Equipment type
Pumps Modbus register maps
Updated 29 October 2026
5 pumps register maps from 3 manufacturers: Daikin, Grundfos, Wilo.
- Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface - Pump (booster system / multi-pump controller)
Grundfos Booster systems (Hydro MPC, Hydro Multi-E, Multi-B) via CIM 200 / CIM 500
Grundfos booster systems: Hydro MPC / Control MPC (CU 352), GENIECON MPC, Hydro Multi-B (CU 323), DDD (CU 354), Hydro Multi-E, TPED and MAGNA3-D twin pumps, with CIM/CIU 200, CIM/CIU 500 or SoftCIM.
Also known as: Hydro MPC, Control MPC, CU 352, GENIECON MPC, Hydro Multi-E, Hydro Multi-B, CU 323, DDD, CU 354, TPED, MAGNA3-D, CIM 200, CIM 500, SoftCIM Modbus TCP - Pump (chemical dosing pump)
Grundfos SMART Digital DDA dosing pump (SoftCIM, CIM 200 / CIM 500)
Grundfos SMART Digital DDA dosing pumps: DDA model C with built-in SoftCIM Modbus RTU/TCP, and DDA XL (or others) through a CIM 200 Modbus RTU or CIM 500 Modbus TCP module in a CIU 900, per functional profile 98473491 (09.2026).
Also known as: DDA, DDA S, DDA XL, DDA-C, DDA model C, SMART Digital S, SMART Digital XL, CIM 200, CIM 500, 98473491 - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080
Pumps: default communication settings
Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).
| Model | Transport | Unit ID | Serial | Word order | Documented addressing | Registers |
|---|---|---|---|---|---|---|
| DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps | RTU | Not stated | 9600 baud, 8N1 | 16-bit only | 0-based | 32 |
| Booster systems (Hydro MPC, Hydro Multi-E, Multi-B) via CIM 200 / CIM 500 | RTU/TCP | Not stated | 19200 baud, 8E1 | ABCD | 1-based | 127 |
| SMART Digital DDA dosing pump (SoftCIM, CIM 200 / CIM 500) | RTU/TCP | Not stated | 19200 baud, 8E1 | ABCD | 1-based | 58 |
| Para MAXO (built-in Modbus RTU) | RTU | 101 | 19200 baud, 8E1 | 16-bit only | 0-based | 28 |
| Stratos MAXO with CIF module Modbus RTU | RTU | Not stated | - | ABCD | 0-based | 56 |