 "manufacturer": "Endress+Hauser",
 "manufacturer_slug": "endress-hauser",
 "model": "Proline Prosonic Flow W 400 ultrasonic flowmeter (Modbus RS485)",
 "model_slug": "prosonic-flow-w-400-modbus",
 "short_model": "Prosonic Flow W 400",
 "aliases": [
  "Prosonic Flow W 400"
 ],
 "equipment_type": "Sensor (clamp-on ultrasonic flowmeter)",
 "applies_to": "Proline Prosonic Flow W 400 clamp-on flowmeter with the Modbus RS485 output, as described in GP01207D/06/EN/01.24.",
 "summary": "The Prosonic Flow W 400 is Endress+Hauser's clamp-on ultrasonic time-of-flight flowmeter. Its Modbus RS485 interface gives every operating parameter a fixed register. This map covers what an integrator needs: flow, velocity, sound velocity, temperature, signal diagnostics, three totalizers and their controls, units, diagnostics and the Modbus settings.",
 "transport": [
  "RTU",
  "ASCII"
 ],
 "defaults": {
  "unit_id": 247,
  "baud": 19200,
  "parity": "Even",
  "data_bits": null,
  "stop_bits": null,
  "tcp_port": null
 },
 "addressing": {
  "convention": "1-based",
  "note": "The manual prints registers in the Modbus Application Protocol form and equates them with Modicon 3XXXX/4XXXX numbers (its own example: 2007 = 32007); the scan-list parameter calls register addresses 1-based. Subtract 1 on the wire: volume flow at register 2007 is requested at 2006."
 },
 "default_word_order": "CDAB",
 "firmware": "Valid from device firmware 01.00.zz",
 "source": {
  "title": "Description of Device Parameters Proline Prosonic Flow W 400 Modbus RS485",
  "doc_number": "GP01207D/06/EN/01.24-00",
  "revision_date": "2024-05-15",
  "url": "https://bdih-download.endress.com/file/005056A5E3831EEF84BF247676F6F971/GP01207DEN_0124-00.pdf",
  "pages": "pp. 108-113 (Modbus settings, byte order), p. 174 (address model), pp. 190-206 (register tables)"
 },
 "notes": [
  "Integrator subset of a parameter manual that lists a register for every menu item; installation (pipe/sensor), I/O, display, WLAN and web-server parameters are left out.",
  "Float word order follows the Byte order parameter (register 4915). The factory setting 1-0-3-2 sends byte 1, byte 0, byte 3, byte 2, byte 3 being sign and exponent, so floats are CDAB. Changing Byte order changes every float.",
  "Integer parameters are 2 bytes and listed as UINT16; the manual does not state signedness and all codes shown are positive.",
  "All parameters read with function 03 or 04 and write with 06 or 16; they are listed as holding registers.",
  "The no-parity picklist codes differ between the parameter description (2 = None/1 stop bit) and the register table (2 = None/2 stop bits), so only Even (0) and Odd (1) are given.",
  "The diagnostic registers return an integer whose coding the manual does not list.",
  "String parameters (tag, serial number, firmware, order code) and the scan list (5001-5016) are left out because their packing depends on the byte order setting.",
  "Velocity unit sits at register 2600, right next to the totalizer 1 block (2601 and up); do not confuse them.",
  "Non-volatile writes go to EEPROM; avoid cyclic writes.",
  "The data-bit and stop-bit count for the Even/Odd parity settings is not stated in this manual, so those defaults are left blank."
