 "manufacturer": "Eaton",
 "manufacturer_slug": "eaton",
 "model": "PowerXL DA1 variable frequency drive (Modbus RTU)",
 "model_slug": "powerxl-da1",
 "short_model": "PowerXL DA1",
 "aliases": [
  "DA1",
  "PowerXL DA1",
  "DA1-12",
  "DA1-32",
  "DA1-34",
  "DA1-35"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.",
 "summary": "The PowerXL DA1 talks Modbus RTU on its RJ45 RS-485 socket. Eaton numbers every value by an ID: a small process-data block (command, speed reference, status/fault word, speed, current) plus parameter IDs. Every value is a single 16-bit register with an implied decimal point. This map covers the process data and the communication settings.",
 "transport": [
  "RTU"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 115200,
  "parity": "None",
  "data_bits": 8,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual numbers registers from ID 1. Its frame examples read status ID 6 with start address 0005h and write command ID 1 to address 0000h, so ID n is wire address n-1."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "PowerXL Modbus RTU Communication manual for Variable Frequency Drives / Variable Speed Starters DA1, DB1, DC1, DE1",
  "doc_number": "MN040018EN",
  "revision_date": "2022-12",
  "url": "https://es-assets.eaton.com/DOCUMENTATION/AWB_MANUALS/MN040018_EN.pdf",
  "pages": "Enable and data format p. 9; DA1 comms parameters pp. 11-12; register mapping p. 27; process data pp. 28-39; frame examples pp. 40-41; DA1 parameter table pp. 42-52"
 },
 "notes": [
  "Every value is one 16-bit register; the decimal point is implied (a displayed 0.3 A is sent as 3).",
  "The manual does not state signedness for the process data; they are typed UINT16 because their ranges are non-negative (direction is a status bit).",
  "Output power (ID 10) is left out: the summary table gives scale 1 but the detailed text says one decimal (53 = 5.3 kW). The power (ID 13) and voltage range (ID 14) words are left out because their meaning depends on the drive's kW/HP setting.",
  "Fault numbers in the high byte of ID 6 for the DA1 (decimal, as printed in table 11): 0 no-Flt (no fault), 1 OI-b brake overcurrent, 2 OL-br brake resistor overload, 3 O-I output overcurrent, 4 I.t-trP motor overload, 5 PS-trp hardware overcurrent, 6 O.Volt DC overvoltage, 7 U.Volt DC undervoltage, 8 O-t heatsink overtemperature, 9 U-t undertemperature, 10 P-dEf defaults loaded, 11 E-trip external fault, 12 SC-ObS keypad/PC comms error, 13 FlT-dc DC ripple too high, 14 P-LOss input phase loss, 15 h O-I output overcurrent, 16 Th-flt heatsink thermistor fault, 17 dAtA-F memory error, 18 4-20 F analog input out of range, 19 dAtA-E memory error, 20 U-dEf user defaults loaded, 21 F-Ptc motor PTC, 22 FAn-F fan fault, 23 O-hEAt ambient too hot, 24 O-torQ torque too high, 25 U-torQ torque too low (hoist brake), 26 OUt-F output fault, 29 Sto-F STO circuit fault, 30-35 Enc-01..06 encoder faults, 40-44 AtF-01..05 motor identification failed, 49 Out-Ph motor phase lost, 50 Sc-FO1 Modbus timeout, 51 Sc-FO2 CANopen timeout, 52 Sc-FO3 fieldbus option lost, 53 Sc-F04 I/O option lost, 60-61 OF-01/OF-02 option card faults, 70-74 PLC-01..05 function-block editor faults. The 'Stop' display (enable signal missing) is listed without a number and is not a fault.",
  "Left out: t-acc/t-dec (P1-03/P1-04), whose scale is printed as 300 = 30.0 s while the range column reads 0.00-6000 s; the fixed-frequency and f-max/f-min registers (60 counts per Hz); heatsink temperature (no data format, so signedness is unknown) and the MWh meter (no scale or data format); serial number words 25-28.",
  "The DA1 also has user registers 51-78 for its function-block editor; they are not mapped."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "ID 1",
   "name": "Fieldbus command",
   "description": "Control word: run, direction, reset, coast, quick stop.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "0 = stop, 1 = run (operational)",
    "1": "0 = forward (clockwise), 1 = reverse",
    "2": "1 = reset fault",
    "3": "1 = coast to stop",
    "5": "1 = quick stop (ramp 2)",
    "6": "1 = run at fixed frequency FF1",
    "7": "1 = force the setpoint to 0"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "ID 2",
   "name": "Fieldbus speed reference",
   "description": "Setpoint frequency, limited to the min/max frequency parameters.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "ID 3",
   "name": "Torque reference",
   "description": "DA1 only; 0-2000 (1000 = 100 %).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "ID 4",
   "name": "Modbus ramp time",
   "description": "Ramp time sent over Modbus, 0-60000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "ID 6",
   "name": "Status and fault word",
   "description": "Low byte = status bits, high byte = fault number.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "1 = ready (READY)",
    "1": "1 = running (RUN)",
    "2": "0 = forward, 1 = reverse",
    "3": "1 = fault (FAULT)",
    "4": "1 = actual frequency equals setpoint (0 = ramping)",
    "5": "1 = zero speed",
    "6": "1 = speed control active",
    "7": "DA1: 0 = STO inhibit, 1 = STO ready",
    "8-15": "Fault word: the fault number (see notes), 0 = no fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 6,
   "documented": "ID 7",
   "name": "Actual speed",
   "description": "Output frequency.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "ID 8",
   "name": "Motor current",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "ID 9",
   "name": "Torque",
   "description": "Motor torque, 1000 = 100 %.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 10,
