- Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Power meter · Modbus register map
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300) Modbus register map
Updated 16 October 2026
The PXM 1000 series are compact multifunction power and energy meters with a built-in RS-485 port running Modbus RTU (DNP3.0 selectable) and optional plug-in I/O and communication modules. Live readings are IEEE floats in holding registers from 4000H, energy counters are 32-bit integers, and setup values are 16-bit words from 0FFDH. This map covers the comm and CT settings, status, voltages, currents, powers, power factor, demand, energy, THD, phase angles and the first I/O module's inputs and relays.
This page lists 92 Modbus registers for the Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300) — 34 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eaton
- Model
- Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
- Equipment type
- Power meter
- Registers
- 92 (34 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000
- Source document
- PXM 1000 User Manual · MN150009EN · rev. 2018-10
Integration notes: Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Over RS-485 at the default 19200 baud, 8N1, address 1, read holding registers 4000H-403BH with function 03 to get frequency, voltages, currents, powers and power factor as big-endian floats; read 4048H-4059H for energy. Set Basic Parameter Mode 101DH to 1 first so the readings come back in primary units.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 16384 | Frequency | FLOAT32 ABCD | Frequency (4000H) | Read |
| HR 16386 | Phase Voltage V1 | FLOAT32 ABCD | Phase voltage V1 (4002H) | Read |
| HR 16402 | Current I1 | FLOAT32 ABCD | Current I1 (4012H) | Read |
| HR 16418 | System Power Psum | FLOAT32 ABCD | Total active power (4022H) | Read |
| HR 16442 | System Power Factor PFsum | FLOAT32 ABCD | System power factor (403AH) | Read |
| HR 16456 | Energy IMP | UINT32 ABCD | Imported active energy (4048H) | Read/write |
| HR 4125 | Basic Parameter Mode | UINT16 | Basic Parameter Mode, set to 1 for primary values (101DH) | Read/write |
Enable Modbus control & writes
Modbus RTU is the default protocol on the built-in RS-485 port (0FFEH = 0). Settings are written with function 16 (10H); one write may only touch registers inside a single settings region. To get primary-unit readings, write 1 to Basic Parameter Mode (101DH). This write is refused while the meter is sealed.
Byte order & addressing
- Addresses are printed in hex and are the wire addresses (4000H = 16384 decimal).
- 32-bit floats and Dwords are high word first.
- By default the 4000H measurement block returns secondary-side values; switch 101DH to Primary or multiply by the PT and CT ratios.
- If Energy Display Mode (1019H) is switched to Secondary, the energy registers hold secondary-side energy in 0.001 steps instead of primary energy in 0.1 steps.
- Function 16 writes must stay inside one settings region (for example system parameters 0FFDH-101DH).
Network setup
- Set the address (S01), baud rate and parity on the meter's System Settings pages or via registers 1001H, 1002H and 0FFFH.
- Built-in port defaults: address 1, 19200 baud, no parity with one stop bit (NON1).
- Parity options are Even, Odd, NON2 (no parity, two stop bits) and NON1 (no parity, one stop bit).
- If an Ethernet or PROFIBUS module is used on the second port, the manual requires 38400 baud and NON1 for that port.
Watch out for
- When the meter's Seal is closed (101FH = 0x0A), setup registers such as wiring, CT, 1019H, 101DH and the energy presets are blocked over Modbus, and 101EH bits 0/1 can also lock the communication settings.
- Clear commands only act on the documented magic value: 1 for demand, run time and energy, 0x0A for max/min.