 ],
 "registers": [
  {
   "table": "holding_register",
   "address": 2006,
   "documented": "2007 to 2008",
   "name": "Volume flow",
   "description": "Measured volume flow in the volume flow unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2008,
   "documented": "2009 to 2010",
   "name": "Mass flow",
   "description": "Mass flow from volume flow and density.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2010,
   "documented": "2011 to 2012",
   "name": "Density",
   "description": "Density used for the mass flow calculation.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2012,
   "documented": "2013 to 2014",
   "name": "Sound velocity",
   "description": "Measured sound velocity of the fluid.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2014,
   "documented": "2015 to 2016",
   "name": "Flow velocity",
   "description": "Average flow velocity in the pipe.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2016,
   "documented": "2017 to 2018",
   "name": "Temperature",
   "description": "Fluid temperature used by the device.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2100,
   "documented": "2101",
   "name": "Mass flow unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "g/s",
    "1": "g/min",
    "2": "g/h",
    "3": "g/d",
    "4": "kg/s",
    "5": "kg/min",
    "6": "kg/h",
    "7": "kg/d",
    "8": "t/s",
    "9": "t/min",
    "10": "t/h",
    "11": "t/d",
    "12": "oz/s",
    "13": "oz/min",
    "14": "oz/h",
    "15": "oz/d",
    "16": "lb/s",
    "17": "lb/min",
    "18": "lb/h",
    "19": "lb/d",
    "20": "STon/s",
    "21": "STon/min",
    "22": "STon/h",
    "23": "STon/d"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2101,
   "documented": "2102",
   "name": "Mass unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "50": "g",
    "51": "kg",
    "52": "t",
    "53": "oz",
    "54": "lb",
    "55": "STon"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2102,
   "documented": "2103",
   "name": "Volume flow unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "cm³/s",
    "1": "cm³/min",
    "2": "cm³/h",
    "3": "cm³/d",
    "4": "dm³/s",
    "5": "dm³/min",
    "6": "dm³/h",
    "7": "dm³/d",
    "8": "m³/s",
    "9": "m³/min",
    "10": "m³/h",
    "11": "m³/d",
    "12": "ml/s",
    "13": "ml/min",
    "14": "ml/h",
    "15": "ml/d",
    "16": "l/s",
    "17": "l/min",
    "18": "l/h",
    "19": "l/d",
    "20": "hl/s",
    "21": "hl/min",
    "22": "hl/h",
    "23": "hl/d",
    "24": "Ml/s",
    "25": "Ml/min",
    "26": "Ml/h",
    "27": "Ml/d",
    "32": "af/s",
    "33": "af/min",
    "34": "af/h",
    "35": "af/d",
    "36": "ft³/s",
    "37": "ft³/min",
    "38": "ft³/h",
    "39": "ft³/d",
    "40": "fl oz/s (us)",
    "41": "fl oz/min (us)",
    "42": "fl oz/h (us)",
    "43": "fl oz/d (us)",
    "44": "gal/s (us)",
    "45": "gal/min (us)",
    "46": "gal/h (us)",
    "47": "gal/d (us)",
    "48": "Mgal/s (us)",
    "49": "Mgal/min (us)",
    "50": "Mgal/h (us)",
    "51": "Mgal/d (us)",
    "52": "bbl/s (us;liq.)",
    "53": "bbl/min (us;liq.)",
    "54": "bbl/h (us;liq.)",
    "55": "bbl/d (us;liq.)",
    "56": "bbl/s (us;beer)",
    "57": "bbl/min (us;beer)",
    "58": "bbl/h (us;beer)",
    "59": "bbl/d (us;beer)",
    "60": "bbl/s (us;oil)",
    "61": "bbl/min (us;oil)",
    "62": "bbl/h (us;oil)",
    "63": "bbl/d (us;oil)",
    "64": "bbl/s (us;tank)",
    "65": "bbl/min (us;tank)",
    "66": "bbl/h (us;tank)",
    "67": "bbl/d (us;tank)",
    "68": "gal/s (imp)",
    "69": "gal/min (imp)",
    "70": "gal/h (imp)",
    "71": "gal/d (imp)",
    "72": "Mgal/s (imp)",
    "73": "Mgal/min (imp)",
    "74": "Mgal/h (imp)",
    "75": "Mgal/d (imp)",
    "76": "bbl/s (imp;beer)",
    "77": "bbl/min (imp;beer)",
    "78": "bbl/h (imp;beer)",
    "79": "bbl/d (imp;beer)",
    "80": "bbl/s (imp;oil)",
    "81": "bbl/min (imp;oil)",
    "82": "bbl/h (imp;oil)",
    "83": "bbl/d (imp;oil)",
    "88": "kgal/s (us)",
    "89": "kgal/min (us)",
    "90": "kgal/h (us)",
    "91": "kgal/d (us)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2103,
   "documented": "2104",
   "name": "Volume unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "cm³",
    "1": "dm³",
    "2": "m³",
    "3": "ml",
    "4": "l",
    "5": "hl",
    "8": "af",
    "9": "ft³",
    "10": "fl oz (us)",
    "11": "gal (us)",
    "12": "Mgal (us)",
    "13": "bbl (us;liq.)",
    "14": "bbl (us;beer)",
    "15": "bbl (us;oil)",
    "16": "bbl (us;tank)",
    "17": "gal (imp)",
    "18": "Mgal (imp)",
    "19": "bbl (imp;beer)",
    "20": "bbl (imp;oil)",
    "22": "kgal (us)"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2106,
   "documented": "2107",
   "name": "Density unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "g/cm³",
    "2": "kg/dm³",
    "3": "kg/l",
    "4": "kg/m³",
    "5": "SD4°C",
    "6": "SD15°C",
    "7": "SD20°C",
    "8": "SG4°C",
    "9": "SG15°C",
    "10": "SG20°C",
    "11": "lb/ft³",
    "12": "lb/gal (us)",
    "13": "lb/bbl (us;liq.)",
    "14": "lb/bbl (us;beer)",
    "15": "lb/bbl (us;oil)",
    "16": "lb/bbl (us;tank)",
    "17": "lb/gal (imp)",
    "18": "lb/bbl (imp;beer)",
