 "manufacturer": "Eaton",
 "manufacturer_slug": "eaton",
 "model": "S811+ soft starter (via C441 Ethernet module)",
 "model_slug": "s811-plus-soft-starter",
 "short_model": "S811+",
 "aliases": [
  "S811+",
  "S811 Plus",
  "S811+ soft starter",
  "C441U",
  "C441V"
 ],
 "equipment_type": "Soft starter",
 "applies_to": "Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.",
 "summary": "The S811+ is Eaton's larger soft starter with full motor protection, metering and a configurable I/O block. Through the C441 Ethernet module it is reachable over Modbus TCP and RS-485 Modbus RTU. This map covers the adapter I/O registers, status, fault and warning words, single-word current, power and frequency monitors, the network control words (500/501) and the main protection and comm-loss settings.",
 "transport": [
  "TCP"
 ],
 "defaults": {
  "unit_id": null,
  "baud": null,
  "parity": null,
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "Tables print register numbers starting at 1; the manual states that the Modbus register address is the register number minus 1 (field inputs, register 1, is address 0). The manual itself calls the control words 'Modbus reg #500' and '#501'."
 },
 "default_word_order": null,
 "firmware": null,
 "source": {
  "title": "C441 Ethernet Module User Manual (C441R, C441T, C441U, C441V)",
  "doc_number": "MN04200002E",
  "revision_date": "2012-08",
  "url": "https://www.precision-elec.com/wp-content/uploads/2021/01/C441-Ethernet-Module-User-Manual-C441R-C441T-C441U-C441V.pdf",
  "pages": "pp. 59-64 (section 7.5, Table 99)",
  "unofficial": true
 },
 "notes": [
  "Source is a distributor copy (precision-elec.com) of Eaton manual MN04200002E dated August 2012. Eaton lists a later edition (January 2016) at eaton.com, which could not be downloaded from this machine; check it for changes.",
  "Only registers that are clearly one 16-bit word are listed. Items printed with a gap after them (fault/fault lists 301, 318, 370; mains voltage 308; starts 311; RMS line and pole current blocks 328-357 apart from the averages; pole temperature 362) have no stated length or word order and are left out, as is the float FLA at 600.",
  "Torque, ramp, stop and start-delay settings without printed units (609-613, 615-622, 641, 681-683) and several trip thresholds without units in the table (652, 655, 657, 673, 674) are left out.",
  "Registers 503-507 are the S811+'s own Modbus port settings (baud default 19200, RTU default). With a C441U/C441V that port is the link to the adapter, so integrators reach this map over Modbus TCP; the adapter's serial settings are 159-163.",
  "Signedness is not stated in the manual; values are typed unsigned."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 0,
   "documented": "1",
   "name": "Field inputs",
   "description": "Adapter input points.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Input 1",
    "1": "Input 2",
    "2": "Input 3",
    "3": "Input 4"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 1,
   "documented": "2",
   "name": "Control voltage",
   "description": "Adapter supply voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "mV",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 4,
   "documented": "5",
   "name": "DIP switch value",
   "description": "Present DIP switch state.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 100,
   "documented": "101",
   "name": "Field relay outputs",
   "description": "Adapter output relays.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Output 1",
    "1": "Output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 109,
   "documented": "110",
   "name": "Modbus TCP com timeout",
   "description": "0 = disabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 110,
   "documented": "111",
   "name": "Field relay fault action",
   "description": "Per relay: 0 = apply fault value, 1 = no change.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 111,
   "documented": "112",
   "name": "Field relay fault state",
   "description": "Per relay value on comm fault: 0 off, 1 on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 112,
   "documented": "113",
   "name": "Field relay idle action",
   "description": "Per relay: 0 = apply idle value, 1 = no change.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 113,
   "documented": "114",
   "name": "Field relay idle state",
   "description": "Per relay value on comm idle: 0 off, 1 on.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Relay / output 1",
    "1": "Relay / output 2"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 142,
   "documented": "143",
   "name": "IP allocation method",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "DHCP",
    "1": "Upper 3 octets from NV, last octet from DIP switches",
    "2": "Full address from NV memory",
    "3": "Restore 192.168.1.254"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 158,
   "documented": "159",
   "name": "Modbus serial com timeout",
   "description": "0 = disabled.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 159,
   "documented": "160",
   "name": "Modbus TX mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RTU",
    "1": "ASCII"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 160,
   "documented": "161",
   "name": "Modbus baud rate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "19200",
    "1": "9600",
    "2": "57600",
    "3": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 161,
   "documented": "162",