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0000H | Relay1 | Relay on module PXM1K-11; read with FC01, switch with FC05. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 1doc 0001H | Relay2 | Relay on module PXM1K-11; read with FC01, switch with FC05. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 2doc 0002H | Relay3 | Relay on module PXM1K-31; read with FC01, switch with FC05. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 3doc 0003H | Relay4 | Relay on module PXM1K-31; read with FC01, switch with FC05. | BIT | Read/write | 0 = Off; 1 = On | |||
| DI | 0doc 0000H | DI1 | Digital input on I/O module PXM1K-11; 0 if module absent. | BIT | Read | 0 = Off; 1 = On | |||
| DI | 1doc 0001H | DI2 | Digital input on I/O module PXM1K-11; 0 if module absent. | BIT | Read | 0 = Off; 1 = On | |||
| DI | 2doc 0002H | DI3 | Digital input on I/O module PXM1K-11; 0 if module absent. | BIT | Read | 0 = Off; 1 = On | |||
| DI | 3doc 0003H | DI4 | Digital input on I/O module PXM1K-11; 0 if module absent. | BIT | Read | 0 = Off; 1 = On | |||
| DI | 4doc 0004H | DI5 | Digital input on I/O module PXM1K-11; 0 if module absent. | BIT | Read | 0 = Off; 1 = On | |||
| DI | 5doc 0005H | DI6 | Digital input on I/O module PXM1K-11; 0 if module absent. | BIT | Read | 0 = Off; 1 = On | |||
| HR | 4093doc 0ffdH | Frequency | Nominal frequency setting. | UINT16 | Read/write | 0 = 50 Hz; 1 = 60 Hz; 2 = 400 Hz | |||
| HR | 4094doc 0ffdH (printed; 0FFEH per the manual's notes) | First Communication Protocol | Protocol on the built-in RS-485 port. | UINT16 | Read/write | 0 = Modbus; 1 = DNP3.0 | |||
| HR | 4095doc 0fffH | Parity Setting1 | Built-in RS-485 parity and stop bits. | UINT16 | Read/write | 0 = Even; 1 = Odd; 2 = None, 2 stop bits; 3 = None, 1 stop bit | |||
| HR | 4097doc 1001H | Communication Address | Modbus address 1-247 on the built-in port. | UINT16 | Read/write | ||||
| HR | 4098doc 1002H | Baud Rate | Built-in RS-485 baud rate, 1200-38400. | UINT16 | bps | Read/write | |||
| HR | 4099doc 1003H | Voltage Input Wiring Type | UINT16 | Read/write | 0 = 3LN; 1 = 1LN; 2 = 2LL; 3 = 3LL; 4 = 1LL | ||||
| HR | 4100doc 1004H | Current Input Wiring Type | UINT16 | Read/write | 0 = 3CT; 1 = 1CT; 2 = 2CT | ||||
| HR | 4104doc 1008H | CT1 | CT primary rating, 1-50000. | UINT16 | A | Read/write | |||
| HR | 4105doc 1009H | CT2 | CT secondary: 1 or 5 (A); 333, 100 or 80-200 for mV, Rogowski or mA CTs. | UINT16 | Read/write | ||||
| HR | 4109doc 100DH | Demand Slid Window Time | Demand window, 1-30 minutes. | UINT16 | min | Read/write | |||
| HR | 4110doc 100EH | Demand Calculating Mode | UINT16 | Read/write | 1 = Sliding window; 2 = Thermal | ||||
| HR | 4111doc 100FH | Clear Demand Memory | Write 1 to clear demand memory. | UINT16 | Read/write | ||||
| HR | 4112doc 1010H | Max/Min Clear | Write 0x0A to clear max/min records. | UINT16 | Read/write | ||||
| HR | 4113doc 1011H | Run Time Clear | Write 1 to clear the run-time counter. | UINT16 | Read/write | ||||
| HR | 4117doc 1015H | VAR/PF Convention | UINT16 | Read/write | 0 = IEC; 1 = IEEE | ||||
| HR | 4118doc 1016H | Energy Clear | Write 1 to clear the energy counters. | UINT16 | Read/write | ||||
| HR | 4119doc 1017H | Energy Calculating Mode | UINT16 | Read/write | 0 = Fundamental; 1 = Full-wave (true RMS) | ||||
| HR | 4121doc 1019H | Energy Display Mode | Selects primary or secondary scaling of the energy registers. | UINT16 | Read/write | 0 = Primary; 1 = Secondary | |||
| HR | 4125doc 101DH | Basic Parameter Mode | Selects primary or secondary values in the 4000H measurement block. | UINT16 | Read/write | 0 = Secondary; 1 = Primary | |||
| HR | 4142doc 102EH | System Status | New-event flags. | BITMAP16 | Read | bit 0 = New alarm; bit 1 = New SOE record | |||