    "19": "lb/bbl (imp;oil)",
    "21": "g/m³"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2108,
   "documented": "2109",
   "name": "Temperature unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "°C",
    "1": "K",
    "2": "°F",
    "3": "°R"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2546,
   "documented": "2547",
   "name": "Device ID",
   "description": "Four-digit hex device type code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2589,
   "documented": "2590 to 2591",
   "name": "Preset value 1",
   "description": "Start value used by the preset totalizer commands.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2591,
   "documented": "2592 to 2593",
   "name": "Preset value 2",
   "description": "Start value used by the preset totalizer commands.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2593,
   "documented": "2594 to 2595",
   "name": "Preset value 3",
   "description": "Start value used by the preset totalizer commands.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2599,
   "documented": "2600",
   "name": "Velocity unit",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "20": "ft/s",
    "21": "m/s"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2600,
   "documented": "2601",
   "name": "Totalizer 1 assign process variable",
   "description": "Which flow the totalizer adds up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Mass flow",
    "2": "Volume flow"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2604,
   "documented": "2605",
   "name": "Totalizer 1 operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Net",
    "1": "Forward",
    "2": "Reverse"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2605,
   "documented": "2606",
   "name": "Totalizer 1 failure behavior",
   "description": "Totalizer behaviour while a device alarm is active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hold",
    "1": "Continue",
    "2": "Last valid value + continue"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2607,
   "documented": "2608",
   "name": "Totalizer 1 control",
   "description": "Write to reset, preset, hold or run the totalizer.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Totalize",
    "1": "Reset + totalize",
    "2": "Preset + hold",
    "3": "Reset + hold",
    "4": "Preset + totalize",
    "5": "Hold"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2608,
   "documented": "2609",
   "name": "Reset all totalizers",
   "description": "Write 1 to reset all totalizers and keep counting.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cancel",
    "1": "Reset + totalize"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2609,
   "documented": "2610 to 2611",
   "name": "Totalizer 1 value",
   "description": "Current totalizer count in the totalizer unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2611,
   "documented": "2612 to 2613",
   "name": "Totalizer 1 overflow",
   "description": "Number of overflows, -32000 to 32000.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2731,
   "documented": "2732",
   "name": "Actual diagnostics",
   "description": "Currently active diagnostic event as an integer code.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2733,
   "documented": "2734",
   "name": "Previous diagnostics",
   "description": "Last diagnostic event before the current one.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2735,
   "documented": "2736",
   "name": "Diagnostics 1",
   "description": "Entry 1 of the diagnostic list.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2737,
   "documented": "2738",
   "name": "Diagnostics 2",
   "description": "Entry 2 of the diagnostic list.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2739,
   "documented": "2740",
   "name": "Diagnostics 3",
   "description": "Entry 3 of the diagnostic list.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2741,
   "documented": "2742",
   "name": "Diagnostics 4",
   "description": "Entry 4 of the diagnostic list.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2743,
   "documented": "2744",
   "name": "Diagnostics 5",
   "description": "Entry 5 of the diagnostic list.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2800,
   "documented": "2801",
   "name": "Totalizer 2 assign process variable",
   "description": "Which flow the totalizer adds up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Mass flow",
    "2": "Volume flow"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2804,
   "documented": "2805",
   "name": "Totalizer 2 operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Net",
    "1": "Forward",
    "2": "Reverse"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2805,
   "documented": "2806",
   "name": "Totalizer 2 failure behavior",
   "description": "Totalizer behaviour while a device alarm is active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hold",
    "1": "Continue",
    "2": "Last valid value + continue"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2807,
   "documented": "2808",
   "name": "Totalizer 2 control",
