 "manufacturer": "Eaton",
 "manufacturer_slug": "eaton",
 "model": "S611 soft starter (via C441 Ethernet module)",
 "model_slug": "s611-soft-starter",
 "short_model": "S611",
 "aliases": [
  "S611",
  "S611 soft starter",
  "C441R",
  "C441T"
 ],
 "equipment_type": "Soft starter",
 "applies_to": "Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.",
 "summary": "The S611 is an Eaton soft starter with built-in motor protection and metering. Through the C441 Ethernet module its data is served over Modbus TCP and RS-485 Modbus RTU. This map covers adapter I/O and comms registers, motor status and metering (300-338), the run/permissive/reset control word (400) and the start, protection and comm-loss settings (401-445).",
 "transport": [
  "TCP",
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 1,
  "baud": 19200,
  "parity": "Even",
  "data_bits": null,
  "stop_bits": 1,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0)."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V)",
  "doc_number": "MN04200002E",
  "revision_date": "2012-08",
  "url": "https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf",
  "pages": "pp. 56-59 (section 7.4, Table 98)",
  "unofficial": true
 },
 "notes": [
  "Source is a distributor copy (precision-elec.com) of Eaton manual MN04200002E dated August 2012. Eaton lists a later edition (January 2016) at eaton.com, which could not be downloaded from this machine; check it for changes.",
  "The tables print 1-based Modbus register numbers: the production/consumption-list note says field inputs register 1 is register address 0 (address = register number - 1).",
  "All registers listed are single 16-bit words. Multi-word items (32-bit adapter serial number at 7, firmware/hardware revision at 9/11, IP addresses 144-154, MAC address 156) have no stated word order or layout and are left out. Signedness is not stated; values are typed unsigned.",
  "The same map is served over Modbus TCP and over the adapter's RS-485 Modbus RTU port; functions 01/02/03/04/05/06/15/16/23 and 43/14 are supported. Coil numbers in the manual are bit views of the same registers and are not listed here.",
  "Registers 1000-4000 are a user-configurable production/consumption list (custom register block); not expanded here.",
  "Currents 302-305 must be divided using the current scale factor in register 301 (the manual does not define the factor further), so they are left unscaled here.",
  "Fault code 325 starts a fault queue read newest first.",
  "Firmware registers 335/336 and the change-tracker queue 399 are left out (no description in the manual); command code 250 is marked unpublished and left out.",
  "Defaults are those printed for the C441R/C441T serial monitoring port (address 1, 19.2k, even parity, 1 stop bit, RTU); data bits and the Modbus TCP port are not stated.",
  "Residual ground fault current 317 and trip level 419 are printed as 'Scaling = x100' with no unit; they are scaled 0.01 here and the unit is left blank."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Field inputs",
   "description": "Adapter input points.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input 1",
    "1": "Input 2",
    "2": "Input 3",
    "3": "Input 4"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Control voltage",
   "description": "Adapter supply voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "DIP switch value",
   "description": "Present DIP switch state.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "101",
   "name": "Field relay outputs",
   "description": "Adapter output relays.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Output 1",
    "1": "Output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "110",
   "name": "Modbus TCP com timeout",
   "description": "0 = disabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "111",
   "name": "Field relay fault action",
   "description": "Per relay: 0 = apply fault value, 1 = no change.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "112",
   "name": "Field relay fault state",
   "description": "Per relay value on comm fault: 0 off, 1 on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "113",
   "name": "Field relay idle action",
   "description": "Per relay: 0 = apply idle value, 1 = no change.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "114",
   "name": "Field relay idle state",
   "description": "Per relay value on comm idle: 0 off, 1 on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "143",
   "name": "IP allocation method",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "DHCP",
    "1": "Upper 3 octets from NV, last octet from DIP switches",
    "2": "Full address from NV memory",
    "3": "Restore 192.168.1.254"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "159",
   "name": "Modbus serial com timeout",
   "description": "0 = disabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 159,
   "documented": "160",
   "name": "Modbus TX mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RTU",
    "1": "ASCII"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "161",
   "name": "Modbus baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "19200",
    "1": "9600",
    "2": "57600",
    "3": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "162",
   "name": "Modbus address",
   "description": "Serial slave address loaded at start-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "163",
   "name": "Modbus parity and stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even, 1 stop",
    "1": "Odd, 1 stop",
    "2": "None, 2 stop",
    "3": "Even, 2 stop",
    "4": "Odd, 2 stop",
    "5": "None, 1 stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "201",
   "name": "Intercom status",
   "description": "Link between adapter and host device.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Connected fully, no errors",
    "1": "Message fault occurred",
    "2": "Devices married, target identified",
    "3": "Basic connection established"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 250,
   "documented": "251",
   "name": "Motor ctrl idle loss act disable",
   "description": "1 = keep motor state on comm idle; 0 = apply idle value (252).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 251,
   "documented": "252",
   "name": "Motor ctrl com idle action value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (no change)",
    "1": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "253",
   "name": "Motor ctrl com loss act disable",
   "description": "1 = keep motor state on comm loss; 0 = apply loss value (254).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 253,
   "documented": "254",
   "name": "Motor ctrl com loss action value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (no change)",