   "name": "Modbus address",
   "description": "Serial slave address loaded at start-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 162,
   "documented": "163",
   "name": "Modbus parity and stop bits",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even, 1 stop",
    "1": "Odd, 1 stop",
    "2": "None, 2 stop",
    "3": "Even, 2 stop",
    "4": "Odd, 2 stop",
    "5": "None, 1 stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 200,
   "documented": "201",
   "name": "Intercom status",
   "description": "Link between adapter and host device.",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Connected fully, no errors",
    "1": "Message fault occurred",
    "2": "Devices married, target identified",
    "3": "Basic connection established"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 252,
   "documented": "253",
   "name": "Motor ctrl com idle act disable",
   "description": "1 = keep motor state on comm idle; 0 = apply idle value (254).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 253,
   "documented": "254",
   "name": "Motor ctrl com idle action value",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ignore (no change)",
    "1": "Stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 299,
   "documented": "300",
   "name": "Motor control status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Running1 (RUN1 active)",
    "1": "Running2 (jog active)",
    "2": "Permissive (start allowed)",
    "3": "Ramp2 settings active",
    "4": "Local control (0 = network)",
    "5": "Faulted",
    "6": "Warning (self-clearing)",
    "7": "In bypass"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 303,
   "documented": "304",
   "name": "Motor control faults",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase loss",
    "1": "Phase imbalance",
    "2": "Thermal pile",
    "3": "Overcurrent",
    "4": "Breaker fault",
    "5": "Ground fault",
    "6": "Motor stall",
    "7": "Motor jam",
    "8": "Over-temperature",
    "9": "Underload",
    "15": "Other",
    "11": "E-stop"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 304,
   "documented": "305",
   "name": "Motor control warnings",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Phase loss",
    "1": "Phase imbalance",
    "2": "Thermal pile",
    "3": "Overcurrent",
    "4": "Breaker fault",
    "5": "Ground fault",
    "6": "Motor stall",
    "7": "Motor jam",
    "8": "Over-temperature",
    "9": "Underload",
    "15": "Other"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 305,
   "documented": "306",
   "name": "Average current % FLA",
   "description": "Average phase current as percent of nameplate FLA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 306,
   "documented": "307",
   "name": "Thermal pile used",
   "description": "Trips at 100%.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 312,
   "documented": "313",
   "name": "Analog input value",
   "description": "Percent of the selected range.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 313,
   "documented": "314",
   "name": "Analog input status",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "Not active",
    "1": "Under range",
    "2": "Over range",
    "3": "In overdrive",
    "4": "In range"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 314,
   "documented": "315",
   "name": "Discrete input status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Terminal input 1",
    "1": "Terminal input 2",
    "2": "Terminal input 3",
    "3": "Terminal input 4",
    "4": "Network input 1 (C441 input 1)",
    "5": "Network input 2 (C441 input 2)",
    "6": "Network input 3 (C441 input 3)",
    "7": "Network input 4 (C441 input 4)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 315,
   "documented": "316",
   "name": "Discrete output status",
   "description": "",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": {
    "0": "Form A relay",
    "1": "Form C relay",
    "2": "Network output 1 (C441 output 1)",
    "3": "Network output 2 (C441 output 2)"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 335,
   "documented": "336",
   "name": "Average line current (A)",
   "description": "Motor line current, 1 A units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 339,
   "documented": "340",
   "name": "Average line current (0.1 A)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 351,
   "documented": "352",
   "name": "Average pole current (A)",
   "description": "Current through the power poles, 1 A units.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 355,
   "documented": "356",
   "name": "Average pole current (0.1 A)",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 359,
   "documented": "360",
   "name": "Power factor",
   "description": "0 to 1.0000.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.0001,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 360,
   "documented": "361",
   "name": "Average 3-phase real power",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "kW",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 364,
   "documented": "365",
   "name": "DC control voltage",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.001,
   "units": "V",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 365,
   "documented": "366",
   "name": "Device temperature",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "°C",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 366,
   "documented": "367",
   "name": "Auto reset count",