   "description": "Write to reset, preset, hold or run the totalizer.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Totalize",
    "1": "Reset + totalize",
    "2": "Preset + hold",
    "3": "Reset + hold",
    "4": "Preset + totalize",
    "5": "Hold"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2809,
   "documented": "2810 to 2811",
   "name": "Totalizer 2 value",
   "description": "Current totalizer count in the totalizer unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 2811,
   "documented": "2812 to 2813",
   "name": "Totalizer 2 overflow",
   "description": "Number of overflows, -32000 to 32000.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3000,
   "documented": "3001",
   "name": "Totalizer 3 assign process variable",
   "description": "Which flow the totalizer adds up.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Off",
    "1": "Mass flow",
    "2": "Volume flow"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3004,
   "documented": "3005",
   "name": "Totalizer 3 operation mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Net",
    "1": "Forward",
    "2": "Reverse"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3005,
   "documented": "3006",
   "name": "Totalizer 3 failure behavior",
   "description": "Totalizer behaviour while a device alarm is active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Hold",
    "1": "Continue",
    "2": "Last valid value + continue"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3007,
   "documented": "3008",
   "name": "Totalizer 3 control",
   "description": "Write to reset, preset, hold or run the totalizer.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Totalize",
    "1": "Reset + totalize",
    "2": "Preset + hold",
    "3": "Reset + hold",
    "4": "Preset + totalize",
    "5": "Hold"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3009,
   "documented": "3010 to 3011",
   "name": "Totalizer 3 value",
   "description": "Current totalizer count in the totalizer unit.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 3011,
   "documented": "3012 to 3013",
   "name": "Totalizer 3 overflow",
   "description": "Number of overflows, -32000 to 32000.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4480,
   "documented": "4481",
   "name": "Device revision",
   "description": "Four-digit hex device revision.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4550,
   "documented": "4551 to 4552",
   "name": "Acceptance rate",
   "description": "Share of accepted measurements, 0-100 %.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "%",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4603,
   "documented": "4604",
   "name": "Totalizer 1 unit",
   "description": "Engineering unit of the totalizer.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "cm³",
    "1": "dm³",
    "2": "m³",
    "3": "ml",
    "4": "l",
    "5": "hl",
    "6": "Ml Mega",
    "8": "af",
    "9": "ft³",
    "10": "fl oz (us)",
    "11": "gal (us)",
    "12": "Mgal (us)",
    "13": "bbl (us;liq.)",
    "14": "bbl (us;beer)",
    "15": "bbl (us;oil)",
    "16": "bbl (us;tank)",
    "17": "gal (imp)",
    "18": "Mgal (imp)",
    "19": "bbl (imp;beer)",
    "20": "bbl (imp;oil)",
    "22": "kgal (us)",
    "23": "Mft³",
    "50": "g",
    "51": "kg",
    "52": "t",
    "53": "oz",
    "54": "lb",
    "55": "STon",
    "111": "Mft³",
    "251": "None"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4604,
   "documented": "4605",
   "name": "Totalizer 2 unit",
   "description": "Engineering unit of the totalizer.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "cm³",
    "1": "dm³",
    "2": "m³",
    "3": "ml",
    "4": "l",
    "5": "hl",
    "6": "Ml Mega",
    "8": "af",
    "9": "ft³",
    "10": "fl oz (us)",
    "11": "gal (us)",
    "12": "Mgal (us)",
    "13": "bbl (us;liq.)",
    "14": "bbl (us;beer)",
    "15": "bbl (us;oil)",
    "16": "bbl (us;tank)",
    "17": "gal (imp)",
    "18": "Mgal (imp)",
    "19": "bbl (imp;beer)",
    "20": "bbl (imp;oil)",
    "22": "kgal (us)",
    "23": "Mft³",
    "50": "g",
    "51": "kg",
    "52": "t",
    "53": "oz",
    "54": "lb",
    "55": "STon",
    "111": "Mft³",
    "251": "None"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4605,
   "documented": "4606",
   "name": "Totalizer 3 unit",
   "description": "Engineering unit of the totalizer.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "cm³",
    "1": "dm³",
    "2": "m³",
    "3": "ml",
    "4": "l",
    "5": "hl",
    "6": "Ml Mega",
    "8": "af",
    "9": "ft³",
    "10": "fl oz (us)",
    "11": "gal (us)",
    "12": "Mgal (us)",
    "13": "bbl (us;liq.)",
    "14": "bbl (us;beer)",
    "15": "bbl (us;oil)",
    "16": "bbl (us;tank)",
    "17": "gal (imp)",
    "18": "Mgal (imp)",
    "19": "bbl (imp;beer)",
    "20": "bbl (imp;oil)",
    "22": "kgal (us)",
    "23": "Mft³",
    "50": "g",
    "51": "kg",
    "52": "t",
    "53": "oz",
    "54": "lb",
    "55": "STon",
    "111": "Mft³",
    "251": "None"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4909,
   "documented": "4910",
   "name": "Bus address",
   "description": "Modbus slave address, 1-247.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4911,
