "name": "Voltage unbalance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 309,
   "documented": "310",
   "name": "Current unbalance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "311",
   "name": "Apparent power factor",
   "description": "Real over apparent power.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 311,
   "documented": "312",
   "name": "Residual ground current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 312,
   "documented": "313",
   "name": "Line frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 313,
   "documented": "314",
   "name": "Thermal pile",
   "description": "100% causes an overload trip.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "315",
   "name": "Fault code",
   "description": "Most recent fault when read as one register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 324,
   "documented": "325",
   "name": "Rapid cycling restart delay remaining",
   "description": "Supply fault time to restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 325,
   "documented": "326",
   "name": "Normal restart delay remaining",
   "description": "Motor fault time to restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 326,
   "documented": "327",
   "name": "Underload restart delay remaining",
   "description": "Load fault time to restart.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 327,
   "documented": "328",
   "name": "Run time hours",
   "description": "Resettable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 328,
   "documented": "329",
   "name": "Start count",
   "description": "Resettable.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 329,
   "documented": "330",
   "name": "Trip reason",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Restart attempts exceeded",
    "1": "Relay turned off (network/UI)",
    "2": "Contactor failure",
    "3": "Under current trip",
    "4": "Overload trip",
    "5": "Ground fault trip",
    "6": "Current unbalance trip",
    "7": "Current single phase",
    "9": "High power trip",
    "10": "Over voltage trip",
    "11": "Under voltage trip",
    "12": "Voltage unbalance trip",
    "13": "Over current trip",
    "14": "Low power trip",
    "15": "Phase reversal trip"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 330,
   "documented": "331",
   "name": "Overload status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Overload trip",
    "1": "Ground fault trip",
    "2": "High power trip",
    "7": "Relay closed"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 331,
   "documented": "332",
   "name": "Warning / alarm indications",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Low voltage warning",
    "1": "High voltage warning",
    "2": "Voltage unbalance warning",
    "3": "Low power warning",
    "4": "Reverse phase warning",
    "5": "Current unbalance warning",
    "6": "Voltage single phase warning",
    "7": "Current single phase warning",
    "8": "Ground fault warning"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 332,
   "documented": "333",
   "name": "C441 DSP firmware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 333,
   "documented": "334",
   "name": "UI firmware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 334,
   "documented": "335",
   "name": "C441 unit ID",
   "description": "Model identifier.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "186": "C441BA",
    "187": "C441BB",
    "202": "C441CA",
    "203": "C441CB",
    "218": "C441DA",
    "219": "C441DB",
    "234": "C4410109(x)",
    "235": "C4410590(x)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 335,
   "documented": "336",
   "name": "Aux relay trip reason",
   "description": "120 V control power models.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "1": "Relay turned off (network/UI)",
    "2": "Contactor failure",
    "3": "Under current trip",
    "4": "Overload trip",
    "5": "Ground fault trip",
    "6": "Current unbalance trip",
    "7": "Current single phase",
    "9": "High power trip",
    "10": "Over voltage trip",
    "11": "Under voltage trip",
    "12": "Voltage unbalance trip",
    "13": "Over current trip",
    "14": "Low power trip",
    "15": "Phase reversal trip",
    "8": "Mains frequency fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 399,
   "documented": "400",
   "name": "Command register",
   "description": "Write a command code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "102": "Clear motor run hours (0x66)",
    "119": "Clear fault queue 1 (0x77)",
    "120": "Clear fault queue (0x78)",
    "136": "Network watchdog enable (0x88)",
    "153": "Network watchdog disable (0x99)",
    "170": "Reset relay (0xAA)",
    "187": "Clear motor start count (0xBB)",
    "204": "Force ground fault (0xCC)",
    "221": "Fault relay off (0xDD)",
    "238": "Reset auxiliary relay (0xEE)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "402",
   "name": "Configuration reset",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Soft reset (like power cycle)",
    "2": "Factory reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "403",
   "name": "CT multiplier",
   "description": "Conductor passes or CT ratio code (see notes).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 403,
   "documented": "404",
   "name": "Ground fault pick-up level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 404,
   "documented": "405",
   "name": "Under current pick-up level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 405,
   "documented": "406",
   "name": "Low power pick-up level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 406,
   "documented": "407",
   "name": "Overload FLA",
   "description": "Motor full load current.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 407,
   "documented": "408",
   "name": "Current unbalance pick-up level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 408,
   "documented": "409",
   "name": "Overload trip class",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 409,
   "documented": "410",
   "name": "Under voltage pick-up level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 410,
   "documented": "411",
   "name": "Over voltage pick-up level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 411,
   "documented": "412",
   "name": "Voltage unbalance pick-up level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "413",
   "name": "Jam pick-up level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 413,