   "description": "Auto reset attempts so far.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 367,
   "documented": "368",
   "name": "Line frequency",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.01,
   "units": "Hz",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 368,
   "documented": "369",
   "name": "Incoming phase sequence",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": {
    "0": "ABC",
    "1": "ACB"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 379,
   "documented": "380",
   "name": "Application status",
   "description": "Last active fault.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 499,
   "documented": "500",
   "name": "Modbus motor control word",
   "description": "Three-wire control (687 = 0).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run1 start (edge)",
    "1": "Jog (level)",
    "2": "Permissive (level, must be 1 to start)",
    "3": "Fault reset",
    "7": "Ramp2 profile"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 500,
   "documented": "501",
   "name": "Modbus two-wire motor control word",
   "description": "Two-wire control (687 = 1).",
   "data_type": "BITMAP16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": {
    "0": "Run1 (level)",
    "1": "Jog (level)",
    "3": "Fault reset",
    "7": "Ramp2 profile"
   },
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 502,
   "documented": "503",
   "name": "Modbus baud rate",
   "description": "S811+ port; applied at power-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "1200",
    "1": "2400",
    "2": "4800",
    "3": "9600",
    "4": "19200 (default)",
    "5": "38400",
    "6": "57600",
    "7": "115200"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 503,
   "documented": "504",
   "name": "Modbus node address",
   "description": "From the DIP switches; read at power-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 504,
   "documented": "505",
   "name": "Modbus parity",
   "description": "Applied at power-up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Even, 1 stop",
    "1": "Odd, 1 stop",
    "2": "None, 2 stop"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 506,
   "documented": "507",
   "name": "Modbus mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RTU (default)",
    "1": "ASCII"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 601,
   "documented": "602",
   "name": "Motor nameplate FLA",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "A",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 602,
   "documented": "603",
   "name": "Overload trip class",
   "description": "5-30, default 20.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 605,
   "documented": "606",
   "name": "Motor wiring configuration",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Inline (default)",
    "1": "Inside the delta"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 606,
   "documented": "607",
   "name": "Expected incoming phase sequence",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "ABC",
    "1": "ACB"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 607,
   "documented": "608",
   "name": "Motor start method",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Ramp start (voltage ramp)",
    "1": "Current limit",
    "3": "Pump start"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 613,
   "documented": "614",
   "name": "Kickstart duration",
   "description": "0.0-2.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 622,
   "documented": "623",
   "name": "Local control only enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled (network control possible)",
    "1": "Enabled (terminal block only)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 639,
   "documented": "640",
   "name": "Fault reset mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Manual",
    "1": "Auto",
    "2": "Power-on reset"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 642,
   "documented": "643",
   "name": "Overload trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 643,
   "documented": "644",
   "name": "Overload during start",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disabled during start ramp",
    "1": "Enabled during start ramp"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 644,
   "documented": "645",
   "name": "Phase reversal trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 645,
   "documented": "646",
   "name": "Undercurrent trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 646,
   "documented": "647",
   "name": "Undercurrent trip level",
   "description": "Percent of nameplate FLA.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 647,
   "documented": "648",
   "name": "Undercurrent trip duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 648,
   "documented": "649",
   "name": "Motor jam trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 649,
   "documented": "650",
   "name": "Motor stall trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 650,
   "documented": "651",
   "name": "Phase loss trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 652,
   "documented": "653",
   "name": "Phase loss duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 653,
   "documented": "654",
   "name": "Phase imbalance trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 655,
   "documented": "656",
   "name": "Phase imbalance trip duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 657,
   "documented": "658",