   "documented": "4912",
   "name": "Baudrate",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "baud",
   "access": "RW",
   "values": {
    "0": "1200",
    "1": "2400",
    "2": "4800",
    "3": "9600",
    "4": "19200",
    "5": "38400",
    "6": "57600",
    "7": "115200",
    "8": "230400"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4912,
   "documented": "4913",
   "name": "Data transfer mode",
   "description": "",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "RTU",
    "1": "ASCII"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4913,
   "documented": "4914",
   "name": "Parity",
   "description": "0 = Even, 1 = Odd; codes 2/3 (no parity) conflict in the manual.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4914,
   "documented": "4915",
   "name": "Byte order",
   "description": "Byte sequence for floats and strings (factory 1-0-3-2).",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "0-1-2-3",
    "1": "3-2-1-0",
    "2": "2-3-0-1",
    "3": "1-0-3-2"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4915,
   "documented": "4916 to 4917",
   "name": "Telegram delay",
   "description": "Reply delay after a request, 0-100 ms.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "ms",
   "access": "RW",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4919,
   "documented": "4920",
   "name": "Failure mode",
   "description": "Value sent for measured values while a diagnostic is active.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "1": "Last valid value",
    "255": "NaN value"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4958,
   "documented": "4959 to 4960",
   "name": "Signal strength",
   "description": "Ultrasonic signal strength (diagnostic).",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 4982,
   "documented": "4983 to 4984",
   "name": "Signal to noise ratio",
   "description": "",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6806,
   "documented": "6807",
   "name": "Fieldbus writing access",
   "description": "Allow or block writes over Modbus.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Read + write",
    "1": "Read only"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 6816,
   "documented": "6817",
   "name": "Device reset",
   "description": "Restart the device or return it to delivery settings.",
   "data_type": "UINT16",
   "length": 1,
   "word_order": null,
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "RW",
   "values": {
    "0": "Cancel",
    "1": "Restart device",
    "2": "To delivery settings",
    "25": "Restore S-DAT backup"
   },
   "bits": null
  },
  {
   "table": "holding_register",
   "address": 22771,
   "documented": "22772 to 22773",
   "name": "Turbulence",
   "description": "Turbulence indicator of the flow profile.",
   "data_type": "FLOAT32",
   "length": 2,
   "word_order": "CDAB",
   "scale": 1,
   "offset": 0,
   "scale_factor_ref": null,
   "units": "",
   "access": "R",
   "values": null,
   "bits": null
  }
 ],
 "integration": {
  "summary": "Read volume flow (wire 2006) and totalizer 1 (wire 2609) as CDAB floats with function 03 or 04; check actual diagnostics (wire 2731) and signal strength for clamp-on health. Reset totalizers through the totalizer control registers.",
  "minimum_registers": [
   {
    "table": "holding_register",
    "address": 2006,
    "why": "Volume flow"
   },
   {
    "table": "holding_register",
    "address": 2014,
    "why": "Flow velocity"
   },
   {
    "table": "holding_register",
    "address": 2609,
    "why": "Totalizer 1 value"
   },
   {
    "table": "holding_register",
    "address": 2102,
    "why": "Volume flow unit code"
   },
   {
    "table": "holding_register",
    "address": 4958,
    "why": "Signal strength"
   },
   {
    "table": "holding_register",
    "address": 2731,
    "why": "Active diagnostic"
   },
   {
    "table": "holding_register",
    "address": 2607,
    "why": "Totalizer 1 control"
   }
  ],
  "enable": "Modbus settings are under Expert > Communication > Modbus configuration. Fieldbus writing access (register 6807) must be Read + write for Modbus writes.",
  "watchdog": null,
  "quirks": [
   "Floats default to CDAB (byte order 1-0-3-2), selectable on the device.",
   "Failure mode 4920 chooses NaN or last valid value for measured values during a fault."
  ],
  "setup": [
   "Factory settings: address 247, 19200 baud, Even parity, RTU.",
   "Telegram delay can be raised for slow masters."
  ],
  "gotchas": [
   "Values are sent in the units set in the unit registers; read the unit registers at start-up.",
   "Clamp-on accuracy depends on the pipe and sensor setup done on the device; check signal strength and acceptance rate if values look wrong."
  ]
 },
 "page": "https://easymodbus.com/modbus-register-maps/endress-hauser/prosonic-flow-w-400-modbus",
 "address_note": "address = 0-based Modbus wire (PDU) address; documented = as printed in the source.",
 "note": "Re-typed from the manufacturer's public documentation (see source) and verified against it. Registers vary by firmware and options; verify against the live device before writing."
}