| HR | 4143doc 102FH | Baud Rate 2 | Baud rate of the second (module) port. | UINT16 | bps | Read/write | |||
| HR | 4144doc 1030H | Parity Setting 2 | Parity of the second (module) port. | UINT16 | Read/write | 0 = Even; 1 = Odd; 2 = None, 2 stop bits; 3 = None, 1 stop bit | |||
| HR | 4145doc 1031H | Communication Address2 | Address of the second (module) port, 1-247. | UINT16 | Read | ||||
| HR | 4148doc 1034H (High) / 1035H (Low) | Run Time | Run-time counter; high word at 1034H, low word at 1035H. | UINT32 | ABCD | × 0.01 | h | Read | |
| HR | 4150doc 1036H | Expanded IO Modules Connecting Status | 1 = module connected. | BITMAP16 | Read | bit 0 = PXM1K-11; bit 1 = PXM1K-12; bit 2 = PXM1K-21; bit 3 = PXM1K-22; bit 4 = PXM1K-31; bit 5 = PXM1K-32 | |||
| HR | 16384doc 4000H~4001H | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| HR | 16386doc 4002H~4003H | Phase Voltage V1 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | V | Read | ||
| HR | 16388doc 4004H~4005H | Phase Voltage V2 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | V | Read | ||
| HR | 16390doc 4006H~4007H | Phase Voltage V3 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | V | Read | ||
| HR | 16392doc 4008H~4009H | Average Voltage Vavg | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | V | Read | ||
| HR | 16394doc 400AH~400BH | Line Voltage V12 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | V | Read | ||
| HR | 16396doc 400CH~400DH | Line Voltage V23 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | V | Read | ||
| HR | 16398doc 400EH~400FH | Line Voltage V31 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | V | Read | ||
| HR | 16400doc 4010H~4011H | Average Line Voltage Vlavg | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | V | Read | ||
| HR | 16402doc 4012H~4013H | Current I1 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | A | Read | ||
| HR | 16404doc 4014H~4015H | Current I2 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | A | Read | ||
| HR | 16406doc 4016H~4017H | Current I3 | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | A | Read | ||
| HR | 16408doc 4018H~4019H | Average Current Iavg | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | A | Read | ||
| HR | 16410doc 401AH~401BH | Neutral Current In | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | A | Read | ||
| HR | 16412doc 401CH~401DH | Phase A Power Pa | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | W | Read | ||
| HR | 16414doc 401EH~401FH | Phase B Power Pb | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | W | Read | ||
| HR | 16416doc 4020H~4021H | Phase C Power Pc | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | W | Read | ||
| HR | 16418doc 4022H~4023H | System Power Psum | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | W | Read | ||
| HR | 16420doc 4024H~4025H | Phase A Reactive Power Qa | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | var | Read | ||
| HR | 16422doc 4026H~4027H | Phase B Reactive Power Qb | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | var | Read | ||
| HR | 16424doc 4028H~4029H | Phase C Reactive Power Qc | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | var | Read | ||
| HR | 16426doc 402AH~402BH | System Reactive Power Qsum | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | var | Read | ||
| HR | 16428doc 402CH~402DH | Phase A Apparent Power Sa | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | VA | Read | ||
| HR | 16430doc 402EH~402FH | Phase B Apparent Power Sb | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | VA | Read | ||
| HR | 16432doc 4030H~4031H | Phase C Apparent Power Sc | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | VA | Read | ||
| HR | 16434doc 4032H~4033H | System Apparent Power Ssum | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | VA | Read | ||