   "name": "Voltage imbalance trip duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 658,
   "documented": "659",
   "name": "Under voltage trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 659,
   "documented": "660",
   "name": "Under voltage trip threshold",
   "description": "Percent of rated motor voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 660,
   "documented": "661",
   "name": "Under voltage trip duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 661,
   "documented": "662",
   "name": "Over voltage trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 662,
   "documented": "663",
   "name": "Over voltage trip threshold",
   "description": "Percent of rated motor voltage.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 663,
   "documented": "664",
   "name": "Over voltage trip duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 664,
   "documented": "665",
   "name": "Line frequency trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 665,
   "documented": "666",
   "name": "Frequency deviation trip threshold",
   "description": "Percent of rated line frequency.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 666,
   "documented": "667",
   "name": "Frequency trip duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 667,
   "documented": "668",
   "name": "Average power trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 668,
   "documented": "669",
   "name": "Low power trip threshold",
   "description": "Percent of rated W (sqrt3 x 0.8 x FLA x rated V).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 669,
   "documented": "670",
   "name": "High power trip threshold",
   "description": "Percent of rated W.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "%",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 670,
   "documented": "671",
   "name": "Power trip duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 671,
   "documented": "672",
   "name": "Analog input trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 674,
   "documented": "675",
   "name": "Analog input trip duration",
   "description": "0.0-60.0 s.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 675,
   "documented": "676",
   "name": "Temperature sensor trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 676,
   "documented": "677",
   "name": "SCR not firing trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 677,
   "documented": "678",
   "name": "SCR shorted trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 683,
   "documented": "684",
   "name": "Motor comm loss action",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Auto stop",
    "1": "Auto run1",
    "3": "Hold last state",
    "7": "All-stop fault (trips)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 686,
   "documented": "687",
   "name": "Network two-wire control enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "3-wire control (register 500)",
    "1": "2-wire control (register 501)"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 687,
   "documented": "688",
   "name": "Ground fault trip enable",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Disable",
    "1": "Fault enable",
    "2": "Warning enable"
   },
   "bits": null,
   "offset": 0
  },
  {
   "table": "holding_register",
   "address": 688,
   "documented": "689",
   "name": "Ground fault inhibit from start delay",
   "description": "0.0-20.0 s after the start ramp.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 0.1,
   "units": "s",
   "access": "RW",
   "values": null,
   "bits": null,
   "offset": 0
  }
 ],
 "integration": {
  "summary": "Poll 300 for running/faulted/bypass state, 304/305 for fault and warning bits, 340 for average line current (0.1 A) and 361 for kW. Control the motor with register 500 (permissive bit 2 plus run bit 0) or 501 in two-wire mode, and set 684 for comm-loss behaviour.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 299,
    "why": "Status word"
   },
   {
    "table": "holding_register",
    "address": 303,
    "why": "Fault bits"
   },
   {
    "table": "holding_register",
    "address": 304,
    "why": "Warning bits"
   },
   {
    "table": "holding_register",
    "address": 339,
    "why": "Average line current"
   },
   {
    "table": "holding_register",
    "address": 360,
    "why": "Real power"
   },
   {
    "table": "holding_register",
    "address": 306,
    "why": "Thermal pile"
   },
   {
    "table": "holding_register",
    "address": 499,
    "why": "Network control word"
   }
  ],
  "enable": "Network control needs 623 = 0 (local-only off); 687 selects three-wire (500, which also needs permissive bit 2 set) or two-wire (501) control. Modbus TCP is served by the C441 module (IP via DHCP, NV memory or DIP switches).",
  "watchdog": "684 sets the motor's comm-loss action (auto stop, run, hold or all-stop fault); 686 is the comm idle timeout that raises a device-missing fault; 110/159 set adapter-level Modbus timeouts.",
  "quirks": [
   "Register numbers are 1-based; subtract 1 on the wire.",
   "Run1 in register 500 is edge-sensitive, but in 501 it is level-sensitive."
  ],
  "setup": [
   "S811+ Modbus settings 503 (baud) and 505 (parity) take effect only after a power cycle; the node address 504 is read from the DIP switches at power-up."
  ],
  "gotchas": [
   "Writing 101 (adapter relay outputs) can change the relay states."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/eaton/s811-plus-soft-starter",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}