    "1": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 299,
   "documented": "300",
   "name": "Motor status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Run",
    "2": "In bypass",
    "5": "Fault",
    "11": "Relay 1 state",
    "12": "Relay 2 state",
    "13": "Control from network",
    "14": "Permissive state"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 300,
   "documented": "301",
   "name": "Current scale factor",
   "description": "Factor used to scale 302-305.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 301,
   "documented": "302",
   "name": "Phase A RMS current",
   "description": "Scaled by register 301.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 302,
   "documented": "303",
   "name": "Phase B RMS current",
   "description": "Scaled by register 301.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 303,
   "documented": "304",
   "name": "Phase C RMS current",
   "description": "Scaled by register 301.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "305",
   "name": "Average current",
   "description": "Scaled by register 301.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 305,
   "documented": "306",
   "name": "Vab RMS voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "307",
   "name": "Vbc RMS voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 307,
   "documented": "308",
   "name": "Vca RMS voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 308,
   "documented": "309",
   "name": "Average voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 309,
   "documented": "310",
   "name": "Total kilowatts",
   "description": "Printed scale factor x10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 310,
   "documented": "311",
   "name": "Apparent power factor",
   "description": "Power factor x 100.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 311,
   "documented": "312",
   "name": "Power sign",
   "description": "Tells whether power is positive or negative (generating).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 312,
   "documented": "313",
   "name": "Line frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 313,
   "documented": "314",
   "name": "Overload thermal memory",
   "description": "100% causes an overload trip.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "315",
   "name": "Current unbalance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 315,
   "documented": "316",
   "name": "Voltage unbalance",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 316,
   "documented": "317",
   "name": "Residual ground fault current",
   "description": "Scaling x100.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 317,
   "documented": "318",
   "name": "Phase A pole temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 318,
   "documented": "319",
   "name": "Phase B pole temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 319,
   "documented": "320",
   "name": "Phase C pole temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 320,
   "documented": "321",
   "name": "Average pole temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 321,
   "documented": "322",
   "name": "Number of starts",
   "description": "Resettable via 402.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 322,
   "documented": "323",
   "name": "Total run time",
   "description": "Resettable via 402.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "h",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 323,
   "documented": "324",
   "name": "Trip reason",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Overload",
    "1": "Jam",
    "2": "Stall",
    "3": "Current imbalance",
    "4": "Load disconnect",
    "5": "Phase loss",
    "6": "Mains fault",
    "7": "Phase reversal",
    "8": "Shorted SCR",
    "9": "SCR not firing",
    "10": "Pole over-temperature",
    "11": "Bypass dropout",
    "12": "SCR overcurrent",
    "13": "Contactor overcurrent",
    "14": "Communication fault",
    "15": "Other device fault"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 324,
   "documented": "325",
   "name": "Fault code",
   "description": "Most recent fault when read as one register.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 336,
   "documented": "337",
   "name": "UI firmware version",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 337,
   "documented": "338",
   "name": "Unit ID",
   "description": "Product identifier.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 399,
   "documented": "400",
   "name": "Motor control",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run",
    "2": "Permissive",
    "3": "Reset"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 400,
   "documented": "401",
   "name": "Start input behavior",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Edge",
    "1": "Level"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 401,
   "documented": "402",
   "name": "Command register",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Clear motor run hours",
    "2": "Clear motor start count",
    "3": "Clear fault queue",
    "255": "Force overload reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 402,
   "documented": "403",
   "name": "Configuration reset",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Soft reset",
    "2": "Factory defaults"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 403,
   "documented": "404",
   "name": "Overload FLA",
   "description": "Scaling x10.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 404,
   "documented": "405",
   "name": "Rated voltage",
   "description": "Motor rated voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 405,
   "documented": "406",
   "name": "Start method",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Vramp (voltage ramp)",
    "1": "Limit",
    "2": "Pump"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 406,
   "documented": "407",
   "name": "Start time",
   "description": "Start ramp time.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 407,
   "documented": "408",
   "name": "Initial torque",
   "description": "Starting torque percent.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 408,
   "documented": "409",
   "name": "Stop time",
   "description": "Stop ramp time.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 409,
   "documented": "410",
   "name": "Pump stop time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 410,
   "documented": "411",
   "name": "Kick start time",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 411,
   "documented": "412",
   "name": "Kick start initial torque",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 412,
   "documented": "413",
   "name": "Reset mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Manual",
