 "manufacturer": "Eaton",
 "manufacturer_slug": "eaton",
 "model": "PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)",
 "model_slug": "powerxl-dg1-dh1",
 "short_model": "PowerXL DG1/DH1",
 "aliases": [
  "DG1",
  "DH1",
  "PowerXL DG1",
  "PowerXL DH1",
  "DG1 general purpose drive",
  "DH1 HVAC drive"
 ],
 "equipment_type": "Variable frequency drive",
 "applies_to": "PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).",
 "summary": "The PowerXL DG1 and DH1 are Eaton variable frequency drives with on-board RS-485 (Modbus RTU, BACnet MS/TP) and Ethernet (Modbus TCP, EtherNet/IP, BACnet IP). Both expose the same Modbus layout: monitoring values by ID, a fixed process-data block for control and status, and parameters by ID. This map covers the control and status words, speed reference, default process data and the main monitoring IDs.",
 "transport": [
  "RTU",
  "TCP"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": 502
 },
 "addressing": {
  "convention": "Modicon",
  "note": "The manual pairs each drive ID with a 4x register (ID 2001 = 42001, ID 1 = 40001) and its frame examples read 'holding registers 2000-2003' with start address 07D0h, so ID n goes on the wire as n-1 (40001 = address 0)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "PowerXL Series VFD Communication Manual",
  "doc_number": "MN040010EN",
  "revision_date": "2018-06",
  "url": "https://www.precision-elec.com/wp-content/uploads/2020/12/PowerXL-Communication-Manual.pdf",
  "unofficial": true,
  "pages": "RTU settings p. 8; functions and frame examples pp. 10-11; register index and process data pp. 12-15; DH1 parameter list p. 205; process data defaults p. 222"
 },
 "notes": [
  "This copy is hosted by the US distributor Precision Electric; it is Eaton manual MN040010EN (June 2018).",
  "Scales come from the 'Display format' column of the parameter ID lists (x100 = two decimals, x10 = one decimal, x0 = none) and from the Appendix B process-data table. INTEGER items are typed INT16 here (the process-data range is printed -32768...32767).",
  "Process data out 8 is left out: the RTU chapter says it defaults to ID 28 (latest fault code) while Appendix B says FB Data Out 8 Sel defaults to ID 8 (unit temperature). Read ID 28 directly instead. Process data in 2-3 (setpoint/feedback) have no fixed unit and are left out.",
  "Left out: every 4-byte (DOUBLE) value such as energy counters, PID setpoints/feedback and instant motor power, because the manual only says data is big endian and does not state the word order of 32-bit values; the FB general status word 2102, whose 'not used' bit marks did not survive in the table.",
  "The DH1 menu codes are P12.3.x for RS-485 settings, the DG1 codes P20.3.x.",
  "Left out: monitoring IDs whose unit the manual does not settle: analog inputs 1-2 and analog output 1 (IDs 10, 11, 25; the BACnet object table calls them volts), PT100 temperature (ID 27) and the PID1/PID2 outputs (IDs 22, 38).",
  "RTU defaults from Table 8: slave address 1, baud rate code 1 (19200), parity code 2 (even, 1 stop bit). Data bits are not stated."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "ID 1 (register 40001)",
   "name": "Output frequency",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "ID 2 (register 40002)",
   "name": "Motor speed",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2,
   "documented": "ID 3 (register 40003)",
   "name": "Motor current",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 3,
   "documented": "ID 4 (register 40004)",
   "name": "Motor torque",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "ID 5 (register 40005)",
   "name": "Motor power",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 5,
   "documented": "ID 6 (register 40006)",
   "name": "Motor voltage",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 7,
   "documented": "ID 8 (register 40008)",
   "name": "Unit temperature",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 8,
   "documented": "ID 9 (register 40009)",
   "name": "Motor temperature",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 23,
   "documented": "ID 24 (register 40024)",
   "name": "Frequency reference",
   "description": "Monitoring value read by ID.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 27,
   "documented": "ID 28 (register 40028)",
   "name": "Latest fault code",
   "description": "Code of the most recent fault.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2000,
   "documented": "42001",
   "name": "FB control word",
   "description": "Drive command bits.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Drive output on (run)",
    "1": "Counter-clockwise (reverse)",
    "2": "Fault reset",
    "3": "FB INDATA1",
    "4": "FB INDATA2",