   "documented": "414",
   "name": "High kW trip limit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "kW",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 414,
   "documented": "415",
   "name": "Phase order",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Trip disabled",
    "1": "ACB",
    "2": "ABC"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 415,
   "documented": "416",
   "name": "Supply fault hold-off time",
   "description": "Restart delay.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 416,
   "documented": "417",
   "name": "Motor fault hold-off time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 417,
   "documented": "418",
   "name": "Load fault hold-off time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 418,
   "documented": "419",
   "name": "Load fault number of restarts",
   "description": "0 manual, 1-4 attempts, 5 automatic.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 419,
   "documented": "420",
   "name": "Motor fault number of restarts",
   "description": "0 manual, 1-4 attempts, 5 automatic.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 420,
   "documented": "421",
   "name": "Ground fault trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 421,
   "documented": "422",
   "name": "Under current trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 422,
   "documented": "423",
   "name": "Low power trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 423,
   "documented": "424",
   "name": "Jam trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 424,
   "documented": "425",
   "name": "Current unbalance trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 425,
   "documented": "426",
   "name": "Under voltage trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 426,
   "documented": "427",
   "name": "Over voltage trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 427,
   "documented": "428",
   "name": "Voltage unbalance trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 428,
   "documented": "429",
   "name": "High kW trip time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 429,
   "documented": "430",
   "name": "Current phase loss trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 432,
   "documented": "433",
   "name": "Trip enable bits",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Ground fault",
    "1": "Voltage unbalance",
    "2": "Current unbalance",
    "3": "Under current",
    "4": "Phase loss",
    "5": "Jam",
    "6": "Low power",
    "7": "High power",
    "8": "Over voltage",
    "9": "Under voltage",
    "10": "Phase order"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 433,
   "documented": "434",
   "name": "Overload reset mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Manual reset",
    "1": "Use motor fault reset delay and attempts"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 434,
   "documented": "435",
   "name": "Voltage faults trip mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Trip on supply fault",
    "1": "Alarm, no trip (inhibit start)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 435,
   "documented": "436",
   "name": "Ground fault trip mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Trip on ground fault",
    "1": "Alarm, no trip"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 436,
   "documented": "437",
   "name": "Run transition percent",
   "description": "Percent of FLA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 437,
   "documented": "438",
   "name": "Run transition time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 438,
   "documented": "439",
   "name": "Network status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Watchdog enabled",
    "2": "Front panel locked"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 439,
   "documented": "440",
   "name": "C441 comm loss timeout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 440,
   "documented": "441",
   "name": "C441 comm loss behavior",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Fault (default)",
    "2": "Hold last state"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 442,
   "documented": "443",
   "name": "Load fault reset delay calc",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (default)",
    "1": "Enabled"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 445,
   "documented": "446",
   "name": "Aux relay reset delay",
   "description": "120 V models; 0 = no auto reset, 1-500 min.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "min",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Read 300-315 for currents, voltages, power and thermal pile, and 330-332 for trip and warning bits. Write command codes to 400 (e.g. 0xAA reset relay) and settings to 403-446. Comm-loss behaviour is set with 440/441 and 251-254.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 299,
    "why": "Phase A current"
   },
   {
    "table": "holding_register",
    "address": 302,
    "why": "Average current"
   },
   {
    "table": "holding_register",
    "address": 306,
    "why": "Average voltage"
   },
   {
    "table": "holding_register",
    "address": 307,
    "why": "Motor power"
   },
   {
    "table": "holding_register",
    "address": 313,
    "why": "Thermal pile"
   },
   {
    "table": "holding_register",
    "address": 329,
    "why": "Trip reason bits"
   },
   {
    "table": "holding_register",
    "address": 331,
    "why": "Warning bits"
   },
   {
    "table": "holding_register",
    "address": 399,
    "why": "Command register (reset relay etc.)"
   }
  ],
  "enable": "Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.",
  "watchdog": "Register 110 (Modbus TCP) and 159 (serial) set a com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.",
  "quirks": [
   "Register numbers are 1-based; subtract 1 on the wire.",
   "Coil numbers in the manual are bit views of registers (coil = 16 x (register - 1) + bit + 1), not separate data."
  ],
  "setup": [
   "Serial port settings live in 160-163 (mode, baud, address, parity/stop) where the table lists them.",
   "On a C441R/C441T the RS-485 port is an extra Modbus RTU/ASCII monitoring port that serves the same register map."
  ],
  "gotchas": [
   "Several values change scale with hardware or a scale register; check the notes before trusting raw numbers."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/eaton/c441-motor-insight",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}