    "1": "Auto"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 413,
   "documented": "414",
   "name": "Fault enable bits",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Overload",
    "1": "Jam",
    "2": "Stall",
    "3": "Current imbalance",
    "4": "Load disconnect",
    "5": "Phase loss",
    "6": "Under voltage",
    "7": "Over voltage",
    "8": "Voltage unbalance",
    "9": "Phase reversal",
    "10": "Ground fault",
    "11": "Overload on start",
    "12": "Shorted SCR",
    "13": "SCR not firing",
    "14": "Over temperature"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 414,
   "documented": "415",
   "name": "Overload class",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 415,
   "documented": "416",
   "name": "Jam trip level",
   "description": "Percent of FLA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 416,
   "documented": "417",
   "name": "Jam trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 417,
   "documented": "418",
   "name": "Stall trip level",
   "description": "Percent of FLA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 418,
   "documented": "419",
   "name": "Residual GF trip level",
   "description": "Scaling x100.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 419,
   "documented": "420",
   "name": "Residual GF trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 420,
   "documented": "421",
   "name": "Residual GF start delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 421,
   "documented": "422",
   "name": "Current unbalance trip level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 422,
   "documented": "423",
   "name": "Current unbalance trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 423,
   "documented": "424",
   "name": "Load disconnect trip level",
   "description": "Percent of rated FLA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 424,
   "documented": "425",
   "name": "Load disconnect trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 425,
   "documented": "426",
   "name": "Load disconnect source",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Under power",
    "1": "Under current"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 426,
   "documented": "427",
   "name": "Phase loss trip level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 427,
   "documented": "428",
   "name": "Phase loss trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 428,
   "documented": "429",
   "name": "Under voltage level",
   "description": "Percent of set voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 429,
   "documented": "430",
   "name": "Under voltage trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 430,
   "documented": "431",
   "name": "Over voltage level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 431,
   "documented": "432",
   "name": "Over voltage trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 432,
   "documented": "433",
   "name": "Voltage unbalance trip level",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 433,
   "documented": "434",
   "name": "Voltage unbalance trip delay",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 434,
   "documented": "435",
   "name": "Phase sequence",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "ABC",
    "2": "ACB"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 435,
   "documented": "436",
   "name": "Fault relay config",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Faulted",
    "1": "Not faulted"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 436,
   "documented": "437",
   "name": "Auxiliary relay configuration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Faulted",
    "1": "Not faulted",
    "2": "Bypass",
    "3": "Not in bypass",
    "4": "Motor energized",
    "5": "Motor not energized"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 437,
   "documented": "438",
   "name": "UI edit lock",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Unlocked",
    "1": "Locked"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 442,
   "documented": "443",
   "name": "Communication loss timeout",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 443,
   "documented": "444",
   "name": "Communication loss behavior",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Fault",
    "2": "Hold last state",
    "3": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 444,
   "documented": "445",
   "name": "Network timeout enable",
   "description": "Network watchdog.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Enable"
   },
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll 300 for run/bypass/fault, 301-305 for current, 306-309 for voltage and 324 for trip bits. Start the motor by setting 400 bit 2 (permissive) and bit 0 (run); bit 3 resets a fault. Set 443-445 so the starter stops or faults when the network drops.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 299,
    "why": "Motor status bits"
   },
   {
    "table": "holding_register",
    "address": 304,
    "why": "Average current (scale by 301)"
   },
   {
    "table": "holding_register",
    "address": 300,
    "why": "Current scale factor"
   },
   {
    "table": "holding_register",
    "address": 308,
    "why": "Average voltage"
   },
   {
    "table": "holding_register",
    "address": 313,
    "why": "Thermal memory"
   },
   {
    "table": "holding_register",
    "address": 323,
    "why": "Trip reason bits"
   },
   {
    "table": "holding_register",
    "address": 399,
    "why": "Run / permissive / reset"
   }
  ],
  "enable": "Modbus TCP is served by the C441 Ethernet module; the IP is set by DHCP, NV memory or the DIP switches (register 143 shows the method; 192.168.1.254 is the restore address). Remote motor control also depends on the comm idle/loss settings 251-254.",
  "watchdog": "Register 110 (Modbus TCP) and 159 (serial) set a com timeout in ms (0 = off); 251-254 choose whether the motor stops or holds on comm idle or loss, and 111-114 set the adapter relays' fault and idle states.",
  "quirks": [
   "Register numbers are 1-based; subtract 1 on the wire.",
   "Coil numbers in the manual are bit views of registers (coil = 16 x (register - 1) + bit + 1), not separate data."
  ],
  "setup": [
   "Serial port settings live in 160-163 (mode, baud, address, parity/stop) where the table lists them.",
   "On a C441R/C441T the RS-485 port is an extra Modbus RTU/ASCII monitoring port that serves the same register map."
  ],
  "gotchas": [
   "Several values change scale with hardware or a scale register; check the notes before trusting raw numbers."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/eaton/s611-soft-starter",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}