    "5": "FB INDATA3",
    "6": "FB INDATA4",
    "7": "Bypass relay enable",
    "8": "FB control on",
    "9": "FB reference on"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2002,
   "documented": "42003",
   "name": "FB speed reference",
   "description": "0-10000 = 0.00-100.00 % between minimum and maximum frequency.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2003,
   "documented": "42004",
   "name": "Process data in 1 (fb torque reference)",
   "description": "FB torque reference in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2006,
   "documented": "42007",
   "name": "Process data in 4 (accel time 1)",
   "description": "Accel time 1 in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2007,
   "documented": "42008",
   "name": "Process data in 5 (decel time 1)",
   "description": "Decel time 1 in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2008,
   "documented": "42009",
   "name": "Process data in 6 (current limit)",
   "description": "Current limit in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2100,
   "documented": "42101",
   "name": "FB status word",
   "description": "Drive state bits.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Ready",
    "1": "Running",
    "2": "Counterclockwise",
    "3": "Faulted",
    "4": "Warning",
    "5": "Reference frequency reached",
    "6": "Bypass activated",
    "7": "Run enabled"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2102,
   "documented": "42103",
   "name": "FB actual speed",
   "description": "Actual motor speed, 0.01 % units.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2103,
   "documented": "42104",
   "name": "Process data out 1 (output frequency)",
   "description": "Output frequency in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2104,
   "documented": "42105",
   "name": "Process data out 2 (motor speed)",
   "description": "Motor speed in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "rpm",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2105,
   "documented": "42106",
   "name": "Process data out 3 (motor current)",
   "description": "Motor current in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2106,
   "documented": "42107",
   "name": "Process data out 4 (motor torque)",
   "description": "Motor torque in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2107,
   "documented": "42108",
   "name": "Process data out 5 (motor power)",
   "description": "Motor power in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2108,
   "documented": "42109",
   "name": "Process data out 6 (motor voltage)",
   "description": "Motor voltage in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 2109,
   "documented": "42110",
   "name": "Process data out 7 (dc link voltage)",
   "description": "DC link voltage in the default process-data mapping.",
   "data_type": "INT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Write the control word at 2000 (bit 0 run, bit 1 reverse, bit 2 reset, bits 8-9 for fieldbus control and reference) and the speed reference at 2002, then read status 2100 and process data out 2103-2109.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2000,
    "why": "Control word"
   },
   {
    "table": "holding_register",
    "address": 2002,
    "why": "Speed reference 0.01 %"
   },
   {
    "table": "holding_register",
    "address": 2100,
    "why": "Status word"
   },
   {
    "table": "holding_register",
    "address": 2103,
    "why": "Output frequency"
   },
   {
    "table": "holding_register",
    "address": 2105,
    "why": "Motor current"
   },
   {
    "table": "holding_register",
    "address": 27,
    "why": "Latest fault code"
   }
  ],
  "enable": "Select Modbus RTU in RS485 comm set (DG1 P20.3.1.1 / DH1 P12.3.1.1, ID 586) and set slave address, baud rate and parity in the same group; set the control place and reference source to fieldbus.",
  "watchdog": "DG1 has a Modbus RTU communication time-out (P20.3.2.9, ID 593, printed default 10000 ms); P20.3.2.10 / P12.3.2.6 (ID 2516) chooses whether a comm loss faults only in fieldbus control or in all control places.",
  "quirks": [
   "Process data and IDs are Modicon-style: subtract 1 (and 40001) for the wire address.",
   "Holding and input registers are the same data (function 03 or 04)."
  ],
  "setup": [
   "Slave address range 1-247, default 1.",
   "Parity choice also sets stop bits: none = 2 stop bits, odd/even = 1 stop bit.",
   "Defaults: 19200 baud, even parity, 1 stop bit."
  ],
  "gotchas": [
   "Control word bits 8 (FB control) and 9 (FB reference) must be set for the drive to take run and speed from the bus."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/eaton/powerxl-dg1-dh1",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}