| HR | 16436doc 4034H~4035H | Phase A Power Factor PFa | FLOAT32 | ABCD | Read | ||||
| HR | 16438doc 4036H~4037H | Phase B Power Factor PFb | FLOAT32 | ABCD | Read | ||||
| HR | 16440doc 4038H~4039H | Phase C Power Factor PFc | FLOAT32 | ABCD | Read | ||||
| HR | 16442doc 403AH~403BH | System Power Factor PFsum | FLOAT32 | ABCD | Read | ||||
| HR | 16444doc 403CH~403DH | Voltage Unbalance Factor U_unbl | Register holds a fraction; percent = value x 100. | FLOAT32 | ABCD | × 100 | % | Read | |
| HR | 16446doc 403EH~403FH | Current Unbalance Factor I_unbl | Register holds a fraction; percent = value x 100. | FLOAT32 | ABCD | × 100 | % | Read | |
| HR | 16450doc 4042H~4043H | Power Demand | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | W | Read | ||
| HR | 16452doc 4044H~4045H | Reactive Power Demand | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | var | Read | ||
| HR | 16454doc 4046H~4047H | Apparent Power Demand | Secondary-side unless Basic Parameter Mode (101DH) = 1. | FLOAT32 | ABCD | VA | Read | ||
| HR | 16456doc 4048H~4049H | Energy IMP | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kWh | Read/write | |
| HR | 16458doc 404AH~404BH | Energy EXP | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kWh | Read/write | |
| HR | 16460doc 404CH~404DH | Reactive Energy IMP | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kvarh | Read/write | |
| HR | 16462doc 404EH~404FH | Reactive Energy EXP | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kvarh | Read/write | |
| HR | 16464doc 4050H~4051H | Energy TOTAL | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kWh | Read/write | |
| HR | 16466doc 4052H~4053H | Energy NET | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kWh | Read/write | |
| HR | 16468doc 4054H~4055H | Reactive Energy TOTAL | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kvarh | Read/write | |
| HR | 16470doc 4056H~4057H | Reactive Energy NET | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kvarh | Read/write | |
| HR | 16472doc 4058H~4059H | Apparent Energy | Primary, 0.1 steps at default 1019H = 0; secondary-side 0.001 steps if 1. | UINT32 | ABCD | × 0.1 | kVAh | Read/write | |
| HR | 16474doc 405AH | THD of V1 (V12) | UINT16 | × 0.01 | % | Read | |||
| HR | 16475doc 405BH | THD of V2 (V31) | UINT16 | × 0.01 | % | Read | |||
| HR | 16476doc 405CH | THD of V3 (V23) | UINT16 | × 0.01 | % | Read | |||
| HR | 16477doc 405DH | Average THD_V | UINT16 | × 0.01 | % | Read | |||
| HR | 16478doc 405EH | THD_I1 | UINT16 | × 0.01 | % | Read | |||
| HR | 16479doc 405FH | THD_I2 | UINT16 | × 0.01 | % | Read | |||
| HR | 16480doc 4060H | THD_I3 | UINT16 | × 0.01 | % | Read | |||
| HR | 16481doc 4061H | Average THD_I | UINT16 | × 0.01 | % | Read | |||
| HR | 17056doc 42A0H | Phase angle V2 to V1 (V23 to V12) | Range 0-360.0 degrees. | UINT16 | × 0.1 | ° | Read | ||
| HR | 17057doc 42A1H | Phase angle V3 to V1 (V31 to V12) | Range 0-360.0 degrees. | UINT16 | × 0.1 | ° | Read | ||
| HR | 17058doc 42A2H | Phase angle I1 to V1 (V12) | Range 0-360.0 degrees. | UINT16 | × 0.1 | ° | Read | ||
| HR | 17059doc 42A3H | Phase angle I2 to V1 (V12) | Range 0-360.0 degrees. | UINT16 | × 0.1 | ° | Read | ||
| HR | 17060doc 42A4H | Phase angle I3 to V1 (V12) | Range 0-360.0 degrees. | UINT16 | × 0.1 | ° | Read |
Notes on this map
- IMPORTANT - primary vs secondary: the 4000H measurement block (voltages, currents, powers and power demand) holds real primary values only when Basic Parameter Mode (101DH) = 1. The manual's default is 0 = Secondary, where voltages must be multiplied by PT1/PT2, currents by CT1/CT2 and powers by both (use CT2 = 5 only for a 5 A CT secondary, otherwise 1). Every affected register says so; scale 1 and the units here assume Primary mode. Frequency, power factor and unbalance are not affected.