   "documented": "ID 11",
   "name": "Digital inputs",
   "description": "Input states; the lowest bit is DI1.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "DI1",
    "1": "DI2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 11,
   "documented": "ID 12",
   "name": "Drive type code",
   "description": "Part-number code: frame size, voltage class, phases and power index as hex digits.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 14,
   "documented": "ID 15",
   "name": "Control section software version",
   "description": "Two implied decimals.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 15,
   "documented": "ID 16",
   "name": "Power section software version",
   "description": "Two implied decimals.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 16,
   "documented": "ID 17",
   "name": "Drive recognition",
   "description": "Fixed family code; DA1 reads 5632.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 22,
   "documented": "23 (P0-20)",
   "name": "DC-link voltage",
   "description": "600 = 600 V.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 29,
   "documented": "30 (P0-26)",
   "name": "kWh meter",
   "description": "100 = 10.0 kWh.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kWh",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 106,
   "documented": "107 (P1-07)",
   "name": "Motor rated voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 107,
   "documented": "108 (P1-08)",
   "name": "Motor rated current",
   "description": "1 = 0.1 A.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "112 (P1-12)",
   "name": "Local process data source",
   "description": "Selects where run commands and the speed reference come from.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Terminal control",
    "1": "Digital reference, forward only",
    "2": "Digital reference, forward and reverse",
    "3": "PID controller",
    "4": "Fieldbus control (Modbus RTU if no fieldbus option)",
    "5": "Server mode (follows a drive in client mode)",
    "6": "CANopen control",
    "9": "SmartWire-DT control and speed reference",
    "10": "SmartWire-DT control, terminal speed reference",
    "11": "Terminal control, SmartWire-DT speed reference",
    "13": "SmartWire-DT control and reference, digital input enables"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "501 (P5-01)",
   "name": "Drive address",
   "description": "1-63 (0 is broadcast), default 1.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 502,
   "documented": "503 (P5-03)",
   "name": "RS-485 baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "9.6 kbit/s",
    "1": "19.2 kbit/s",
    "2": "38.4 kbit/s",
    "3": "57.6 kbit/s",
    "4": "115.2 kbit/s"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 503,
   "documented": "504 (P5-04)",
   "name": "RS-485 parity type",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "No parity, 1 stop bit",
    "1": "No parity, 2 stop bits",
    "2": "Odd parity, 1 stop bit",
    "3": "Even parity, 1 stop bit"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 504,
   "documented": "505 (P5-05)",
   "name": "Modbus comms timeout",
   "description": "Time without a valid telegram before P5-06 acts.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 505,
   "documented": "506 (P5-06)",
   "name": "Action on Modbus fault",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Switch off (trip)",
    "1": "Ramp to stop, then switch off",
    "2": "Ramp to stop, no fault",
    "3": "Run at fixed frequency 8 (P2-08)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 506,
   "documented": "507 (P5-07)",
   "name": "Fieldbus ramp control",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ramps from drive parameters",
    "1": "Ramps from fieldbus"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Write the speed reference to ID 2 and the command word to ID 1 (bit 0 = run), then read IDs 6-8 for status, speed and current. The control-source parameter must select Modbus first.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 0,
    "why": "Run/stop/reset command word"
   },
   {
    "table": "holding_register",
    "address": 1,
    "why": "Speed reference (0.1 Hz)"
   },
   {
    "table": "holding_register",
    "address": 5,
    "why": "Status bits and fault number"
   },
   {
    "table": "holding_register",
    "address": 6,
    "why": "Actual frequency"
   },
   {
    "table": "holding_register",
    "address": 7,
    "why": "Motor current"
   },
   {
    "table": "holding_register",
    "address": 111,
    "why": "Control source must select Modbus"
   }
  ],
  "enable": "Set P1-12 = 4 (fieldbus control; Modbus RTU when no fieldbus option is fitted). The STO input acts as the enable signal. Address P5-01, baud P5-03, parity P5-04.",
  "watchdog": "P5-05 sets the comms timeout in 0.1 s steps and P5-06 the reaction: trip, ramp then trip, ramp without fault, or run at P2-08.",
  "quirks": [
   "Register = ID - 1 on the wire; tools with a +1 offset take the ID directly.",
   "Function codes 03, 06, 16 and 23 only; at most 11 registers per read.",
   "The high byte of ID 6 is a fault number, not flags."
  ],
  "setup": [
   "P5-01 = address (default 1), P5-03 = baud (default 4 = 115.2 kbit/s), P5-04 = parity (default no parity, 1 stop bit).",
   "The RS-485 link is on the RJ45 socket."
  ],
  "gotchas": [
   "Without the DI1/STO enable the drive reports 'Stop' and will not run from Modbus.",
   "Set bit 2 of the command word to reset a fault."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/eaton/powerxl-da1",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}