- Word order: the manual defines Dword as high word first, and its function-03 example returns frequency 4000H-4001H as 42 48 00 00 (50.00 Hz) with the high word in the first register. Its function-16 energy example writes 0A9D then 4089. All 32-bit values here are ABCD.
- Left out: current demand 4600H-4605H. Its table gives only the secondary formula with format code F1 and does not say whether Basic Parameter Mode (101DH) applies, so its scaling is ambiguous.
- Energy registers 4048H-4059H: scale 0.1 kWh / kvarh / kVAh applies to primary energy (format codes F4-F6), which is the default Energy Display Mode (1019H = 0). If 1019H is set to 1 (Secondary) the same registers hold secondary energy in 0.001 units (F7-F9). The manual prints the apparent energy unit as kVA; kVAh is used here.
- The system-parameter table prints address 0ffdH twice (Frequency and First Communication Protocol). The manual's notes and its sealed-parameter table both put the protocol at 0FFEH, so Frequency is kept at 0FFDH and the protocol at 0FFEH.
- Left out: PT1 (1005H, printed as a 32-bit 'Unit 32' with a one-decimal range but no stated scaling) and PT2 (1007H, a word with a one-decimal default of 220.0 but no stated scaling). The PT ratio still matters when Basic Parameter Mode is Secondary.
- Left out: password (1000H), the 100 ms refresh block 3000H (always secondary values, duplicates 4000H), the standard-register block 2000H (duplicates), the load-characteristic register 4040H (an ASCII code stored in a float), individual harmonics, max/min records with timestamps, sequence components, alarm, SOE and data-log blocks, per-phase energy (4620H-463DH), pulse counters and analog I/O.
- Digital inputs DI7-DI28 and relays 5-8 follow the same pattern on further I/O modules (see manual Tables 76-77); only the first modules' points are listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
What Modbus registers does the Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300) have?
This map lists 92 registers: 4 coils, 6 discrete inputs, 82 holding registers. 34 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints register addresses in hex (4000H, 1001H). They go on the wire unchanged: its read example for frequency at 4000H sends start address bytes 40 00. Relays and digital inputs start at 0000H.
What byte order does the Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)?
Start with HR 16384 Frequency (Frequency (4000H)); HR 16386 Phase Voltage V1 (Phase voltage V1 (4002H)); HR 16402 Current I1 (Current I1 (4012H)); HR 16418 System Power Psum (Total active power (4022H)); HR 16442 System Power Factor PFsum (System power factor (403AH)); HR 16456 Energy IMP (Imported active energy (4048H)); HR 4125 Basic Parameter Mode (Basic Parameter Mode, set to 1 for primary values (101DH)).
How do I enable Modbus control of the Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)?
Modbus RTU is the default protocol on the built-in RS-485 port (0FFEH = 0). Settings are written with function 16 (10H); one write may only touch registers inside a single settings region. To get primary-unit readings, write 1 to Basic Parameter Mode (101DH). This write is refused while the meter is sealed.
Where is the official Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300) Modbus documentation?
The source is PXM 1000 User Manual (MN150009EN), revision 2018-10, published free by Eaton at https://www.eaton.com/content/dam/eaton/products/low-voltage-power-distribution-controls-systems/power-energy-meters/power-xpert-meter-1000/power-xpert-meter-1000-user-manual-mn15009en.pdf.
More Eaton Modbus register maps
Source: PXM 1000 User Manual · MN150009EN · rev. 2018-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.